Plan Review Details - Permit 16080232
Plan Review Stops For Permit 16080232
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-09-28 Cont ID  
Sent By Mgonzale Date 2016-09-02 Time   Rev Time 1.00
Received By mgonzale Date 2016-09-02 Time   Sent To I
Notes
2016-09-02 15:42:37PROVISOS:
  
 #1 POINT OF SERVICE SHALL BE AT THE PROPERTY LINE. 8"
 DCDA MUST BE LOCATED JUST INSIDE OF YOUR PROPERTY.
 CONTACT UTILITY CUSTOMER SERVICE SHOULD YOU NEED FIELD
 COORDINATION AS TO THE LOCATION PLACEMENT OF THE
 DEVICE. (561) 822-2040.
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/B ACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL.
  
 #2 SPECIFICATIONS FOR 8" DCDA TO BE USED AT THE POINT
 OF SERVICE. BACKFLOW MUST ALSO BE USC APPROVED AND LEAD
 FREE TYPE.
 (THE CITY OF WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL HAS BEEN REVISED, MAKING KNOWN THAT "ALL
 BACKFLOW DEVICES MUST BE LEAD FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW: HTTP://WP
 B.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/B
 ACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL)
  
 #3 PROVIDE SPECIFICATION SHEET FOR FIRE HYDRANT, MODEL,
 (MUST MEET CITY OF WPB STANDARD) SEE CITY'S APPROVED
 MATERIAL LIST AT THIS LINK:
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-08-18 Cont ID  
Sent By pleduc Date 2016-08-18 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 12:47 Sent To PC
Notes
2016-08-15 10:59:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FACE SHEET FOR HYDRAULIC CALCULATIONS BLDG. "C"
 NORTH - PAGE 1 0F 1 INDICATES AN AREA OF 3000FT2;
 HOWEVER, THE HYDRAULIC OVERVIEW SHEET AND PLAN SHEET
 INDICATES 2000FT2.
  
 PLEASE PROVIDE A REVISION FOR CORRECTION.
  
  
 2) THE FIRST SHEET INDICATES A SCALE OF 1" TO 500'
 APPEARS TO BE INACCURATE.
  
 PLEASE PROVIDE A REVISION FOR CORRECTION.
  
  
 3) THE PLAN SHEETS ARE NOT NUMBERED OR IDENTIFIED. I
 HAVE INSERTED TEMPORARY NUMBERS I.E. 1 OF 8, ETC.
  
 PLEASE PROIVDE A REVISION FOR CORRECTION.
  
  
 4) THE SECOND SHEETS PUMP SECTION VIEWS DO NOT CLEARLY
 INDICATE THE MINIMUM DISTANCE FROM THE SUCTION TO THE
 ELBOW.
  
 4.14.6.3 ELBOWS AND TEES.
 4.14.6.3.1 UNLESS THE REQUIREMENTS OF 4.14.6.3.2 ARE
 MET, ELBOWS AND TEES WITH A CENTERLINE PLANE PARALLEL
 TO A HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE
 PERMITTED. (SEE FIGURE A.4.14.6.)
 4.14.6.3.2 THE REQUIREMENTS OF 4.14.6.3.1 SHALL NOT
 APPLY TO ELBOWS AND TEES WITH A CENTERLINE PLANE
 PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT WHERE
 THE DISTANCE BETWEEN THE FLANGES OF THE PUMP SUCTION
 INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10 TIMES
 THE SUCTION PIPE DIAMETER.
 4.14.6.3.3 ELBOWS WITH A CENTERLINE PLANE PERPENDICULAR
 TO THE HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL BE
 PERMITTED AT ANY LOCATION IN THE PUMP SUCTION INTAKE.
  
 PLEASE PROVIDE JUSTIFICATION OR CLEARLY INDICATE ON
 REVISION THE COMPLIANCE WITH THE MINIMUM 10 TIMES THE
 SUCTION PIPE DIAMETER.
  
  
 5) THE FIFTH SHEET IN THE HYDRAULIC INFOMATION TABLE
 AND THE HYDRAULIC CALCULATION PACKAGE INDICATES AN
 ACTUAL AREA OF 4866.67FT2. THE AREA HIGHLIGHTED DOES
 NOT MATCH THAT TOTAL.
  
 PLEASE PROVIDE JUSTIFICATION OR CLEARLY INDICATE
 CORRECTION ON REVISION SHEET.
  
 ADDITIONALLY, IF JUSTIFIED, PLEASE PROVIDE A REVIEW FOR
 THE CHANGEAND APPROVAL BY THE ENGINEER OF RECORD AS
 THIS WOULD EXCEED PREVIOUSLY SUBMITTED DOCUMENTATION'S.
  
  
 6) THERE IS NO "VALUE" INDICATED ON THE PERMIT
 SUBMITTAL.
  
 PLEASE PROVIDE AN ACCURATE "VALUE" OR A COPY OF THE
 CONTRACT AMOUNT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-18 Cont ID  
Sent By mgonzale Date 2016-09-28 Time 12:28 Rev Time 0.00
Received By pleduc Date 2016-08-04 Time 12:33 Sent To  
Notes
2016-08-05 12:33:16SUBMITTAL ROUTED TO FIRE INBOX