Plan Review Details - Permit 16080298
Plan Review Stops For Permit 16080298
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-15 Cont ID  
Sent By ccole Date 2016-09-15 Time 10:02 Rev Time 0.00
Received By ccole Date 2016-09-13 Time 11:23 Sent To  
Notes
2016-09-14 11:23:38RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-30 Cont ID  
Sent By ccole Date 2016-08-30 Time 10:14 Rev Time 0.00
Received By ccole Date 2016-08-26 Time 11:04 Sent To  
Notes
2016-08-29 11:04:26RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-16 Cont ID  
Sent By ccole Date 2016-08-16 Time 07:52 Rev Time 0.00
Received By ccole Date 2016-08-12 Time 16:17 Sent To  
Notes
2016-08-12 16:17:42RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-09 Cont ID  
Sent By ccole Date 2016-08-09 Time 08:54 Rev Time 0.00
Received By ccole Date 2016-08-08 Time 14:49 Sent To  
Notes
2016-08-08 14:49:47MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-09-15 Cont ID  
Sent By ccole Date 2016-09-15 Time 10:03 Rev Time 0.00
Received By ccole Date 2016-09-15 Time 10:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-08-30 Cont ID  
Sent By ccole Date 2016-08-30 Time 10:04 Rev Time 0.00
Received By ccole Date 2016-08-30 Time 10:04 Sent To  
Notes
2016-08-30 10:14:031ST REVIEW FBC-2014 MECHANICAL
 PERMIT 316080298
 8/30/16
  
 1) THE RESUBMITTED PLANS MUST BEAR THE ORIGINAL
 SIGNATURE AND SEAL OF THE ARCHITECT ANTHONY A.
 HARRINGTON AIA- REFER TO SECTION 61G1-16.003 FLORIDA
 ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-16 Cont ID  
Sent By ccole Date 2016-08-16 Time 07:37 Rev Time 0.00
Received By ccole Date 2016-08-16 Time 07:37 Sent To  
Notes
2016-08-16 07:52:342ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080298
 8/16/16
  
 1) REFER TO SECTION 501.2 FBC-14 MECHANICAL. THE DRYER
 EXHAUST AND THE KITCHEN HOOD EXHAUST CAN NOT BE IN THE
 SAME CHASE AS THE BATHROOM EXHAUST- PLEASE CORRECT.
  
 2) INDICATE THE DIMENSIONS OF THE MAIN SUPPLY PLENUM
 AND VERIFY IT IS SIZED LARGE ENOUGH FOR 1600 CFMS.
 PLEASE NOTE THAT A 35X5" DUCT IS UNDERSIZED PER ASHRAE
 APPROVED DUCTULATORS.
  
 3) NOTE #2 IS INDICATING THE NEW CEILING HEIGHT WILL BE
 7 FT. PLEASE SEE SECTION 1208.2 FBC-14 BUILDING AND
 VERIFY THAT THE 7 FT. CEILING HEIGHT IS LIMITED TO THE
 KITCHEN, THE BATHROOMS, THE LAUNDRY ROOM, AND STORAGE
 ROOMS.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER.
 PLEAS NOTE MAKEUP AIR MAY BE REQUIRED PER SECTION
 504.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By ccole Date 2016-08-09 Time 09:35 Rev Time 0.00
Received By ccole Date 2016-08-09 Time 08:54 Sent To  
Notes
2016-08-09 09:16:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080298
 8/9/16
  
 1) PLEASE ENLARGE THE PRINT SO THAT ALL RIGID AND FLEX
 DUCT SIZES, DIFFUSER SIZES, AND SUPPLY CFMS CAN BE SEEN
 CLEARLY FOR REVIEW.
  
 2) THE RETURN AIR SYSTEM APPEARS TO BE AN ABOVE-CEILING
 RETURN AIR PLENUM. PLEASE PLACE A NOTE ON THE PLAN TO
 CLEARLY IDENTIFY IT AS SUCH, AND REFER TO SECTION
 606.2.2.1 FOR MATERIALS WITHIN PLENUMS.
  
 3) INDICATE HOW AIR IS BEING RETURNED FROM THE LIVING
 ROOM AND BREAKFAST ROOM. DOES THE HALL CLOSET HAVE A
 LOUVERED DOOR AND A RETURN GRILL IN THE CEILING? PLEASE
 SEE SECTION C403.2.7.2 FOR MECHANICAL CLOSET
 COMPLIANCE.
  
 4) CLARIFY THE PURPOSE OF THE HOOD EXHAUST IN THE
 LAUNDRY ROOM, INDICATE THE MAKE AND MODEL OF THE
 APPLIANCE IT IS SERVING. PLEASE NOTE THAT IF WHAT IS
 DEPICTED IS DRYER EXHAUST, THEN THE EXHAUST DUCT SHALL
 BE MINIMUM 4" IN DIAMETER PER SECTION 504.6.1.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 WASHER/DRYER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  