Plan Review Details - Permit 16080121
Plan Review Stops For Permit 16080121
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-09-12 Cont ID  
Sent By rmcdouga Date 2016-09-12 Time 14:20 Rev Time 0.00
Received By rmcdouga Date 2016-09-09 Time 13:52 Sent To  
Notes
2016-09-12 10:19:23 
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FLORIDA ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN
 SIGNATURE IS REQUIRED ON THE STRUCTURAL DRAWINGS,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002
  
 2) SUBMIT TWO SETS OF A SURFACE WATER DRAINAGE PLAN
 PURSUANT TO R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 3) SHOW COMPLIANCE WITH R302.12 DRAFTSTOPPING. IN
 COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE
 BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A
 FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE
 THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS.
 WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE
 ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL
 BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE
 FOLLOWING CIRCUMSTANCES:
 1. CEILING IS SUSPENDED UNDER THE FLOOR FRAMING.
 2. FLOOR FRAMING IS CONSTRUCTED OF TRUSS-TYPE OPEN-WEB
 OR PERFORATED MEMBERS.
  
 4) PROVIDE A DETAIL OF THE STEEL POST CAP ON THE PLANS.
 FBC 107.2.1
  
 5) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATIONS. FBC ENERGY CONSERVATION - SECT. 103.1.1.2
 CODE COMPLIANCE CERTIFICATION. THE BUILDING?S OWNER,
 THE OWNER?S ARCHITECT, OR OTHER AUTHORIZED AGENT
 LEGALLY DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE
 BUILDING IS IN COMPLIANCE WITH THE CODE, AS PER SECTION
 553.907, FLORIDA STATUTES, PRIOR TO RECEIVING THE
 PERMIT TO BEGIN CONSTRUCTION OR RENOVATION.
  
 6) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 OUT DOOR BBQ AND HOOD. FBC 107.2.1
  
 7) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORTS
 WITH INSTALLATION REQUIREMENTS FOR THE ICYENE SPRAY
 FOAM INSULATION. FBC R316
  
 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE ROOFING MATERIALS, AS WELL AS, THE DECK AND BALCONY
 WATERPROOFING SYSTEMS.
  
 9) THE DOOR SCHEDULE ON SHEET A-6 OF THE PLANS
 SPECIFIES CGI ( NOA NO. 16-0303.01 ) FOR THE SLIDING
 GLASS DOOR AND ( NOA NO. 15-1013.15 ) FOR PGT SLIDING
 GLASS DOORS WAS SUBMITTED.
  
 10) THE DOOR SCHEDULE ON SHEET A-6 OF THE PLANS
 SPECIFIES CGI ( NOA NO. 14-1103.08 ) FOR THE FRENCH
 DOORS AND ( NOA NO. 14-1117.05 ) FOR PGT GLAZED FRENCH
 DOORS WAS SUBMITTED.
  
 11) PRODUCT APPROVALS WERE SUBMITTED FOR PGT CA-740
 FIXED CASEMENT WINDOWS (NOA NO. 15-0519.15 ). THIS
 PRODUCT APPROVALS IS NOT LISTED IN THE WINDOW SCHEDULE
 ON SHEET A-6. THE WINDOW AND DOOR SCHEDULES SPECIFY CGI
 WINDOWS AND DOORS.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-05 Cont ID  
Sent By albarran Date 2016-08-05 Time 11:57 Rev Time 0.00
Received By albarran Date 2016-08-05 Time 10:53 Sent To  
Notes
2016-08-05 11:59:48CORRECTED ELECTRICAL BLOCK NOTE 7 TO READ NM CABLE
 RATHER THAN ROMEX. ADDED THE FOLLOWING NOTATION:
 FBC-ER404.1 MANDATORY REQUIREMENT
 A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR
 CONTAIN HIGH-EFFICACY LAMPS. LOW VOLTAGE LIGHTING
 EXCLUDED.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-08-23 Cont ID  
Sent By fmittner Date 2016-08-23 Time 08:42 Rev Time 0.00
Received By fmittner Date 2016-08-23 Time 08:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-12 Cont ID  
Sent By rmcdouga Date 2016-09-12 Time 14:22 Rev Time 0.00
Received By rmcdouga Date 2016-08-03 Time 09:48 Sent To  
Notes
2016-08-04 09:58:19R19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-09-09 Cont ID  
Sent By rmcdouga Date 2016-09-09 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2016-09-09 Time 13:52 Sent To  
Notes
2016-09-09 13:53:04BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-09 Cont ID  
Sent By hmoser Date 2016-09-09 Time 15:22 Rev Time 0.00
Received By hmoser Date 2016-09-09 Time 14:50 Sent To  
Notes
2016-09-09 15:21:59PLAN DENIED
 1) THERE IS NO ADDRESS ON PLAN SECTION 107.2.1 FBC 2014
 2) PROVIDE ENGINEERING ON PLAN FOR CONDENSER TIE DOWN
 PER SECTION M1305.1.4.1 GROUND CLEARANCE AND
 M1401.4 EXTERIOR INSTALLATION 2014 RESIDENTIAL CODE
 3) REFER TO SECTION R403.2.4 AIR HANDLING UNITS
 2014 FLORIDA ENERGY CODE.
 4) REFER TO SECTION M1305.1.3 APPLIANCES IN ATTIC
 2014 RESIDENTIAL CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-25 Cont ID  
Sent By gjohnson Date 2016-08-25 Time 12:56 Rev Time 0.00
Received By gjohnson Date 2016-08-25 Time 12:56 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-09-12 Cont ID  
Sent By rmcdouga Date 2016-09-12 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2016-09-12 Time 14:21 Sent To  
Notes
2016-09-12 14:21:53NO ROOFING OR WATERPROOFING PRODUCT APPROVALS WERE
 SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-23 Cont ID  
Sent By fmittner Date 2016-08-23 Time 08:42 Rev Time 0.00
Received By fmittner Date 2016-08-23 Time 08:42 Sent To  
Notes
***NONE***