Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-08-03 Cont ID  
Sent By albarran Date 2016-08-03 Time 08:32 Rev Time 0.00
Received By albarran Date 2016-08-02 Time 18:21 Sent To I
Notes
2016-08-03 08:32:48ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: JOSEPH WEINBERG
 JOB ADDRESS: 8744 LAKES BLVD.
 DESCRIPTION: INSTALLATION OF STAND-BY GENERATOR
 MASTER PERMIT:16071222
 REVISION:
  
 PERMIT CONDITIONALLY APPROVED WITH THE FOLLOWING
 CORRECTIONS TO THE SUBMITTAL. ALL WORK IS SUBJECT TO
 FIELD INSPECTOR?S APPROVAL.
 1. NEC 240.4(B): DUE TO THE OCPD INCORPORATED INTO THE
 GENERATOR OF 100 AMP #4 CU WILL NOT BE PROTECTED.
 2. NEC 310.15(B): CONDUCTOR FOR 100 AMP IS #3CU (#4CU
 IS FOR 85 AMP)
 3. NEC 240.6: THE NEXT STANDARD OCPD FOR #4 IS 90 AMP,
 NOT 100.
 4. NEC 250.122: EQUIPMENT GROUNDING CONDUCTOR FOR 100
 AMP IS #8. NOTHING SAYS YOU CANT USE #6.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By albarran Date 2016-08-03 Time 08:34 Rev Time 0.00
Received By albarran Date 2016-07-29 Time 10:02 Sent To  
Notes
2016-08-03 08:37:53PERMIT IS RUNNING WITH THE GAS PERMIT 16071221. WALKED
 TO GJ (PLUMBING) FOR REVIEW.
2016-08-01 10:03:20ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-01 Cont ID  
Sent By njwira Date 2016-08-01 Time 16:55 Rev Time 0.00
Received By njwira Date 2016-08-01 Time 15:06 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved