Plan Review Details - Permit 16080172
Plan Review Stops For Permit 16080172 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2016-08-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-08-12 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-08-12 |
Time |
06:58 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2016-08-05 |
|
|
Cont ID |
|
Sent By |
malbarra |
Date |
2016-08-05 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-08-05 |
Time |
10:11 |
Sent To |
|
|
Notes |
2016-08-05 10:28:40 | ELECTRICAL REVISION LIMITED TO THE AREA CLOUDED IN | | GREEN INK. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2016-08-12 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-08-12 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-08-10 |
Time |
08:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-08-22 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-08-22 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-08-03 |
Time |
11:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2016-11-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-08-05 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-08-05 |
Time |
16:44 |
Sent To |
|
|
Notes |
2016-08-05 16:50:40 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT 16080172 | | 8/5/16 | | | | 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE PLAN. | | A NEW HEAT PUMP IS SHOWN ON THE PLAN- CLARIFY IF THIS | | IS AN EXACT SIZE CHANGOUT AND SUBMIT AN AC CHANGEOUT | | FORM IF APPLICABLE. . OTHERWISE PROVIDE COOLING AND | | HEATING CALCULATIONS AS REQUIRED BY SECTION C403.2.1 | | FBC-14 ENERGY CONSERVATION. | | | | 2) SHOW LOCATIONS OF AC DUCT, DIFFUSER, OR RETURN GRILL | | ALTERATIONS AND PROVIDE DETAILS IF APPLICABLE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2016-08-22 |
|
|
Cont ID |
|
Sent By |
gearl |
Date |
2016-08-22 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-08-22 |
Time |
09:20 |
Sent To |
|
|
Notes |
|
|
|