Plan Review Details - Permit 16080300
Plan Review Stops For Permit 16080300
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-05 Cont ID  
Sent By   Date 2016-11-05 Time   Rev Time 0.00
Received By jwitmer Date 2016-11-05 Time 06:25 Sent To  
Notes
2016-11-05 07:10:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080300
 ADD: 5016 SOUTH DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-762-2713
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. NOV. 05/2016
 ACTION: BUILDING PROVISO
  
 1) PROVISO: SHEET SP-1 SEPARATE PERMITS ARE REQUIRED
 FOR PAVING AND STRIPPING, LANDSCAPE, IRRIGATION,
 AWNINGS AND SIGNS ARE UNDER SEPARATE PERMIT, REVIEWS
 AND FEES. 105.1 REQUIRED PERMITS.
  
 2) PROVISO: SHEET SP-1 SHOWS WORK ON THE LOT TO THE
 NORTH BEING ACCOMPLISHED UNDER THIS PERMIT. PLEASE NOTE
 THE LOT TO THE NORTH 5008 S. DIXIE IS ALSO OWNER BY A
 DIFFERENT OWNER AND WOULD REQUIRE A SEPARATE
 PERMIT.105.1 REQUIRED PERMITS.
  
 3) PROVISO: DEFERRED SUBMITTAL : 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. DEFERRED SUBMITTAL ITEMS
 SHALL NOT BE INSTALLED UNTIL THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By jwitmer Date 2016-09-07 Time 17:25 Rev Time 0.00
Received By jwitmer Date 2016-09-07 Time 14:18 Sent To  
Notes
2016-09-07 17:11:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080300
 ADD: 5016 SOUTH DIXIE HWY.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-762-2713
 E-MAIL: NO E-MAIL ADDRESS PROVIDED FOR
 COMMUNICATION!!!!!!!!!
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 07/2016
 ACTION: DENIED
  
 1) THE COVERSHEET UNDER THE HEADING PROJECT INFORMATION
 LIST THIS AS A BUSINESS OCCUPANCY, TRAINING AND SKILL
 DEVELOPMENT, NOT ASSOCIATED WITH A SCHOOL. DEPENDING ON
 THE AGE OF THE STUDENTS THIS OCCUPANCY COULD BE ANY OF
 THE THREE, DAY CARE I-4 , EDUCATIONAL OR BUSINESS ?
 2014 FBC-B ,308.6 305.1 & B 304.1.
 PLEASE PROVIDE THE AGE GROUP OF THE STUDENTS, IF THE
 BUILDING IS TO BE USED BY MULTIPLE AGE GROUPS, THEN IT
 WOULD BE CONSIDERED A MIXED USE OCCUPANCY. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) SHEET SP-1 SEPARATE PERMITS ARE REQUIRED FOR PAVING
 AND STRIPPING, LANDSCAPE, IRRIGATION, AWNINGS AND SIGNS
 ARE UNDER SEPARATE PERMIT, REVIEWS AND FEES. 105.1
 REQUIRED PERMITS.
  
 3) SHEET SP-1 SHOWS WORK ON THE LOT TO THE NORTH BEING
 ACCOMPLISHED UNDER THIS PERMIT. PLEASE NOTE THE LOT TO
 THE NORTH 5008 S. DIXIE IS ALSO OWNER BY A DIFFERENT
 OWNER AND WOULD REQUIRE A SEPARATE PERMIT.
 105.1 REQUIRED PERMITS.
  
 4) BOTH SHEETS SP-1 AND S-1 SHOW A NEW ACCESSIBLE
 PARKING SPACE, PLEASE SEE THE CITY OF WEST PALM BEACH
 MUNI CODE SECTION 94-485 FOR THE REQUIRED COLOR AND
 STRIPING OF AN ACCESSIBLE PARKING SPACE AND ACCESS
 AISLE.
 ACCESS. CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE
 MARKED SO AS TO DISCOURAGE PARKING IN THEM.
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED.
  
