Plan Review Details - Permit 16080290
Plan Review Stops For Permit 16080290
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-07 Cont ID  
Sent By jwitmer Date 2016-11-07 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2016-11-07 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-14 Cont ID  
Sent By jwitmer Date 2016-10-14 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2016-10-14 Time 07:31 Sent To  
Notes
2016-10-14 07:49:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080290
 ADD: 321 S. DIXIE HWY.
 CONT: MASTER CONTRACTOR
 TEL: 561-248-5498
 E-MAIL: MASTERCONTRACTORS@??????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. AUGUST 13/ 2016
 ACTION: DENIED
  
 1) COMPLIED. THE COVERSHEET INDICATES THIS 2 STORY
 BUILDING IS A BUILDING TYPE IIA-SPRINKLERED. PLEASE
 NOTE THIS 2 STORY BUILDING WAS BUILT IN 1925 THE 1ST
 FLOOR CONSISTING OF EITHER BUSINESS AND OR MERCANTILE.
 THIS BUILDING TYPE IS NOT A TYPE IIA BUILDING, MORE
 LIKELY A TYPE VB. A TYPE IIA MEANS THERE IS NO WOOD IN
 THE STRUCTURE AND ALL OF THE STRUCTURAL MEMBERS ARE 1
 HOUR FIRE PROTECTED PER TABLE 601.
  
 2)2ND REQUEST. PLEASE PROVIDE HOW MANY SQUARE FEET MAKE
 UP THE RETAIL PORTION OF THIS TENANT SPACE TO SEE IF IT
 IS A MIXED USE OCCUPANCY. THE COVERSHEET ALSO LIST THE
 OCCUPANCY TYPE AS BUSINESS/ RETAIL, THE TENANCY SQUARE
 FOOTAGE OF 827 AND AN OCCUPANT LOAD OF 13. PLEASE
 PROVIDE THE SQUARE FOOTAGE FOR THE BEAUTY SALOON
 PORTION THAT WILL BE BUSINESS OCCUPANCY AND THE POTION
 THAT WILL BE MERCANTILE OCCUPANCY. THIS TENANCY MAY BE
 CLASSIFIED AS A MIXED USE OCCUPANCY.
 2014 FBC-B 508.2.1 AREA LIMITATIONS. AGGREGATE
 ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10
 PERCENT OF THE BUILDING AREA OF THE STORY (TENANT
 SPACE) IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED
 THE TABULAR VALUES IN TABLE 503, WITHOUT BUILDING AREA
 INCREASES IN ACCORDANCE WITH SECTION 506 FOR SUCH
 ACCESSORY OCCUPANCIES.
  
 3-4) COMPLIED.
  
 5) SEMI COMPLIED. SHEET A-1. PLEASE NOTE THERE IS AN
 EXISTING STAIR TO A TENANCY ABOVE THIS UNIT. THE PLANS
 INDICATE AN EXISTING WATER HEATER BELOW THE STAIR
 ENCLOSURE. PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B
 1009.9.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE PLANS
 SHOW 2 OF THE 3 WALLS BEING FIRE RATED AND THE CEILING
 OF THE CLOSET NEEDS TO BE FIRE RATED AS WELL.
 THE WALLS, SOFFIT AND OR CEILING WITHIN ENCLOSED USABLE
 SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-13 Cont ID  
Sent By jwitmer Date 2016-08-13 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2016-08-13 Time 09:57 Sent To  
Notes
2016-08-13 10:57:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080290
 ADD: 321 S. DIXIE HWY.
 CONT: MASTER CONTRACTOR
 TEL: 561-248-5498
 E-MAIL: MASTERCONTRACTORS@??????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. AUGUST 13/ 2016
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THIS 2 STORY BUILDING IS A
 BUILDING TYPE IIA-SPRINKLERED. PLEASE NOTE THIS 2 STORY
 BUILDING WAS BUILT IN 1925 THE 1ST FLOOR CONSISTING OF
 EITHER BUSINESS AND OR MERCANTILE. THIS BUILDING TYPE
 IS NOT A TYPE IIA BUILDING, MORE LIKELY A TYPE VB. A
 TYPE IIA MEANS THERE IS NO WOOD IN THE STRUCTURE AND
 ALL OF THE STRUCTURAL MEMBERS ARE 1 HOUR FIRE PROTECTED
 PER TABLE 601.
  
