2016-08-11 14:44:52 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: TOUB RESIDENCE/REMODEL |
| JOB ADDRESS: 221 POTTER ROAD |
| DESCRIPTION: REMOVE EXISTING GENERATOR & RELOCATE W/NEW |
| GENERATOR PER PLANS |
| MASTER PERMIT: 16080116 |
| REVISION: |
| |
| BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| REVIEW: |
| |
| 1. NEC 702.4(B): PROVIDE LOAD CALCS IN ACCORDANCE W/NEC |
| 220. |
| 2. NEC 702.4(B)(2): STANDBY GENERATOR SHALL BE CAPABLE |
| OF SUPPLYING THE FULL LOAD APPLIED, OR ATS NOT |
| PERMITTED W/O ACCEPTABLE LOAD SHED PROVISIONS. |
| 3. ON THE FLOOR PLAN NOTE THE LOCATION OF ALL SERVICE |
| EQUIPMENT AS WELL AS ALL ELECTRICAL PANELS. |
| 4. NEC 215.5: PROVIDE A SITE SPECIFIC RISER DIAGRAM |
| SHOWING THE LOCATION AND POSITION IN THE SERVICE OF THE |
| TRANSFER SWITCH WITH RELATION TO ALL OTHER PANELS. |
| INCLUDE ON THE RISER DIAGRAM CONDUCTOR SIZING. |
| 5. NEC 250.104(B): SHOW ON PLANS WHERE THE GAS LINE IS |
| BONDED. EQUIPMENT BONDING CONDUCTOR PER NEC 250.122. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |