Plan Review Details - Permit 16080378
Plan Review Stops For Permit 16080378
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-11 Cont ID  
Sent By vperez Date 2016-08-11 Time 07:54 Rev Time 0.00
Received By vperez Date 2016-08-11 Time 07:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-11-07 Cont ID  
Sent By tklarge Date 2016-11-07 Time 05:54 Rev Time 0.00
Received By tklarge Date 2016-11-07 Time 05:30 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-08-27 Cont ID  
Sent By tklarge Date 2016-08-27 Time 04:30 Rev Time 0.00
Received By tklarge Date 2016-08-27 Time 04:08 Sent To  
Notes
2016-08-27 04:30:151) THE GAS RISER SHOWS 3/4 INCH METALLIC PIPE AT THE
 METER . REFER TO 2014 FGC TABLE 402.4 (2) FOR CORRECT
 SIZING OF THE GAS SYSTEM.AS DRAWN, IT IS UNDERSIZED.
 2) SHOW THE LOCATION OF ANY DOORS OR WINDOWS ON THE
 FLOOR PLAN AND THE DISTANCE FROM THESE OPENINGS TO THE
 TANKLESS WATER HEATER. COMPLY WITH THE 2014 FGC SEC.
 503.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 04:56 Rev Time 0.00
Received By tklarge Date 2016-08-11 Time 04:37 Sent To  
Notes
2016-08-11 04:56:031) SUBMIT TWO COMPLETE SETS OF PLANS THAT ARE LEGIBLE
 AND CLEAR IN DETAIL. THE GAS DRAWINGS THAT WERE
 SUBMITTED ARE ILLEGIBLE AND UNACCEPTABLE.WPB AMEND. TO
 FBC SEC. 107.21.
 2) THE PLANS AND SPECIFICATIONS SHALL BE ASSEMBLED INTO
 TWO COMPLETE ORGANIZED SETS.WPB AMEND. TO FBC SEC.
 107.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-07 Cont ID  
Sent By tklarge Date 2016-11-07 Time 05:54 Rev Time 0.00
Received By tklarge Date 2016-11-02 Time 13:31 Sent To  
Notes
2016-11-03 13:31:16RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-27 Cont ID  
Sent By tklarge Date 2016-08-27 Time 04:30 Rev Time 0.00
Received By tklarge Date 2016-08-25 Time 14:00 Sent To  
Notes
2016-08-26 14:01:29TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 04:56 Rev Time 0.00
Received By tklarge Date 2016-08-09 Time 15:43 Sent To  
Notes
2016-08-09 15:43:15PLUMB <5K