 2) THE COVERSHEET ALSO LIST THE OCCUPANCY TYPE AS
 BUSINESS/ RETAIL, THE TENANCY SQUARE FOOTAGE OF 827 AND
 AN OCCUPANT LOAD OF 13. PLEASE PROVIDE THE SQUARE
 FOOTAGE FOR THE BEAUTY SALOON PORTION THAT WILL BE
 BUSINESS OCCUPANCY AND THE POTION THAT WILL BE
 MERCANTILE OCCUPANCY. THIS TENANCY MAY BE CLASSIFIED AS
 A MIXED USE OCCUPANCY.
 2014 FBC-B 508.2.1 AREA LIMITATIONS. AGGREGATE
 ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10
 PERCENT OF THE BUILDING AREA OF THE STORY (TENANT
 SPACE) IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED
 THE TABULAR VALUES IN TABLE 503, WITHOUT BUILDING AREA
 INCREASES IN ACCORDANCE WITH SECTION 506 FOR SUCH
 ACCESSORY OCCUPANCIES.
  
 3) THE COVERSHEET LIST 13 OCCUPANTS BUT THE FLOOR PLAN
 INDICATES IF EACH CHAIR IS TAKEN BY AN OCCUPANT AND
 BEAUTICIAN AT EACH STATION THE OCCUPANT LOAD WOULD BE
 CLOSER TO 30 OCCUPANTS.
 2014 FBC-B 1004.2 INCREASED OCCUPANT LOAD. THE OCCUPANT
 LOAD PERMITTED IN ANY BUILDING, OR PORTION THEREOF, IS
 PERMITTED TO BE INCREASED FROM THAT NUMBER ESTABLISHED
 FOR THE OCCUPANCIES IN TABLE 1004.1.2, PROVIDED THAT
 ALL OTHER REQUIREMENTS OF THE CODE ARE ALSO MET BASED
 ON SUCH MODIFIED NUMBER AND THE OCCUPANT LOAD DOES NOT
 EXCEED ONE OCCUPANT PER 7 SQUARE FEET (0.65 M2) OF
 OCCUPIABLE FLOOR SPACE.
  
 4) SHEET A-1. THE DOOR SWING OF THE LAUNDRY ROOM DOOR
 SWINGS OVER ? OF THE REQUIRED EGRESS PATH. 1005.7.1
 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 5) SHEET A-1. PLEASE NOTE THERE IS AN EXISTING STAIR TO
 A TENANCY ABOVE THIS UNIT. THE PLANS INDICATE AN
 EXISTING WATER HEATER BELOW THE STAIR ENCLOSURE. PLEASE
 PROVIDE COMPLIANCE WITH 2014 FBC-B 1009.9.3 ENCLOSURES
 UNDER INTERIOR STAIRWAYS.
 THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES
 UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-11-09 Cont ID  
Sent By ccole Date 2016-11-09 Time 16:39 Rev Time 0.00
Received By vperez Date 2016-11-09 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-11-03 Cont ID  
Sent By vperez Date 2016-11-03 Time 10:21 Rev Time 0.00
Received By vperez Date 2016-11-03 Time 10:21 Sent To  
Notes
2016-11-03 10:21:33PREVIOUSLY APPROVED BY MIKE ALBARRAN

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-29 Cont ID  
Sent By albarran Date 2016-09-29 Time 14:13 Rev Time 0.00
Received By albarran Date 2016-09-29 Time 13:30 Sent To  
Notes
2016-09-29 14:14:42ELECTRICAL REVIEW APPROVED. ALL PREVIOUSLY MENTIONED
 DEFICIENCIES HAVE BEEN SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-12 Cont ID  
Sent By albarran Date 2016-08-12 Time 10:43 Rev Time 0.00
Received By albarran Date 2016-08-12 Time 10:00 Sent To  
Notes
2016-08-12 10:43:26ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: FUSION HAIR SALON
 JOB ADDRESS: 321 S. DIXIE HWY.
 DESCRIPTION: INTERIOR IMPROVEMENT ? NEW HAIR SALON
 MASTER PERMIT: 16080290
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW:
  
