Plan Review Details - Permit 16071217
Plan Review Stops For Permit 16071217
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-12-06 Cont ID  
Sent By jwitmer Date 2016-12-06 Time 09:44 Rev Time 0.00
Received By jwitmer Date 2016-12-06 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-15 Cont ID  
Sent By jwitmer Date 2016-08-15 Time 06:57 Rev Time  
Received By jwitmer Date 2016-08-15 Time   Sent To  
Notes
2016-08-15 06:57:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071217
 ADD: 505 BANYAN ST./ COUNTY PARKING GARAGE
 CONT: CARRICK
 TEL: 561-844-5322
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 15/ 2016
 ACTION: DENIED
  
 1) PLANS SUBMITTED FROM JOBY L. BALINT AR 0016653
 APPEAR TO BE PLANS THAT WERE SHRUNK NOT TO SCALE. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
  
 2) PLANS SUBMITTED FROM JOBY L. BALINT AR 0016653 ARE
 NOT SIGNED NOR SEALED. FL ADMIN CODE 61G16.003
 ARCHITECTS PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE
 FROM THE ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM
 OF FIRST AND LAST NAME AS SHOWN ON THE ARCHITECTS'
 LICENSE, FAC 61G1-16.003.
  
 3) PLEASE NOTE THE SUBMITTALS/ ENERGY DOCUMENTS WERE
 SUBMITTED FOR THE STATE APPROVED PLANS NO. 16-089
 PAR-KUT INTERNATIONAL BUT NO APPROVED PLANS!!!!
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-16 Cont ID  
Sent By mvaldes Date 2016-11-16 Time 10:58 Rev Time 0.00
Received By mvaldes Date 2016-11-16 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By mvaldes Date 2016-08-01 Time 15:09 Rev Time 0.00
Received By mvaldes Date 2016-08-01 Time 14:08 Sent To  
Notes
2016-08-01 14:35:01REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1) FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2) FBC-107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT
  
 3) NEC 215.5 PROVIDE A DIAGRAM SHOWING FEEDER ROUTING,
 SERVICE RISER DIAGRAM TO SHOW POWER SOURCE FROM UTILITY
 SERVICE.
  
 4) FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP.
  
 5) PROVIDE AIC RATING OF OCPD AND ELECTRICAL EQUIPMENT
 NEC 110.9 & 110.10, FPL LETTER MIGHT BE REQUIRED TO
 VERIFY AVAILABLE FAULT CURRENT NEC 110.24(A)
  
 6) OUTDOOR ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN
 SUITABLE ENCLOSURES AND SHALL BE PROTECTED FROM
 ACCIDENTAL CONTACT BY UNAUTHORIZED PERSONNEL, OR BY
 VEHICULAR TRAFFIC, OR BY ACCIDENTAL SPILLAGE OR LEAKAGE
 FROM PIPING SYSTEMS. IF APPLICABLE PLEASE PROVIDE
 PROPER GUARDING NEC 110.27
  
 ADDITIONAL COMMENTS MAY BE ADDED ON THE NEXT SUBMITTAL
 IF NECCESSARY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-11-22 Cont ID  
Sent By pleduc Date 2016-11-22 Time   Rev Time 0.00
Received By pleduc Date 2016-11-22 Time 16:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-08 Cont ID  
Sent By pleduc Date 2016-08-08 Time   Rev Time 0.00
Received By pleduc Date 2016-08-08 Time 16:51 Sent To  
Notes
2016-08-08 17:05:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE DOES NOT HAVE AN OBJECTION TO THE PROPOSED;
 HOWEVER, IT WILL NOT BE REVIEW STAMPED BASED ON THE
 BELOW COMMENT.
  
 1) FOUR (4) PLAN SHEETS WERE SUBMITTED; HOWEVER, TWO
 (2) SHEETS APPEAR TO HAVE MATCHING PAPERWORK AND TWO
 (2) SHEETS DO NOT. WHICH PLAN SETS ARE CORRECT?
  
 PLEASE REVIEW AND CORRECT/CLARIFY AND PROVIDE MATCHING
 PAPERWORK FOR ALL FOUR (4) SHEETS.
  
  
 2) WILL THERE BE FIRE EXTINGUISHERS PROVIDED IN OR
 AROUND EACH BOOTH?
  
 PLEASE INDICATE WITH A NOTE THE NEAREST FE WITHIN THE
 GARAGE OR PROVIDE ONE AT THE CENTER BOOTH.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-22 Cont ID  
Sent By lmarchan Date 2016-12-22 Time 14:38 Rev Time 0.00
Received By lmarchan Date 2016-11-09 Time 12:00 Sent To  
Notes
2016-11-09 12:00:32C05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-26 Cont ID  
Sent By tklarge Date 2016-08-26 Time 07:34 Rev Time 0.00
Received By lmarchan Date 2016-07-29 Time 11:38 Sent To  
Notes
2016-08-25 11:28:22TO LMERCHANT
2016-07-29 11:38:10C11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-18 Cont ID  
Sent By ccole Date 2016-11-18 Time 16:35 Rev Time 0.00
Received By ccole Date 2016-11-18 Time 16:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By ccole Date 2016-08-04 Time 07:55 Rev Time 0.00
Received By ccole Date 2016-08-04 Time 07:55 Sent To  
Notes
2016-08-04 08:03:001ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 PERMIT #16071217
 8/3/16
  
 1) SUBMIT ORIGINAL PLANS FOR ALL SITE-RELATED WORK ON
 THE PROJECT INCLUDING FOUNDATION DETAILS, ELECTRICAL
 AND MECHANICAL CONNECTIONS ETC.- SEE FLORIDA STAUTES
 553.38. ALL SUBMITTED SITE RELATED PLANS SHALL BEAR THE
 ORIGINAL SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 PER FLORIDA STATURE AND FAC 61G15.
 SEE ALSO SECTION 107.1 WPB AMENDMEMTS TO THE FBC:
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 2) PROVIDE AC PLANS AND COOLING AND HEATING
 CALCULATIONS IN COMPLIANCE WITH SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION.
  
 3) PLEASE NOTE SITE SPECIFIC WIND LOAD ENGINEERING IS
 REQUIRED FOR ALL EXTERIOR MECHANICAL EQUIPMENT
 INSTALLATIONS- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-29 Cont ID  
Sent By gjohnson Date 2016-11-29 Time 17:19 Rev Time 0.00
Received By gjohnson Date 2016-11-29 Time 17:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-24 Cont ID  
Sent By tklarge Date 2016-08-24 Time 04:22 Rev Time 0.00
Received By tklarge Date 2016-08-24 Time 04:09 Sent To  
Notes
2016-08-24 04:19:20SECTION 403.3.3 OF THE 2014 FBC-PLUMBING REQUIRES
 SANITARY FACILITIES TO BE ON A PATH OF TRAVEL NOT TO
 EXCEED A DISTANCE OF 500 FEET. INDICATE ON THE SITE
 PLAN THAT SANITARY FACILITIES ARE WITHIN A DISTANCE OF
 500 FEET OF THESE TICKET BOOTHS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-12-22 Cont ID  
Sent By aaponte Date 2016-12-22 Time 14:23 Rev Time 0.00
Received By aaponte Date 2016-12-22 Time 14:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-25 Cont ID  
Sent By aaponte Date 2016-08-25 Time 11:28 Rev Time 0.00
Received By aaponte Date 2016-08-25 Time 11:28 Sent To  
Notes
***NONE***