Plan Review Details - Permit 16080066
Plan Review Stops For Permit 16080066
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By jwitmer Date 2016-08-31 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2016-08-31 Time 07:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-12 Cont ID  
Sent By jwitmer Date 2016-08-12 Time 06:15 Rev Time 0.00
Received By jwitmer Date 2016-08-12 Time 05:45 Sent To  
Notes
2016-08-12 06:15:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080066
 ADD: 303 BANYAN BLVD. 3RD FLOOR/ NEW CONFERENCE ROOM.
 CONT: IBIS BUILDING
 TEL: 561-568-2570
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 12/ 2016
 ACTION: DENIED
  
 1) PLEASE NOTE (3) A1.1 FLOOR PLANS WERE SUBMITTED ONLY
 ONE WAS SIGNED AND SEALED BY THE DESIGNER OF RECORD.
 PLEASE NOTE ON THE OTHER TWO SHEETS ONE MECHANICAL
 SYSTEMS WAS DRAWN IN THE OTHER ELECTRICAL SYSTEMS WERE
 DRAWN IN. IF THIS IS NOT WORK COMPLETED BY THE DESIGNER
 OF RECORD, THE AUTHOR OF THESE SHEETS ARE VIOLATING
 COPYRIGHT LAWS. PLEASE NOTE THERE ARE NO ELECTRICAL NOR
 MECHANICAL CONTRACTORS SIGNED ON AS SUB-PERMITS. ONLY
 THE QUALIFIER FOR EACH OF THOUGHS COMPANIES ELECTRICAL
 & MECHANICAL CAN DEVELOP THEIR OWN PLAN UNDER THERE
 LICENSE. THEY WILL NEED TO PRINT THEIR NAME SIGN THEIR
 NAME AND PRINT THEIR LICENSE NUMBER ON THE DOCUMENT
 THEY CREATED. THEY CAN NOT CREATE A DOCUMENT FOR
 ANOTHER CONTRACTOR IT HAS TO BE THE PROPOSED WORK THEIR
 COMPANY IS LICENSED FOR AND WORK THEY WILL BE
 PREFORMING UNDER THEIR LICENSE. 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.1.
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED
 UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA
 STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED
 PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER
 CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA
 STATUTES.
  
 2) PLANS NEED TO BE BOUND TOGETHER INTO ONE SET OF
 DOCUMENTS BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.
  
 3) SHEET A1.1 INDICATES 6 UL WALL PENETRATION SYSTEMS
 BUT DOES NOT PROVIDE THE UL DOCUMENTATION FOR EACH
 SYSTEM WHAT MAKES UP EACH SYSTEM. THE FIELD INSPECTORS
 NEED THIS INFORMATION TO SEE WHAT COMPONENTS EACH
 SYSTEM IS MADE FROM, AND THE LIMITATIONS ON EACH
 SYSTEM. PROVIDE DOCUMENTATION.
 714.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 4) WITH THIS NEW TENANT SPACE THERE WILL BE MORE LIKELY
 A NEW FIRE SPRINKLER LAYOUT REQUIRED. PLEASE NOTE WHEN
 LESS THAN 50 SPRINKLER HEADS ARE BEING MOVED, THE PLANS
 CAN BE CREATED BY THE FIRE SPRINKLER CONTRACTOR.
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED
 UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA
 STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED
 PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER
 CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA
 STATUTES.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-21 Cont ID  
Sent By mvaldes Date 2016-09-21 Time 10:05 Rev Time 0.00
Received By mvaldes Date 2016-09-21 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-12 Cont ID  
Sent By mvaldes Date 2016-09-12 Time 10:00 Rev Time 0.00
Received By mvaldes Date 2016-09-12 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By mvaldes Date 2016-08-04 Time 10:10 Rev Time 0.00
Received By mvaldes Date 2016-08-04 Time 08:55 Sent To  
Notes
2016-08-04 10:16:35REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - DESIGNER OF RECORD CONFLICT PER FLORIDA STATUE 481,
 IF THE INTENT IS TO USE DRAWINGS AS A TEMPLATE PLEASE
 REMOVE ARCHITECT TILTE BLOCK. THERE COULD BE A
 COPYWRITE ISSUE PLEASE CLARIFY ?
  
 - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 - LOW VOLTAGE SHALL BE UNDER A SEPERATE PERMIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By pleduc Date 2016-08-31 Time   Rev Time 0.00
Received By pleduc Date 2016-08-31 Time 14:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-08 Cont ID  
Sent By pleduc Date 2016-08-08 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 13:49 Sent To  
Notes
2016-08-08 14:09:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1. COVER SHEET - THERE IS NO INDICATION TO A REFERENCED
 FIRE CODE COMPLIANCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
 2. SHEET A 1.1 - THERE WERE THREE (3) SHEETS INDICATED
 AS A 1.1. ONLY OFFICIAL SHEETS SHALL BE SUBMITTED.
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
 3. COVER SHEET - THERE IS NO INDICATIONS OF ANY
 ENGINEERED LIFE SAFETY SYSTEM(S), I.E. FIRE SPRINKLER
 OR FIRE ALARM.
  
 THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND
 DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE
 SAFETY CONCERNS OF THE PROPOSED PROJECT.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PLEASE PROVIDE A NOTE INDICATING ANY EXISTING SYSTEM(3)
 AND THAT ALL WORK RELATED TO THE FIRE SPRINKLER AND/OR
 FIRE ALARM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS
 BY CERITIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 4. ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-29 Cont ID  
Sent By ccole Date 2016-09-29 Time 06:44 Rev Time 0.00
Received By ccole Date 2016-09-27 Time 10:41 Sent To  
Notes
2016-09-28 10:42:01RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-21 Cont ID  
Sent By ccole Date 2016-09-21 Time 11:50 Rev Time 0.00
Received By ccole Date 2016-09-13 Time 14:51 Sent To  
Notes
2016-09-13 14:51:10RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-12 Cont ID  
Sent By mvaldes Date 2016-09-12 Time 10:01 Rev Time 0.00
Received By mvaldes Date 2016-08-25 Time 11:33 Sent To  
Notes
2016-08-25 11:33:33B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-12 Cont ID  
Sent By jwitmer Date 2016-08-12 Time 06:15 Rev Time 0.00
Received By jwitmer Date 2016-08-02 Time 12:51 Sent To  
Notes
2016-08-03 12:51:53B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-12 Cont ID  
Sent By jwitmer Date 2016-08-12 Time 06:15 Rev Time 0.00
Received By jwitmer Date 2016-08-12 Time 06:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-10-03 Cont ID  
Sent By ccole Date 2016-10-03 Time 14:49 Rev Time 0.00
Received By ccole Date 2016-10-03 Time 14:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-09-29 Cont ID  
Sent By ccole Date 2016-09-29 Time 06:44 Rev Time 0.00
Received By ccole Date 2016-09-29 Time 06:44 Sent To  
Notes
2016-09-29 06:47:324TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16080066
 9/29/16
  
 1) THE REVISED PLAN DOES NOT BEAR THE NAME AND
 SIGNATURE OF THE AC CONTRACTOR RESPONSIBLE FOR THE
 DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-09-21 Cont ID  
Sent By ccole Date 2016-09-21 Time 11:44 Rev Time 0.00
Received By ccole Date 2016-09-21 Time 11:33 Sent To  
Notes
2016-09-21 11:50:223RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080066
 9/21/16
  
 1) SUPPLY DUCT AND CHILLED WATER PIPE SIZES NOT SHOWN.
 SHOW THE POINT OF CONNECTIONFOR THE CHILLED WATER
 PIPING.
  
 2) THE PLAN DOES NOT CLEARLY INDICATE HOW O/A IS BEING
 PROVIDED. DOES THE NEW 6" DUCT CONNECT TO AN EXISTING
 O/A DUCT- PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-31 Cont ID  
Sent By ccole Date 2016-08-31 Time 11:11 Rev Time 0.00
Received By ccole Date 2016-08-31 Time 11:19 Sent To  
Notes
2016-08-31 11:31:252ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16080066
 8/31/16
  
