Plan Review Details - Permit 16080247
Plan Review Stops For Permit 16080247
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By jwitmer Date 2016-08-31 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2016-08-31 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-13 Cont ID  
Sent By jwitmer Date 2016-08-13 Time 07:45 Rev Time  
Received By jwitmer Date 2016-08-13 Time 06:45 Sent To  
Notes
2016-08-13 07:57:48BUILDING PLAN REVIEW
 W. P. B. REVISION: 16080247
 W. P. B. PERMIT: 16020859
 ADD: 8055 IRONHORSE BLVD./ CLUBHOUSE
 CONT: CUTTING EDGE BUILDING SYSTEMS
 TEL: 561-282-8265
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. AUGUST 13/2016
 ACTION: DENIED
  
 1) SHEET A2.0 SHOWS IN THE MENS/ WOMENS ATTEDANT ROOM
 THE AIR HANDLER BEING RELOCATED WITHIN A NEW CLOSET
 WITH DOUBLE DOORS IN FRONT FOR ACCESS AND A DOOR ON ONE
 SIDE FOR ACCESS. SHEET ALR4.1 DOES NOT SHOW A RETURN
 DUCT, IT WOULD APPEAR THE CLOSET IS TO BE CONSIDERED A
 PLENUM. THE PLANS GIVE NO INFORMATION ON THE WALL
 FINISHES NOR THE TYPE OF MATERIALS THE DOORS ARE MADE.
 2014 FBC-M 602.2.1 MATERIALS WITHIN PLENUMS. EXCEPT AS
 REQUIRED BY SECTIONS 602.2.1.1 THROUGH 602.2.1.5,
 MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR
 SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 E 84 OR UL 723. PLEASE PROVIDE WALL FINSIHES OF THE AIR
 HANDLER CLOSET AND OF THE DOORS.
  
 2) SHEET A2.0 & ALF4.1 THE MENS/ WOMENS ATTENDANT
 ACCESS ROOM DOOR NOT IDENTIFIED ALSO HAS A NEW
 STRUCTURE AROUND IT. THIS DOOR NO LONGER HAS THE
 REQUIRED MANEUVERING CLEARANCES AROUND IT BY THE 2014
 FBC-ACCESS. CODE. 404.2.4.1 18 INCHES ON THE PULL SIDE
 OF THE DOOR LATCH SIDE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-15 Cont ID  
Sent By vperez Date 2016-08-15 Time 11:07 Rev Time 0.00
Received By albarran Date 2016-08-15 Time 10:31 Sent To I
Notes
2016-08-15 11:10:388/15/16 CONDITIONAL APPROVAL: PLAN SHEET E-1.2
 REFLECTED CEILING INCLUDED BUT EXCLUDED FROM PERMIT
 APPLICATION THEREFORE NOT ELECTRICAL WORK RELATING
 THERETO SHALL BE AUTHORIZED. THE SCOPE OF PERMITTED
 WORK ADDRESSED THE RELOCATION OF EXISTING APPARATUS
 THEREFORE THE EXISTING COP SHOULD BE ADEQUATE. NEVER
 THE LESS ALL NEW WIRING AND COP TO BE VERIFIED BY FIELD
 INSPECTOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-29 Cont ID  
Sent By pleduc Date 2016-08-29 Time   Rev Time 0.00
Received By pleduc Date 2016-08-26 Time 14:28 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-12 Cont ID  
Sent By pleduc Date 2016-08-12 Time   Rev Time 0.00
Received By pleduc Date 2016-08-10 Time 17:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-31 Cont ID  
Sent By jwitmer Date 2016-08-31 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2016-08-23 Time 13:20 Sent To  
Notes
2016-08-23 13:20:45RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-15 Cont ID  
Sent By albarran Date 2016-08-15 Time 11:13 Rev Time 0.00
Received By albarran Date 2016-08-05 Time 16:16 Sent To  
Notes
2016-08-15 11:15:588/15/16 FAILED UNANIMOUS DISCIPLINE APPROVAL.
 CONTRACTOR NOTIFIED VIA EMAIL. FILE SENT TO LARGE
 DENIED BIN "C". MA
2016-08-09 07:54:44B34
2016-08-08 16:16:32B33

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-19 Cont ID  
Sent By ccole Date 2016-08-19 Time 09:01 Rev Time 0.00
Received By ccole Date 2016-08-19 Time 09:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By ccole Date 2016-08-15 Time 07:16 Rev Time 0.00
Received By ccole Date 2016-08-15 Time 07:12 Sent To  
Notes
2016-08-15 07:53:321ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16080247
 8/15/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE THAT LOCKER
 ROOMS REQUIRE EXHAUST AT A RATE OF 0.5 CFM'S PER SQ.
 FT. AND RECIRCULATION OF AIR IS LIMITED TO 10% OF THE
 SUPPLY AIR STREAM.
  
 2) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 THAT INDICATES WHICH AREAS OF THE OCCUPANCY ARE BEING
 CONDITIONED BY THE NEW AC SYSTEMS.
  
 3) SHEET M-1.1: SHOW THE LOCATIONS OF THE EXISTING
 AHU'S AND SUPPLY, RETURN, AND O/A DUCTWORK. HOW CAN THE
 O/A BRANCH DUCTS TO THE NEW UNITS BE EXISTING? PLEASE
 INDICATE THE SIZES OF THE EXISTING AND NEW O/A DUCTS.
  
 4) M-1.1: PROVIDE COMPLETE SUPPLY AND RETURN DUCTWORK
 PLANS FOR THE NEW AHU'S. HOW IS AIR BEING RETURNED TO
 THE UNITS FROM ALL THE ROOMS AND SPACES?
  
 5) M-1.1: A NEW MECHANICAL CLOSET IS BEING CREATED FOR
 AHU-1. PLEASE NOTE THAT ALL MATERIALS IN THE CLOSET
 INCLUDING THE NEW DOOR SHALL BE NON-COMBUSTIBLE OR
 PLENUM-RATED- SEE SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  