 5) SHEET S-1 WILL NEED TO SHOW THE ELEVATION OF THE 2
 CORNER OF THE ACCESSIBLE PARKING SPACE AND THE OPPOSITE
 CORNERS OF THE ACCESS AISLE FOR COMPLIANCE WITH:
 ACCESS. CODE 502.4 FLOOR OR GROUND SURFACES. PARKING
 SPACES AND ACCESS AISLES SERVING THEM SHALL COMPLY WITH
 302. ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE
 PARKING SPACES THEY SERVE. CHANGES IN LEVEL ARE NOT
 PERMITTED. EXCEPTION: SLOPES NOT STEEPER THAN 1:48
 SHALL BE PERMITTED.
  
 6) SHEET S-1 THE BOTTOM PORTION OF THE RAMP. THE BOTTOM
 LANDING HAS A ELEVATION MARK OF 15.10 FT., THE
 MID-LANDING A ELEVATION MARK OF 15.53 FT. MIDWAY UP THE
 RAMP THERE IS AN ELEVATION MARKED 15.03? IS THIS A
 TYPO? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
 7) SHEET S-2 SHOWS THE NEW ACCESSIBLE RAMP A SECTION
 4/S-3. THIS IS SECTION THROUGH THE RAMP IN A NORTH
 SOUTH DIRECTION. WHEN VIEWING THIS DETAIL THERE SHOWS A
 HANDRAIL SYSTEM, ALSO SEE SHEET A2 DETAIL 6. THERE IS A
 NOTE THAT THE ADA APPROVED HANDRAIL IS TO BE APPROVED
 BY THE OWNER.
 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING REQUIREMENTS
 FOR HANDRAILS FOR RAMPS:
 2014 ACCESS. CODE 505.3 ? 505.10.2. ALL SECTIONS.
  
 8) SHEET A1 INDICATES A NEW DOOR OPENING AND THE
 EXISTING WINDOWS BEING REPLACED, SHEET S3 PROVIDES
 STRUCTURAL DETAILS FOR THE NEW DOOR OPENING AND A
 INFILL OF A DOOR TO NEW WINDOW OPENING. THE PLANS DO
 NOT PROVIDE THE WIND DESIGN CRITERIA;
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 8.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 8.2. RISK CATEGORY.
  
 8.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 8.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 8.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 9) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 10) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) SHEET A100 THE ACCESSIBLE RESTROOM 107 HAS 2 WATER
 CLOSETS IN THE ONE RESTROOM. THE SMALLER CHILDS WATER
 CLOSET DOES NOT MEET THE SIDE CLEARANCE REQUIREMENTS OF
 ACCESS. CODE 604.3.1 BOTH THE OTHER WATER CLOSET AND
 DIAPER CHANGING TABLE ARE IN THE WAY.
  
 12) PLEASE NOTE CHILDRENS WATER CLOSETS ARE AGE
 SPECIFIC TO THE AGE OF THE CHILDREN SEE 604.9 AND
 ADVISORY 604.9. FOR CENTERLINES, TOILET SEAT HEIGHT,
 GRAB BAR HEIGHT AND DISPENSER HEIGHTS.
  
 13) ACCESSIBILITY DETAIL SHEET A000:
 13A) THE WATER CLOSET GRAB RAILS ARE SHOWN AS BEING
 MEASURED FROM THE CENTERLINE OF THE GRAB BAR. PLEASE
 UPDATE PLANS THE 2014 FBC-ACCESS. CODE 609.4 MEASURES
 THE GRAB BAR FROM THE TOP OF THE GRASPING SURFACE NOT
 THE CENTERLINE.
  
 13B) THE TYPICAL HANDICAPPED SIGNAGE IS SHOWN CENTERED
 AT THE HEIGHT OF 5 FOOT.
 2014 ACCESS. CODE 703.4.1 HEIGHT ABOVE FINISH FLOOR OR
 GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48
 INCHES (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 LOWEST TACTILE CHARACTER AND 60 INCHES (1525 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE HIGHEST TACTILE
 CHARACTER.
  