 PLEASE REVIEW THE 1ST REVIEW COMMENTS PRINTED BELOW
 REGARDING THE AC PLAN. THE COMMENTS REMAIN APPLICABLE
 TO THE RESUBMITTED PLANS. IN ADDITION PLEASE NOTE THE
 FOLLOWING: THE INSTALLING AC CONTRACTOR MAY DRAW, SIGN,
 AND SUBMIT AC PLANS, BUT MUST ALSO SUBMIT A SUB-PERMIT
 APPLICATION. THE INSTALL AC CONTRACTOR'S PLANS MUST
 SHOW ONLY DETAILS FOR THE AC SYSTEM, AND NOT CONTAIN
  
 ANY ARCHITECTURAL DETAILS AND SCHEDULES PREPARED BY THE
 ARCHITECT OF RECORD. THE WPB BUILDING DEPT. IS
 REQUIRING A SIGNED AND SEALED LETTER FROM THE ARCHITECT
 OF RECORD HARVARD JOLLY STATING THAT THEY ARE NOT
 PROVIDING THE DESIGN OF THE MEP SYSTEMS, HOWEVER THEY
 MAY ALLOW THE CONTRACTOR TO USE THEIR FLOOR PLAN OR
 REFLECTIVE CEILING DRAWING AS THE BASIS FOR THE AC
 SYSTEM PLANS.
  
 1) TWO A1.1 PLANS SHEETS HAVE BEEN SUBMITTED. ONE SHEET
 IS SIGNED AND SEALED BY THE ARCHITECT OF RECORD- RENE
 TERCILLA AIA. THE OTHER A1.1 PLAN SHEET IS NOT SIGNED
 AND SEALED AND HAS A HANDWRITTEN AC PLAN AND NOTES
 WRITTEN OVER THE CEILING DETAIL. THIS PLAN WILL NOT BE
 REVIEWED AND MUST BE DISCARDED PER FLORIDA STATUTE
 481.221(2), FLORIDA ADMINISTRATIVE CODE 61G1-16.003.
  
 2) REFER TO SECTION 107.1 WPB AMENDMENTS TO THE FBC AND
 RESUBMIT MECHANICAL PLANS THAT INCLUDE: A SCOPE OF WORK
 OUTLINE FOR THE PROJECT, AC EQUIPMENT SCHEDULE, DUCT
 LAYOUT PLAN, AIR DISTRIBUTION AND DEVICE SCHEDULES,
 COOLING AND HEATING CALCULATIONS, CONDENSATE DISPOSAL,
 O/A CALCULATIONS AND CONTROLS, ENERGY COMPLIANCE, SMOKE
 AND FIRE PROTECTION TRANSFER OPENING PROTECTIONS,
 FIRESTOPPING DETAILS, AND DUCT HANGING AND SUPPORT
 DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-05 Cont ID  
Sent By ccole Date 2016-08-05 Time 10:39 Rev Time 0.00
Received By ccole Date 2016-08-05 Time 10:39 Sent To  
Notes
2016-08-05 10:45:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080066
 8/5/16
  
 1) TWO A1.1 PLANS SHEETS HAVE BEEN SUBMITTED. ONE SHEET
 IS SIGNED AND SEALED BY THE ARCHITECT OF RECORD- RENE
 TERCILLA AIA. THE OTHER A1.1 PLAN SHEET IS NOT SIGNED
 AND SEALED AND HAS A HANDWRITTEN AC PLAN AND NOTES
 WRITTEN OVER THE CEILING DETAIL. THIS PLAN WILL NOT BE
 REVIEWED AND MUST BE DISCARDED PER FLORIDA STATUTE
 481.221(2), FLORIDA ADMINISTRATIVE CODE 61G1-16.003.
  
 2) REFER TO SECTION 107.1 WPB AMENDMENTS TO THE FBC AND
 RESUBMIT MECHANICAL PLANS THAT INCLUDE: A SCOPE OF WORK
 OUTLINE FOR THE PROJECT, AC EQUIPMENT SCHEDULE, DUCT
 LAYOUT PLAN, AIR DISTRIBUTION AND DEVICE SCHEDULES,
 COOLING AND HEATING CALCULATIONS, CONDENSATE DISPOSAL,
 O/A CALCULATIONS AND CONTROLS, ENERGY COMPLIANCE, SMOKE
 AND FIRE PROTECTION TRANSFER OPENING PROTECTIONS,
 FIRESTOPPING DETAILS, AND DUCT HANGING AND SUPPORT
 DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  