Plan Review Details - Permit 16071123
Plan Review Stops For Permit 16071123
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-06 Cont ID  
Sent By rmcdouga Date 2016-09-06 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2016-09-06 Time 07:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By rmcdouga Date 2016-07-29 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2016-07-29 Time 17:51 Sent To P
Notes
2016-07-29 18:07:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY WHAT THE AREA BESIDE THE SPA WITH THE LIGHT
 IS PROPOSED TO BE. FBC 107.2.1
  
 2) PROVIDE THE DIMENSIONS OF THE SPA AND THE AREA NEXT
 TO IT THAT IS NOT IDENTIFIED ON THE PLANS. FBC 107.2.1
  
 3) SPECIFY HOW THE POOL WILL COMPLY WITH THE
 RESIDENTIAL POOL BARRIER REQUIREMENTS. FBCR 4501.17
  
 4) SPECIFY HOW THE POOL EQUIPMENT WILL BE ANCHORED TO
 RESIST WIND LOADS. FBCR 301.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-06 Cont ID  
Sent By rmcdouga Date 2016-09-06 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2016-09-06 Time 07:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By rmcdouga Date 2016-07-29 Time 17:44 Rev Time 0.00
Received By rmcdouga Date 2016-07-29 Time 17:44 Sent To  
Notes
2016-07-29 17:49:49PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS AND
 A PANEL SCHEDULE TO SHOW THAT THE EXISTING ELECTRICAL
 SYSTEM IS ADEQUATE TO ADD THE POOL HEATER AND
 EQUIPMENT. FBC 107.2.3
  
 2) SHOW COMPLIANCE WITH FBCR - E4204.3 FOR BONDING OF
 THE POOL WATER.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-07-29 Cont ID  
Sent By rmcdouga Date 2016-07-29 Time 17:44 Rev Time 0.00
Received By rmcdouga Date 2016-07-29 Time 17:44 Sent To  
Notes
2016-07-29 18:10:53NO GAS SHOWN ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-06 Cont ID  
Sent By rmcdouga Date 2016-09-06 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2016-08-31 Time 15:34 Sent To  
Notes
2016-08-31 15:34:36RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 03:15 Rev Time 0.00
Received By tklarge Date 2016-07-27 Time 15:30 Sent To  
Notes
2016-07-27 15:30:38ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-06 Cont ID  
Sent By tklarge Date 2016-09-06 Time 07:02 Rev Time 0.00
Received By tklarge Date 2016-09-06 Time 06:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 03:15 Rev Time 0.00
Received By tklarge Date 2016-07-30 Time 02:30 Sent To  
Notes
2016-07-30 03:02:201) SPECIFY WHAT THE AREA WITH THE LIGHT THAT IS
 ADJACENT TO THE SPA IS PROPOSED TO BE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) THE NOTES ON SHEET 2 OF 2 AT THE POOL & SPA PIPE
 SCHEMATIC ARE BECOMING DIFFICULT TO READ. PLEASE
 ADDRESS THIS COMMENT FOR FUTURE SUBMITTALS AND ENSURE
 THE NOTES ARE LEGIBLE.
 3) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE
 WATER SERVICE. THIS SHALL BE DONE AS A SEPARATE PERMIT
 SUBMITTAL.
 4) A TEST REPORT FROM AN INDEPENDENT LABORATORY IS
 REQUIRED TO VERIFY PROCEDURE COMPLIANCE OF THE HEAT
 PUMP WITH AHRI 1160 PER THE 2014 FBC-ENERGY
 SEC.R403.9.1.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-09-01 Cont ID  
Sent By njwira Date 2016-09-01 Time 15:55 Rev Time 0.00
Received By njwira Date 2016-09-01 Time 08:28 Sent To E
Notes
2016-09-01 15:56:499/1/16- POOL EQUIPMENT MOVED TO MEET ZONING
 REQUIREMENTS.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By njwira Date 2016-07-29 Time 15:08 Rev Time 0.00
Received By njwira Date 2016-07-27 Time 16:55 Sent To P
Notes
2016-07-29 15:16:187/29/16- FAILED
  
 ZONE: SF-14
  
 FAILED
  
 1. POOL EQUIPMENT REQUIRES A 11FT. REAR SETBACK AND HAS
 A 4FT. REAR SETBACK.
 2. REMOVAL OF TREES REQUIRES A TREE ALTERATION PERMIT.
  
 PASSED
 1. SIDE SETBACK IS 8FT. AND MEETS THE 5FT. SETBACK
 REQUIREMENT
 2. REAR SETBACK IS 17FT. AND MEETS THE 5FT. SETBACK
 REQUIREMENT.
 3. REAR YARD
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  