 14) FURTHER COMMENTS MAY BE FORTH COMING DEPENDING ON
 THE MECHANICAL REVIEW COMMENTS ADDITIONAL FRESHAIR WILL
 BE REQUIED AND POSSIBLY ADDTIONAL A/C EQUIPMENT ON THE
 ROOF TOP, 2014 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS
  
 15) THIS PLAN MAY END UP A CHANGE IN OCCUPANCY IF SO
 THEN IMPACT FEE ASSESSMENT SHALL OCCUR. BEFORE A PERMIT
 TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID
 TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2016-08-19 15:18:36PRODUCT APPROVAL TO BE DEFERRED PER EMAIL FROM STEVEN
 VITEK SR. PROJECT MANAGER STEVEN E. MYOTT, ARCHITECT
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-26 Cont ID  
Sent By vperez Date 2016-10-26 Time 11:18 Rev Time 0.00
Received By vperez Date 2016-10-26 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-09-06 Cont ID  
Sent By vperez Date 2016-09-06 Time 15:30 Rev Time 0.00
Received By vperez Date 2016-09-06 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-27 Cont ID  
Sent By pleduc Date 2016-10-27 Time   Rev Time 0.00
Received By pleduc Date 2016-10-26 Time 16:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-10 Cont ID  
Sent By wjolin Date 2016-08-10 Time 11:19 Rev Time 0.00
Received By wjolin Date 2016-08-10 Time 11:00 Sent To  
Notes
2016-08-10 11:14:325016 SOUTH DIXIE HIGHWAY
 PERMIT #16080300
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A120: OPEN STUDIO #111 & #113 FEATURES SLIDING
 EGRESS DOORS IN LIEU OF SWINGING DOORS. THE FLOOR PLAN
 INDICATES 14 SEATS. PER NFPA 101 SECTION
 7.2.1.4.1(4)(D) "BUSINESS AREAS WITH AN OCCUPANT LOAD
 NOT EXCEEDING 10 CONTAIN ONLY LOW OR ORDINARY HAZARD
 CONTENTS, DOOR OPENINGS TO SUCH AREAS SHALL BE
 PERMITTED TO BE HORIZONTAL-SLIDING DOOR ASSEMBLIES."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2016-11-15 Time 14:07 Sent To  
Notes
2016-11-16 14:07:53RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-05 Cont ID  
Sent By   Date 2016-11-05 Time   Rev Time 0.00
Received By lmarchan Date 2016-10-19 Time 11:58 Sent To  
Notes
2016-10-21 11:59:53C06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-07 Cont ID  
Sent By   Date 2016-09-07 Time   Rev Time 0.00
Received By lmarchan Date 2016-08-08 Time 12:41 Sent To  
Notes
2016-08-09 12:42:07C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-12-27 Cont ID  
Sent By skennedy Date 2016-12-27 Time 10:28 Rev Time 0.00
Received By skennedy Date 2016-12-27 Time 10:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-11-29 Cont ID  
Sent By jwitmer Date 2016-11-29 Time 10:11 Rev Time 0.00
Received By jwitmer Date 2016-11-29 Time 10:10 Sent To  
Notes
2016-11-29 10:11:11BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By jwitmer Date 2016-09-07 Time 17:11 Rev Time 0.00
Received By jwitmer Date 2016-09-07 Time 14:20 Sent To  
Notes
2016-09-07 17:10:47BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-11-18 Cont ID  
Sent By ccole Date 2016-11-18 Time 15:39 Rev Time 0.00
Received By ccole Date 2016-11-18 Time 15:39 Sent To  
Notes
2016-11-18 15:43:48MECHANICAL PROVISOS:
 11/18/16
  
 1) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE FABRIC
 DUCTWORK WITH REVIEW SIGNATURE BY THE ENGINEER OF
 RECORD, OR REVISE PLANS TO PROVIDE ALTERNATE APPROVED
 DUCTWORK.
  
 2) RELOCATE THE OUTSIDE AIR INLETS FOR AHU-1 & 2 TO A
 LOCATION THAT IS A MINIMUM OF 10' FROM STREETS,
 A;LLEYS, OR PARKLING LOTS- SECTION 401.4 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-28 Cont ID  
Sent By ccole Date 2016-10-28 Time 08:43 Rev Time 0.00
Received By ccole Date 2016-10-28 Time 06:48 Sent To  
Notes
2016-10-28 08:56:552ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080300
 10/28/16
  
 1) THE LETTER FROM ROCAMAR ENGINEERING HAS BEEN
 FORWARDED TO ROBERT BROWN- BUILDING OFFICIAL FOR
 REVIEW. FINAL APPROVAL OF THE MECHANICAL PLANS ARE
 CONTINGENT ON APPROVAL OF THE LETTER REQUEST TO EXCLUDE
 EXHAUST VENTILATION FOR THE ART CLASSROOMS, AND TO
 RETAIN THE CURRENT MECHANICAL DESIGN.
  
 2) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE PER
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. NOTE 20
 ON SHEET A100 IS INDICATING WOOD.
  
 3) PLEASE PROVIDE ON THE PLAN THE FABRIC DUCT
 MANUFACTURER AND SUBMIT SPECIFICATIONS WITH APPROVAL
 SIGNATURE BY THE EOR- SECTION 603.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 12:18 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 12:18 Sent To  
Notes
2016-09-07 12:42:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080300
 9/7/16
  
 1) REFER TO TABLE 403.3: ART CLASSROOMS ARE REQUIRED TO
 HAVE EXHAUST AT A RATE OF 0.7 CFMS PER SQ. FT. AND
 RECIRCULATION OF AIR FROM THE SPACES IS PROHIBITED PER
 FOOTNOTE G, EXCEPT THAT RECIRCULATION SHALL BE
 PERMITTED WHERE THE RESULTING SUPPLY AIRSTREAM CONSISTS
 OF NOT MORE THAN 10 PERCENT AIR RECIRCULATED FROM THESE
 SPACES (SEE SECTION 403.2.1, ITEMS 2 AND 4). PLEASE
 REVISE THE PLANS AND VENTILATION CALCULATIONS
 ACCORDINGLY, IDENTIFY THE SPACES USE FOR ART
 INSTRUCTION, AND SHOW THE REQUIRED EXHAUST SYSTEMS.
  
 2) THE SUBMITTED COMCHECK COMPLIANCE CERTIFICATE
 INDICATES RTU-1 FOR THE ART SECTION, HOWEVER THE PLANS
 ARE INDICTICATING TWO SPLIT AC SYSTEMS- PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-03 Cont ID  
Sent By gjohnson Date 2016-11-03 Time 12:44 Rev Time 0.00
Received By gjohnson Date 2016-11-03 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-09-07 Cont ID  
Sent By gjohnson Date 2016-09-07 Time 13:45 Rev Time 0.00
Received By gjohnson Date 2016-09-07 Time 13:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-28 Cont ID  
Sent By njwira Date 2016-10-28 Time 16:09 Rev Time 0.00
Received By njwira Date 2016-10-28 Time 15:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By njwira Date 2016-08-11 Time 16:24 Rev Time 0.00
Received By njwira Date 2016-08-10 Time 17:12 Sent To  
Notes
2016-08-11 16:29:318/11/16- FAILED
  
 ZONE- NC NEIGHBORHOOD COMMERCIAL
  
 FAILED
 1. PLEASE PROVIDE DRAWINGS FOR CURB CUT IT MUST BE
 20FT. OR LESS AND A 3FT. SIDE SETBACK.
  
 PASSED
 1. 5 REQUIRED PARKING SPACES 5 PARKING SPACES PROVIDED.
 2. 1 HANDICAPPED SPACE PROVIDED ONE HANDICAPPED SPACE
 PROVIDED.
 3. 9FT. WIDE REGULAR SPACE MEETS THE 8FT. WIDE SPACE
 REQUIRED.
 4. 18FT. LONG REGULAR PARKING SPACE PROVIDED 16FT. LONG
 REQUIRED.
 5. HANDICAPPED SPACE MEETS THE 12FT. WIDE 16FT. LONG
 SPACE REQUIREMENT.
 6. GROUND COVERAGE IS 32.53% MEETING THE 60%
 REQUIREMENT.
 7. 18.14% LANDSCAPING MEETING THE 15% LANDSCAPING
 REQUIREMENT.
 8. ONE(1)STORY BUILDING MEETING THE ONE 30FT. HEIGHT
 LIMIT.
 9. MORE THAN 10FT. BUILDING SEPORATION.
 10. BIKE RACK BEING ADDED.
 11. DIRECTIONAL SIGNS INCLUDED.