Plan Review Stops For Permit 16080421 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2016-12-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-12-16 |
Time |
13:51 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-12-15 |
Time |
12:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-08-26 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-08-26 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-08-26 |
Time |
13:26 |
Sent To |
|
|
Notes |
2016-08-26 13:39:24 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1. PROVIDE SITE PLAN SHOWING REQUIRED PARKING, | | INCLUDING ACCESSIBLE PARKING. | | 2. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO MODULAR | | STRUCTURE. | | 3. PROVIDE ACCESSIBLE RAMP. | | | | PROVIDE A LEGIBLE PLAN TO PROVIDE THE FOLLOWING | | INFORMATION: | | TOTAL NUMBER OF PARKING SPACES | | NUMBER OF ACCESSIBLE SPACES ? PER TABLE 208.2 | | LOCATION OF ACCESSIBLE ENTRANCES | | LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES | | SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY | | ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE | | ENTRANCE | | | | SEE FBC 2010 ACCESSIBILITY 202.3 (ALTERATIONS), 208.2 | | (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE | | ROUTE). | | | | 402.2 COMPONENTS. | | ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR MORE OF THE | | FOLLOWING COMPONENTS: WALKING SURFACES WITH A RUNNING | | SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, CURB | | RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND | | PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE | | SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF | | CHAPTER 4 AND 208.3.1. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2016-10-13 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-10-13 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-10-13 |
Time |
08:48 |
Sent To |
|
|
Notes |
2016-10-13 08:49:40 | ELECTRICAL SUBMITTED SEPERATE TEMP ELECTRICAL PERMIT | | SETUP/ C/F ELECTRIC |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-08-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-08-26 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-08-26 |
Time |
13:01 |
Sent To |
|
|
Notes |
2016-08-26 13:04:51 | 1ST REVIEW: FBC 2014 5TH ED. | | | | FBC 107 - PROVIDE ELECTRICAL DETAILS FOR THE FEED TO | | THE MODULAR BUILDING. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-09-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-09-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-09-27 |
Time |
17:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2016-08-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-08-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-08-22 |
Time |
11:39 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-12-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-12-15 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-09-22 |
Time |
10:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-08-26 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-08-26 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-08-10 |
Time |
13:24 |
Sent To |
|
|
Notes |
2016-08-10 13:24:17 | ROUTED TO ZONING |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-10-21 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-10-21 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-10-21 |
Time |
14:09 |
Sent To |
|
|
Notes |
2016-10-21 14:14:46 | APPROVED WITH PROVISO | | | | 1. PROVIDE SIZE OF HOLDING TANK IF OVER 300 GAL PERMIT | | FROM HEALTH DEPT IS REQUIRED. | | 2. BACKFLOW FOR WATER SERVICE REQUIRED WITH SEPARATE | | PERMIT REQUIRED. | | 3. A SIGNED COPY OF CONTRACT FROM VENDOR WITH PUMP OUT | | SCHEDULE FOR HOLDING TANK. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-08-26 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-08-26 |
Time |
13:01 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-08-26 |
Time |
13:01 |
Sent To |
|
|
Notes |
2016-08-26 13:03:50 | 1ST REVIEW: FBC 2014 5TH ED. | | | | FBC 107 - PROVIDE PLUMBING DETAILS FOR SEWER CONNECTION | | OR OSTD, & POTABLE WATER CONNECTION.\. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2016-10-28 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-10-28 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-10-28 |
Time |
13:58 |
Sent To |
|
|
Notes |
2016-10-28 14:09:18 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 10.28.2016 | | PERMIT NO.: 16080421 | | ADDRESS: 3501 PARKER AVENUE | | CONTRACTOR/CONTACT: BRETT STRASSEL | | TELEPHONE NO.: 561.324.1127 | | SCOPE OF REVIEW: TEMPORARY CONSTRUCTION TRAILER | | ___________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ___________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. ALL CONSTRUCTION TRAILERS SHALL BE REMOVED WITHIN | | SEVEN DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE | | CITY AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | OCCUPANCY. | | | | 2. ALL LANDSCAPING (TREES, PALMS, SHRUBS, SOD, ETC.) | | THAT IS DAMAGED AS A RESULT OF CONSTRUCTION SHALL BE | | REPLACED WITH THE SAME SPECIES, OF EQUAL SIZE. | | | | 3. PRIOR TO THE REMOVAL OF ANY TREES / PALMS, A TREE | | ALTERATION PERMIT SHALL BE OBTAINED FROM THE | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION. | | | | 4. ALL TREES / PALMS WITHIN THE CONSTRUCTION ZONE THAT | | ARE PROPOSED TO REMAIN SHALL BE SURROUNDED BY A TREE | | PROTECTION BARRIER TO PREVENT DAMAGE. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2016-08-17 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-08-17 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-08-10 |
Time |
17:17 |
Sent To |
FIRE |
|
Notes |
2016-08-17 16:42:13 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 08.17.2016 | | PERMIT NO.: 16080421 | | ADDRESS: 3501 PARKER AVENUE | | CONTRACTOR/CONTACT: BRETT STRASSEL | | TELEPHONE NO.: 561.324.1127 | | SCOPE OF REVIEW: TEMPORARY CONSTRUCTION TRAILER | | ___________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ___________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. ALL CONSTRUCTION TRAILERS SHALL BE REMOVED WITHIN | | SEVEN DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE | | CITY AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF | | OCCUPANCY. | | | | 2. ALL LANDSCAPING (TREES, PALMS, SHRUBS, SOD, ETC.) | | THAT IS DAMAGED AS A RESULT OF CONSTRUCTION SHALL BE | | REPLACED WITH THE SAME SPECIES, OF EQUAL SIZE. | | | | 3. PRIOR TO THE REMOVAL OF ANY TREES / PALMS, A TREE | | ALTERATION PERMIT SHALL BE OBTAINED FROM THE | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION. | | | | 4. ALL TREES / PALMS WITHIN THE CONSTRUCTION ZONE THAT | | ARE PROPOSED TO REMAIN SHALL BE SURROUNDED BY A TREE | | PROTECTION BARRIER TO PREVENT DAMAGE. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|