Plan Review Details - Permit 16080314
Plan Review Stops For Permit 16080314
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By cthroop Date 2016-08-30 Time 12:51 Rev Time 0.00
Received By cthroop Date 2016-08-29 Time 14:40 Sent To M
Notes
2016-08-30 13:01:42BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. SUBMITTAL HAS ONLY ONE SET OF PLANS. PROVIDE TWO
 SETS OF PLANS REVIEWD AND APPROVED BY DESIGN
 PROFESSIONAL.
 2. ADDITIONAL PLAN SHEETS 10,12 & 13 OF 15 PROVIDED.
 PLEASE CLARIFY.
 3. PROVIDE DETAIL OF RAISED FLOOR AREAS FROM EOR.
 4. PROVIDE ROOF FRAMING PLAN.
 5. PROVIDE WIND DESIGN LOADS FOR NEW ROOFING.
 6. PROVIDE FASTENER SCHEDULE FOR NEW ROOFING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-09-29 Cont ID  
Sent By mvaldes Date 2016-09-29 Time 12:32 Rev Time 0.00
Received By mvaldes Date 2016-09-26 Time 14:04 Sent To  
Notes
2016-09-29 12:41:14REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] PLANS MUST BE SUBMITTED AS A PACKAGE WITH ALL
 ARCHITECTURAL, MECHANICAL, PLUMBING, ALONG WITH
 ELECTRICAL SHEETS IN ORDER TO COMPLETE A QUALITY
 REVIEW. FBC 107
  
 2] NEW ELECTRICAL PLANS DON'T MATCH THE DESIGN OF
 RECORD INCORRECT SHEET #, WALL CONFIGURATION CHANGES,
 AND ETC.
  
 3] MISSING A SMOKE ALARM IN THE VICINITY OUTSIDE OF
 EACH SLEEPING AREA ( BEDROOMS ). FBC-R 314.3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By mvaldes Date 2016-08-15 Time 10:43 Rev Time 0.00
Received By mvaldes Date 2016-08-15 Time 09:23 Sent To  
Notes
2016-08-15 11:15:34JOB PERMIT NUMBER: 16080314
 JOB ADDRESS: 370 MARLBOROUGH RD.
 WEST PALM BEACH FLORIDA
 DATE: AUGUST 15, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1) THE SMALL ELECTRICAL SHEETS SHALL BE A MINIMUM 1/8''
 SCALE FOR THE QUALITY OF THE REVIEW. FBC 107
 2) AT LEAST ONE WALL SWITCHED CONTROLLED LIGHTING
 OUTLET SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. FBC-R SECTION E3903.3
 3) SMOKE ALARMS REQUIRED PER FBC-R 314 & CARBON
 MONOXIDE ALARMS REQUIRED PER FBC-R315 [ DUE TO
 FIRE-PLACE ]. VERIFY ALL LOCATIONS REQUIRED BY CODE.
 4) ALL NEWLY INSTALLED RECEPTACLES SHALL BE
 TAMPER-RESISTANT. FBC-R SECTION E4002.14 [ A NOTE WILL
 SUFFICE ]
 5) ALL NEWLY MODIFIED CIRCUITS SHALL COMPLY WITH AFCI
 PROTECTION IN AREAS REQUIRED. FBC-R SECTION E3902.13 [
 A NOTE WILL SUFFICE ]
 6) INSTALL AN OUTLET IN THE FRONT AND BACK OF THE
 HOUSE. THE OUTDOOR RECEPTACLE SHALL BE GFCI PROTECTED.
 FBC-R SECTION E3901.7
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED TO
 PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING EACH
 ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL FORM.
 THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S
 COMMENTS AND YOUR RESPONSE OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By tklarge Date 2016-08-29 Time 11:34 Rev Time 0.00
Received By tklarge Date 2016-08-29 Time 11:32 Sent To  
Notes
2016-08-29 11:34:301) A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED ON THE
 GAS BECAUSE THE TYPE OF PIPE BEING INSTALLED WAS NOT
 INDICATED ON THE GAS PLAN.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
 3.) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 5) ) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3, FBCR SEC. G 2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-08-24 Cont ID  
Sent By fmittner Date 2016-08-24 Time 11:28 Rev Time 0.00
Received By fmittner Date 2016-08-24 Time 11:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-29 Cont ID  
Sent By mvaldes Date 2016-09-29 Time 12:41 Rev Time 0.00
Received By mvaldes Date 2016-09-22 Time 10:53 Sent To  
Notes
2016-09-23 10:53:14RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-31 Cont ID  
Sent By cpuell Date 2016-08-31 Time 09:08 Rev Time 0.00
Received By cpuell Date 2016-08-08 Time 12:37 Sent To  
Notes
2016-08-09 12:37:24R26

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By jvalido Date 2016-08-30 Time 18:30 Rev Time 0.00
Received By jvalido Date 2016-08-30 Time 18:26 Sent To  
Notes
2016-08-30 18:28:34CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE (2) SETS OF MECHANICAL PLANS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-29 Cont ID  
Sent By tklarge Date 2016-08-29 Time 12:42 Rev Time 0.00
Received By tklarge Date 2016-08-29 Time 09:24 Sent To  
Notes
2016-08-29 11:55:151) SUBMIT A PROPOSED SECOND FLOOR PLAN FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) TWO OF THE SUBMITTED RISER DIAGRAMS SHOWS A SHOWER
 AND THERE IS NO SHOWER ON THE FIRST FLOOR.CLARIFY.
 3) THE RISERS SHOW A "FUTURE 2ND FLR." RISER. THERE ARE
 EXISTING PLUMBING FIXTURES ON THE 2ND FLOOR SO PLEASE
 EXPLAIN "FUTURE 2ND FLOOR".
 4) SUBMIT A SANITARY AND WATER RISER FOR ALL THE
 CHANGES BEING MADE TO THE SANITARY SYSTEM ON BOTH
 FLOORS. INCLUDE THE PLUMBING FOR THE WET BARS. IF NO
 WPB AMEND. TO FBC SEC. 107.3.5.3.
 5) THE LOCATION OF THE WASHER AND DRYER ONSHT. 5 OF 15
 DOES NOT CORRELATE WITH THE LOCATION ON SHT.13 OF 15.
 CLARIFY.
 6) THE LOCATION OF THE WET BARS ON SHT. 5 DOES NOT
 CORRELATE WITH SHT. 13. CLARIFY.
 7) THE RISERS ON SHT.12 ARE TOO SMALL TO READ. DELETE
 THESE RISERS IF YOU ARE SUBMITTING 8 1/2 X 11 DIAGRAMS.
 8) SHT. 12 IS LACKING INFORMATION AS TO THE SCOPE OF
 WORK BEING DONE. SUBMIT A SET OF PLANS THAT CLEARLY
 SHOWS THE ENTIRE SCOPE OF PLUMBING WORK TO BE DONE. WPB
 AMEND. TO FBC SEC. 107.2.1.
 9) SUBMIT TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-30 Cont ID  
Sent By cthroop Date 2016-08-30 Time 12:50 Rev Time 0.00
Received By cthroop Date 2016-08-30 Time 12:50 Sent To  
Notes
2016-08-30 12:51:45BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-24 Cont ID  
Sent By fmittner Date 2016-08-24 Time 11:28 Rev Time 0.00
Received By fmittner Date 2016-08-24 Time 11:28 Sent To  
Notes
***NONE***