Plan Review Details - Permit 16080055
Plan Review Stops For Permit 16080055
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-31 Cont ID  
Sent By cthroop Date 2016-08-31 Time 10:56 Rev Time 0.00
Received By cthroop Date 2016-08-31 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 15:10 Rev Time 0.00
Received By cthroop Date 2016-08-09 Time 15:10 Sent To  
Notes
2016-08-08 19:16:02 
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-27 Cont ID  
Sent By albarran Date 2016-09-27 Time 19:35 Rev Time 0.00
Received By albarran Date 2016-09-23 Time 07:10 Sent To I
Notes
2016-09-27 19:36:39ELECTRICAL REVIEW APPROVED. ALL PREVIOUSLY MENTIONED
 DEFICIENCIES HAVE BEEN SATISFACTORILY ADDRESSED.
2016-09-23 10:12:313RD ELECTRICAL REVIEW:
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: DOCK/PIER & SEAWALL
 JOB ADDRESS: 3200 WASHINGTON RD.
 DESCRIPTION: REPAIR 102 FT. OF SEAWALL; REPLACE DOCK
 W/PIER, ACCESS PIER AND PLATFORM. INSTALL A 16K & A 10K
 LB. FOUR POLE BOAT LIFT.
 MASTER PERMIT: 16080055
  
 0. NOW THAT AN ELECTRICAL SHEET HAS BEEN PROVIDED,
 BELOW ARE THE DEFICIENCIES NOTED AT THE TIME OF THE
 ELECTRICAL PLAN REVIEW.
 SECTION 107.2.1.4 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT BUILDING PLANS BE DRAWN TO A
 MINIMUM 1/8? SCALE. THE PLANS SUBMITTED ARE WAY TOO
 SMALL TO BE LEGIBLE.
 1. PROVIDE PROOF OF THE REQUIRED LONGSHORE & HARBOR
 WORKERS COMPENSATION INSURANCE.
 YOU WERE PREVIOUSLY ASKED TO PROVIDE PROOF OF LONGSHORE
 & HARBOR WORKERS COMP AS REQUIRED BY TITLE 33 CHAP 18
 OF THE DEPT. OF LABOR.
 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 THE DOCUMENTS ARE NOT YET SIGNED AS REQUIRED.
 3. YOU SHALL INCLUDE ON THE SITE DRAWING THE LOCATION
 OF THE OVERCURRENT PROTECTION AND OR DISCONNECTS FOR
 THE PIER.
 THERE SHALL BE A READILY ACCESSIBLE DISCONNECT ON LAND
 TO DISCONNECT ALL POWER TO THE PIER.
 4. YOU WILL NEED TO PROVIDE A WIRING DIAGRAM AND LOAD
 CALCS FOR THE PROPOSED INSTALLATION INCLUDING THE
 INDIVIDUAL MOTOR LOADS.
 YOU MENTIONED THE CONCURRENT LOADS BETWEEN THE SHORE
 POWER AND LIFT, BUT LOAD CALCS SHALL BE PROVIDED. YOU
 MAY CONSIDER IN THE CALCS EACH LIFT AS A UNIT.
 5. IF THE POWER WILL BE PROVIDED UNDER A SEPARATE
 PERMIT, YOU NEED TO PROVIDE THAT NUMBER AND INCLUDE ON
 THE DRAWING THE AVAILABLE POWER.
 SATISFIED: POWER TO PIER PROVIDED UNDER PERMIT
 16071076.
 6. FBC?R4002.9 NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS: 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE,
 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER?RESISTANT TYPE WR. THIS APPLIES TO THE OUTLETS
 IN THE PEDESTAL AS WELL.
 SATISFIED: THE OUTLETS INSTALLED ON THE PEDESTALS
 COMPLY WITH THIS REQUIREMENT, BUT YOU MAY HAVE TO
 REPLACE THE OUTLETS WITH ONES THAT ARE LISTED WEATHER
 RESISTANT AS REQUIRED BY CODE.
 7. NEC 555.19(B)(2): ALL RECEPTACLES OTHER THAN THOSE
 DESIGNATED FOR SHORE POWER SHALL BE MARKED TO INDICATE
 THAT THEY ARE NOT TO BE USED FOR SHORE POWER TO BOATS.
 THIS CAN BE ADDRESSED WITH A BLOCK NOTE TO BE VERIFIED
 IN THE FIELD.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-09-23 Cont ID  
Sent By albarran Date 2016-08-31 Time 13:51 Rev Time 0.00
Received By albarran Date 2016-08-31 Time 11:27 Sent To I
Notes
2016-08-31 13:51:562ND ELECTRICAL REVIEW:
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: DOCK/PIER & SEAWALL
 JOB ADDRESS: 3200 WASHINGTON RD.
 DESCRIPTION: REPAIR 102 FT. OF SEAWALL; REPLACE DOCK
 W/PIER, ACCESS PIER AND PLATFORM. INSTALL A 16K & A 10K
 LB. FOUR POLE BOAT LIFT.
 MASTER PERMIT: 16080055
  
 NOW THAT AN ELECTRICAL SHEET HAS BEEN PROVIDED, BELOW
 ARE THE DEFICIENCIES NOTED AT THE TIME OF THE
 ELECTRICAL PLAN REVIEW.
  
 1. PROVIDE PROOF OF THE REQUIRED LONGSHOREMAN?S WORKERS
 COMPENSATION INSURANCE.
 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 3. YOU SHALL INCLUDE ON THE SITE DRAWING THE LOCATION
 OF THE OVERCURRENT PROTECTION AND OR DISCONNECTS FOR
 THE PIER.
 4. YOU WILL NEED TO PROVIDE A WIRING DIAGRAM AND LOAD
 CALCS FOR THE PROPOSED INSTALLATION INCLUDING THE
 INDIVIDUAL MOTOR LOADS.
 5. IF THE POWER WILL BE PROVIDED UNDER A SEPARATE
 PERMIT, YOU NEED TO PROVIDE THAT NUMBER AND INCLUDE ON
 THE DRAWING THE AVAILABLE POWER.
 6. FBC-R4002.9 NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS: 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE,
 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE ?WR?. THIS APPLIES TO THE
 OUTLETS IN THE PEDESTAL AS WELL.
 7. NEC 555.19(B)(2): ALL RECEPTACLES OTHER THAN THOSE
 DESIGNATED FOR SHORE POWER SHALL BE MARKED TO INDICATE
 THAT THEY ARE NOT TO BE USED FOR SHORE POWER TO BOATS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2016-08-08 Cont ID  
Sent By albarran Date 2016-08-08 Time 19:17 Rev Time 0.00
Received By albarran Date 2016-08-08 Time 19:05 Sent To  
Notes
2016-08-08 19:17:25ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: DOCK/PIERS/SEAWALL
 JOB ADDRESS: 3200 WASHINGTON RD.
 DESCRIPTION: REPAIR 102? OF SEAWALL; REPLACE DOCK
 W/PIER, ACCESS PIER AND PLATFORM. INSTALL A 16K & 10K
 LB. FOUR POLE BOAT LIFT.
 MASTER PERMIT: 16080055
  
 1. THE SUBMITTED DRAWINGS DO NOT INCLUDE ELECTRICAL
 DATA FOR THE LIFTS. YOU SHALL PROVIDE AN ELECTRICAL
 PLAN SHOWING THE LOCATION OF THE POWER SOURCE AS WELL
 AS THE INTENDED WIRING METHOD. ALL TERMINAL CONNECTIONS
 INCLUDING THE REQUIRED DISCONNECT AND CONVENIENCE GFI
 OUTLETS.
 2. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS AND
 VOLTAGE DROP CALCULATIONS.
 3. ALL WORK SHALL COMPLY WITH NEC SECTION 682
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2016-08-04 Cont ID  
Sent By fmittner Date 2016-08-04 Time 11:10 Rev Time 0.00
Received By fmittner Date 2016-08-04 Time 11:10 Sent To  
Notes
2016-08-04 11:10:26SENT TO NATHAN FOR ZONING REVIEW
2016-08-03 08:07:42ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-27 Cont ID  
Sent By albarran Date 2016-09-27 Time 19:40 Rev Time 0.00
Received By albarran Date 2016-09-27 Time 14:24 Sent To  
Notes
2016-09-27 19:42:09IN LIEU OF CONTACTING GC, I NOTIFIED EC VIA EMAIL. NO
 EMAIL ON FILE FOR GC. FILE SENT TO SMALL READY BIN B.
 MA
2016-09-27 14:25:14ROUTED TO MICHAEL ALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By albarran Date 2016-09-23 Time 08:30 Rev Time 0.00
Received By cpuell Date 2016-09-14 Time 13:20 Sent To  
Notes
2016-09-15 13:20:37MALBARRAN'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-31 Cont ID  
Sent By albarran Date 2016-08-31 Time 14:27 Rev Time 0.00
Received By albarran Date 2016-08-25 Time 08:13 Sent To  
Notes
2016-08-31 14:29:548/31/16 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. FILE SENT TO SMALL DENIED BIN ?B?. MA
2016-08-26 08:14:06RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 15:09 Rev Time 0.00
Received By cthroop Date 2016-08-02 Time 12:54 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-30 Cont ID  
Sent By njwira Date 2016-08-30 Time 11:39 Rev Time 0.00
Received By njwira Date 2016-08-26 Time 15:46 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By cthroop Date 2016-08-09 Time 15:10 Rev Time 0.00
Received By njwira Date 2016-08-04 Time 13:50 Sent To E
Notes
2016-08-04 13:53:148/3/16- FAILED
  
 1. DOCK MUST BE IN THE MIDDLE 1/3 OF THE PROPERTY AS
 INDICATED IN THE DRAWING.
 2. DRAWING MUST SHOW THE DIMENSIONS OF THE DRAWING
 MATCHING THE DESCRIPTION OF THE WORK BEING DONE.
 3. LADDER REQUIRED.
  
 PASSED
 1. MEETS STATE AND FEDERAL STANDARDS.
 2. DOCK LENGTH IS 97FT. AND MEETS THE 100FT. LENGTH
 LIMIT.
 3. DOCK IS 5FT. WIDE AND MEETS THE 10FT. LIMIT
  