 1. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT, OTHERWISE THEY SHALL BE ON THE SAME
 CIRCUIT AS FOR THE LIGHTING OF THE ROOM THEY OCCUPY.
 2. NEC 600.5 - EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE 20 AMP DEDICATED OUTLET IN
 AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING. SERVICE HALLWAYS OR
 CORRIDORS SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. THE SUBMITTED DRAWING DOES NOT INDICATE
 THIS ON THE PANEL SCHEDULE OR THE FLOOR PLAN.
 3. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY. THE SUBMITTED
 DRAWING DOES NOT INDICATE THIS ON THE PANEL SCHEDULE OR
 THE FLOOR PLAN.
 4. NEC 422.31. PERMANENTLY CONNECTED APPLIANCE OF OVER
 300 VA OR 1/8 HP REQUIRES A DISCONNECT WITHIN SIGHT OF
 THE APPLIANCE. MARK ON THE PLANS THE DISCONNECT FOR THE
 WATER HEATER.
 5. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. THIS CAN
 BE ADDRESSED WITH A BLOCK NOTE ON THE PLANS.
 6. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL
 BE DURABLY MARKED AND DATED ON ALL NON-DWELLING
 ELECTRICAL APPARATUS. THIS CAN BE ADDRESSED WITH A
 BLOCK NOTE ON THE PLANS.
 7. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY.
 8. FBC-E SECTION C405 REQUIRES MANDATORY LIGHTING
 CONTROL.
 9. FBC-EC 405.2.2.2 REQUIRES OCCUPANCY SENSORS IN THE
 RESTROOMS, STORAGE CLOSET, PRIVATE OFFICES AND SIMILAR
 ROOMS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-16 Cont ID  
Sent By wjolin Date 2016-09-16 Time 12:01 Rev Time 0.00
Received By wjolin Date 2016-09-16 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By wjolin Date 2016-08-10 Time 12:19 Rev Time 0.00
Received By wjolin Date 2016-08-10 Time 12:02 Sent To  
Notes
2016-08-10 12:18:59321 SOUTH DIXIE HIGHWAY
 PERMIT #16080290
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A2: WATER HEATER DOES NOT APPEAR TO BE FIRE
 SEPARATED FROM THE EXISTING STAIR. PER NFPA 101 SECTION
 7.2.2.5.3.2, ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT THE SPACE SHALL BE
 SEPARATED FROM THE STAIR ENCLOSURE BY THE SAME FIRE
 RESISTANCE AS THE EXIT ENCLOSURE.
  
 SHEET A2: LAUNDRY DOOR SWING OBSTRUCTS EGRESS. PER NFPA
 101 SECTION 7.2.1.4.3.1, DURING ITS SWING, ANY DOOR IN
 A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, HALLWAY OR
 LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN
 7-INCHES INTO THE REQUIRED WIDTH OF THE EGRESS PATH
 WHEN FULLY OPEN.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-11-09 Cont ID  
Sent By ccole Date 2016-11-09 Time 16:39 Rev Time 0.00
Received By ccole Date 2016-11-09 Time 14:22 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-07 Cont ID  
Sent By   Date 2016-11-07 Time   Rev Time 0.00
Received By cpuell Date 2016-10-27 Time 13:46 Sent To  
Notes
2016-10-27 13:46:29B04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-14 Cont ID  
Sent By jwitmer Date 2016-10-14 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2016-09-06 Time 11:54 Sent To  
Notes
2016-09-15 11:55:34B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-26 Cont ID  
Sent By gjohnson Date 2016-08-26 Time 12:30 Rev Time 0.00
Received By gjohnson Date 2016-08-08 Time 09:42 Sent To  
Notes
2016-08-09 09:42:35B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-13 Cont ID  
Sent By jwitmer Date 2016-08-13 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2016-08-13 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-11-09 Cont ID  
Sent By ccole Date 2016-11-09 Time 16:38 Rev Time 0.00
Received By ccole Date 2016-11-09 Time 16:38 Sent To  
Notes
2016-11-09 16:50:31MECHANICAL PROVISOS:
 FBC-14 MECHANICAL
 11/9/16
  
