Plan Review Details - Permit 16080355
Plan Review Stops For Permit 16080355
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 11:06 Rev Time 0.00
Received By albarran Date 2016-08-25 Time 09:45 Sent To I
Notes
2016-08-25 11:07:33ALL PREVIOUSLY MENTIONED EFFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By albarran Date 2016-08-09 Time 17:11 Rev Time 0.00
Received By albarran Date 2016-08-09 Time 16:05 Sent To I
Notes
2016-08-09 17:12:16ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 1383 10TH ST.
 JOB ADDRESS: 1383 10TH ST.
 DESCRIPTION: SERVICE CHANGE
 MASTER PERMIT: 16080355
  
 1. NEC 408.3: PANEL RATING OF 125 AMP IS NOT SUFFICIENT
 TO COMPLY WITH CODE REQUIREMENTS.
 2. RISER DIAGRAM & PANEL DESCRIPTION AS SUBMITTED DO
 NOT MATCH. CORRECT ACCORDINGLY.
 3. NEC 230.6: YOU SHALL PROVIDE A SITE/FLOOR PLAN SHOW
 THE LOCATION OF THE PANELS AND THE METER AND MAIN
 DISCONNECT IF ANY.
 4. NEC 230.70: YOU ARE REQUIRED TO PROVIDE A DISCONNECT
 FOR THE SERVICE CONDUCTORS BEFORE THEY ENTER THE
 PREMISES; THE PANEL AS DESCRIBED IS A MLO. CORRECT
 ACCORDINGLY.
 5. FBC-107.1: THE CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FBC SECTION 107.2.1 REQUIRE THAT ALL SUBMITTED
 DRAWINGS FOR PERMIT APPROVAL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. THE
 PLANS FOR THE ABOVE MENTIONED JOB DO NOT HAVE THE NAME
 OR SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 6. FBC-R314: YOU SHALL COME INTO COMPLIANCE WITH THE
 SMOKE DETECTOR REQUIRMENTS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-25 Cont ID  
Sent By albarran Date 2016-08-25 Time 11:08 Rev Time 0.00
Received By albarran Date 2016-08-17 Time 12:57 Sent To  
Notes
2016-08-25 11:09:548/25/16 ELECTRICAL REVIEW APPROVED. CONTRACTOR NOTIFIED
 VIA EMAIL. FILE SENT TO SMALL READY BIN "C". MA
2016-08-17 12:57:33MALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-09 Cont ID  
Sent By albarran Date 2016-08-09 Time 17:32 Rev Time 0.00
Received By albarran Date 2016-08-09 Time 12:47 Sent To  
Notes
2016-08-09 17:33:108/9/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED DRAWER
 "C". MA
2016-08-09 12:47:20ELEC <5K