 1) THE OUTSIDE AIR INTAKE SHALL BE LOCATED A MINIMUM OF
 10' HORIZONTALLY FROM THE REAR DRIVEWAY AND PARKING
 AREA- SECTION 401.4
  
 2) THE EXHAUST OUTLETS SHALL TERMINATE A MINIMUM OF 10'
 ABOVE ADJOINING GRADE- SECTION 501.3.1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-10-28 Cont ID  
Sent By ccole Date 2016-10-28 Time 15:36 Rev Time 0.00
Received By ccole Date 2016-10-28 Time 15:36 Sent To  
Notes
2016-10-28 15:46:433RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080290
 10/28/16
  
 1) SHEET M1: THE AC SYSTEM IS NOTED AS EXISTING WITH NO
 CHANGES IN HOWEVER THERE IS AN EQUIPMENT SCHEDULE FOR A
 NEW 7.5 TON SPLIT SYSTEM ON THE PLAN, AND ALSO A NOTE
 SPECIFYING RELOCATION AND INSTALLATION OF DROPS AND
 RETURNS. PLEASE NOTE THE ELECTRICAL PQNEL SCHEDULE
 INDICATES AN RTU. PLEASE CLARIFY THE SCOPE OF THE
 PROPOSED PROJECT.
  
 2) M-1: PROVIDE A DETAIL FOR INSTALLATION OF THE NEW
 AIR HANDLER (IF APPLICABLE) AND HOW THE RETURN DUCT
 SPECIFED AS "SURFACE MOUNTED" WILL CONNECT TO THE UNIT.
 INDICATE THE HEIGHT FROM THE FINISHED FLOOR TO THE
 UNDERSIDE OF THE SURFACE MOUNTED RETURN.
  
 3) M-1: SHOW THE COMPONENTS OF THE SOURCE CAPTURE
 SYSTEM AT THE NAIL STATIONS INCLUDING THE EXHAUST DUCT
 RUNS FROM THE POINT OF CAPTURE TO THE DISCHARGE
 LOCATIONS AND THE TYPES AND SIZES OF DUCTWORK. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE MANICURE TABLES
 AND ALL ASSOCIATED PRODUCTS WITH APPROVAL SIGNATURES BY
 THE DESIGNER OF RECORD.
  
 4) M-1: INDICATE THE TYPE AND SIZE OF OUTSIDE AIR VENT
 TO BE INSTALLED AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND A FL. PRODUCT APPROVAL AND/OR
 MIAMI-DADE NOA- SECTION 401.5. INDICATE WITH A NOTE, OR
 SHOW MEASUREMENTS TO VERIFY THE LOCATION OF THE AIR
 INLET MEETS THE MNINIMUM REQUIRED CLEARANCE DISTANCES
 PER SECTION 401.4.
  
 5) SHOW THE LOCATION OF THE NEW AC CONDENSER AND
 PROVIDE ENGNEERING FOR INSTALLATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-19 Cont ID  
Sent By ccole Date 2016-09-19 Time 17:36 Rev Time 0.00
Received By ccole Date 2016-09-19 Time 17:36 Sent To  
Notes
2016-09-19 17:51:392ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080290
 9/19/16
  
 1) THE REVISED PLAN SHOWS BOTH AN EXISTING 3TON AC
 SYSTEM TO REMAIN AND A NEW 5TON AC SYSTEM. IT APPEARS
 BY THE 1800 CFMS OF SUPPLY AIR SHOWN THAT THE NEW 5TON
 SYSTEM IS BEING INSTALLED- PLEASE REMOVE THE 3TON
 SCHEDULE AND ALL OTHER REFERENCES TO THE EXISTING 3 TON
 SYSTEM.
  
 2) PLEASE CONSULT WITH A MECHANICAL ENGINEER AND AC
 MANUFACTURER FOR ACCURATE O/A CAPACITY IF THE NEW 5TON
 UNIT. VERY TYPICALLY, THE RATIO OF O/A TO SUPPLY AIR
 WILL BE 15-20%. 600 CFMS SHOWN WOULD REQUIRE A UNIT
 SIZED AT 7 OR 7.5 TONS.
  
 3) A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF THE NEW 5TON SYSTEM, UNLESS MANUFACTURER'S
 SPECIFICATIONS INDICATE THE SYSTEM WILL NOT PRODUCE
 OVER 2000 CFMS OF SUPPLY AIR- SECTION 606.2.1.
  
 4) PLEASE REVIEW COMMENTS #1, 2, & 4 FROM THE 1ST
 REVIEW PRINTED BELOW. THE REVISED PLAN DOES NOT A
 SOURCE CAPTURE SYSTEM AT THE NAIL STATIONS, DOES NOT
 SHOW EXHAUST FOR THE BEAUY SALON, AND THE O/A AND AIR
 BALANCE CALCULATIONS ARE INCORRECT. REQUIRED CLEARANCES
 FOR EXHAUSDT TERMINATION NOT SHOWN.
  
 1) THE PLAN IS NOT IN COMPLIANCE WITH TABLE 403.3 AND
 FOOTNOTES B AND H. THE 4 NAIL STATIONS SHOWN REQUIRE 50
 CFMS OF EXHAUST EACH, AND EACH NAIL STATION IS REQUIRED
 TO HAVE A SOURCE CAPTURE SYSTEM. THE BEAUTY SALON SPACE
 IN TOTAL IS REQUIRED TO HAVE AN EXHAUST VENTILATION
 SYSTEM DESIGNED AT 0.6 CFMS PER SQ. FT. PLEASE REVISE
 THE PLANS AND CALCULATIONS TO SHOW COMPLIANCE.
 PLEASE NOTE THAT O/A FOR THE SALON SHALL BE PROVIDED AT
 A RATE 20 CFMS PER PERSON AND 0.12 CFMS PER SQ. FT. OF
 SPACE.
  
 2) PROVIDE AIR BALANCE CALCULATIONS- REFER TO SECTION
 501.4
  
 4) INDICATE THE TYPES AND SIZES OF THE NEW EXHAUST
 DUCTS, AND VERIFY COMPLIANCE WITH SECTION 501.3.1 FOR
 OUTLET TERMINATION LOCATION, AND 501.3.2 FOR OPENING
 PROTECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By ccole Date 2016-08-15 Time 15:28 Rev Time 0.00
Received By ccole Date 2016-08-15 Time 15:28 Sent To  
Notes
2016-08-15 15:57:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080290
 8/15/16
  
 1) THE PLAN IS NOT IN COMPLIANCE WITH TABLE 403.3 AND
 FOOTNOTES B AND H. THE 4 NAIL STATIONS SHOWN REQUIRE 50
 CFMS OF EXHAUST EACH, AND EACH NAIL STATION IS REQUIRED
 TO HAVE A SOURCE CAPTURE SYSTEM. THE BEAUTY SALON SPACE
 IN TOTAL IS REQUIRED TO HAVE AN EXHAUST VENTILATION
 SYSTEM DESIGNED AT 0.6 CFMS PER SQ. FT. PLEASE REVISE
 THE PLANS AND CALCULATIONS TO SHOW COMPLIANCE.
 PLEASE NOTE THAT O/A FOR THE SALON SHALL BE PROVIDED AT
 A RATE 20 CFMS PER PERSON AND 0.12 CFMS PER SQ. FT. OF
 SPACE.
  
 2) PROVIDE AIR BALANCE CALCULATIONS- REFER TO SECTION
 501.4
  
 3) PROVIDE BOTH A REFLECTIVE CEILING PLAN, AND AN AC
 LAYOUT PLAN SHOWING THE LOCATIONS OF ALL SUPPLY AND
 RETURN DIFFUSERS AND GRILLS. THERE IS AN AIR DEVICE
 SCHEDULE ON M-1 BUT NO DETAILS ON THE PLAN.
  
 4) INDICATE THE TYPES AND SIZES OF THE NEW EXHAUST
 DUCTS, AND VERIFY COMPLIANCE WITH SECTION 501.3.1 FOR
 OUTLET TERMINATION LOCATION, AND 501.3.2 FOR OPENING
 PROTECTION.
  
 5) INDICATE HOW THE EXHAUST FANS WILL ACTIVATE. THE
 ELECTRICAL PLANS TO DO NOT INDICATE SWITCHES OR OTHER
 METHODS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-11-03 Cont ID  
Sent By gjohnson Date 2016-11-03 Time 08:44 Rev Time 0.00
Received By gjohnson Date 2016-11-02 Time 16:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-10-13 Cont ID  
Sent By gjohnson Date 2016-10-13 Time 10:43 Rev Time 0.00
Received By gjohnson Date 2016-10-12 Time 15:52 Sent To  
Notes
2016-10-13 11:11:491ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENTS
 1. NOT COMPLIED SHT. A-3 DETAIL #6 SHOULD REFLECT THE
 PLAN.THE SIDE DIMENSION OF 60IN SHALL NOT HAVE ANY
 OTHER FIXTURES IN THAT SPACE THE DETAIL IS SHOWING THE
 LAVATORY. PER FBC ACC
 604.3.1 AND 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 2. NOT COMPLIED. LAVATORY'S IN PUBLIC BATHROOMS SHALL
 HAVE TEMPERED WATER DELIVERED FROM A TEMPERATURE
 LIMITING DEVICE THE THERMOSTAT ON THE WATER HEATER DOES
 NOT COMPLY. PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC
 HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. AND 607.1.1 TEMPERATURE LIMITING
 MEANS.
 A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE
 AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES.
  
 8. NOT COMPLIED THE WATER HEATER SHALL BE PROVIDED WITH
 A MEANS OF CONTROLLING THERMAL EXPANSION THE
 TEMPERATURE AND PRESSURE RELIER VALVE DOES NOT COMPLY
 WITH THIS CODE SECTION. PER FBC PL 607.3 THERMAL
 EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY
 THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. AND 504.4
 RELIEF VALVE.
 STORAGE WATER HEATERS OPERATING ABOVE ATMOSPHERIC
 PRESSURE SHALL BE PROVIDED WITH AN APPROVED,
 SELF-CLOSING (LEVERED) PRESSURE RELIEF VALVE AND
 TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF. THE
 RELIEF VALVE SHALL CONFORM TO ANSI Z21.22. THE RELIEF
 VALVE SHALL NOT BE USED AS A MEANS OF CONTROLLING
 THERMAL EXPANSION.
  
 11. NOT COMPLIED. SHOW THE SHUT OFF ON THE COLD WATER
 MAIN AND ALL THE DROPS. PER FBC PL
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 2. ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE
 ENTRANCE INTO THE STRUCTURE.
  
  
 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN
 OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By gjohnson Date 2016-08-26 Time 12:07 Rev Time 0.00
Received By gjohnson Date 2016-08-26 Time 11:54 Sent To  
Notes
2016-08-26 12:30:231ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHT. A-3 THE DETAIL # 6 DOES NOT COMPLYY WITH THE
 FLORIDA ACCESSIBILITY CODE 2014 IT SHA COMPL WITH FBC
 ACC. SEC 606 AND 604.
  
 2. THE LAVATORY IN THE BATH ROOM SHALL COMPLY WITH FBC
 PL. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 3. THE FIXTURE DRAIN FOR WASHING MACHINE SHALL BE 3IN.
 PER FBC PL 406.2
  
 4. THE STACK FOR THE WASHING MACHINE SHALL BE VENTED.
 PER FBC PL 901.2-901.2.1
  
 5. WATER SUPPLY'S FOR THE WASHING MACHINE SHALL COMPLY
 WITH FBC PL 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010. 6.
  
 6. A MINIMUM OF 1 VENT SHALL EXTEND THROUGH THE ROOF.
 PER FBC PL 904.1 REQUIRED VENT EXTENSION.
 THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE
 NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE
 OUTDOORS.
  
 7. THE FIXTURE BRANCH FOR THE TOILET SHALL BE A MINIMUM
 OF 3IN. PER FBC PL 420.3
  
 8. THE HOT WATER SYSTEM SHALL COMPLY WITH FBC PL
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY
 THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2
 AND
 607.2 HOT OR TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 9. SHOW PIPE SIZES ON THE PIPING FOR THE BATHROOM
 GROUP. WPB AMEND TO FBC 107.2.1
  
 10. SHOW PIPE SIZES ON THE PIPING FOR THE WATER RISER.
 WPB AMEND TO FBC 107.2.1
  
 11. SHOW THE COLD WATER MAIN AND SHUT OFF ON THE WATER
 RISER
 . WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  