Plan Review Details - Permit 16071041
Plan Review Stops For Permit 16071041
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-03 Cont ID  
Sent By jwitmer Date 2016-08-03 Time 06:31 Rev Time  
Received By jwitmer Date 2016-08-03 Time 06:00 Sent To  
Notes
2016-08-03 16:51:28BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16071041
 ADD: 1254 PALM BEACH LAKES BLVD.
 CONT: TBD
 TEL: 561-577-6874
 E-MAIL: ???????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 03/2016
 ACTION: DENIED
  
 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE SPRINKLERS
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT- PLAYGROUND
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 2) THE PERMIT APPLICATION INDICATES THIS IS A CHANGE OF
 USE TO DAYCARE FACILITY. PLEASE PROVIDE TO WHICH
 CLASSIFICATION YOU ENTEND TO USE THIS SPACE. DEFINE THE
 USE OF SPACE.
  
 305.2 GROUP E, DAY CARE FACILITIES. THIS GROUP INCLUDES
 BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OCCUPIED
 BY MORE THAN FIVE CHILDREN OLDER THAN 21/2 YEARS OF AGE
 WHO RECEIVE EDUCATIONAL, SUPERVISION OR PERSONAL CARE
 SERVICES FOR FEWER THAN 24 HOURS PER DAY.
  
 308.6.1 CLASSIFICATION AS GROUP E.
 A CHILD DAY CARE FACILITY THAT PROVIDES CARE FOR MORE
 THAN FIVE BUT NO MORE THAN 100 CHILDREN 21/2 YEARS OR
 LESS OF AGE, WHERE THE ROOMS IN WHICH THE CHILDREN ARE
 CARED FOR ARE LOCATED ON A LEVEL OF EXIT DISCHARGE
 SERVING SUCH ROOMS AND EACH OF THESE CHILD CARE ROOMS
 HAS AN EXIT DOOR DIRECTLY TO THE EXTERIOR, SHALL BE
 CLASSIFIED AS GROUP E.
  
 CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT
 ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT
 RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS
 WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN
 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS
 CHILD CARE FACILITIES AND CONSIDERED TO BE GROUP I-4.
  
 308.6 INSTITUTIONAL GROUP I-4, DAY CARE FACILITIES.
 THIS GROUP SHALL INCLUDE BUILDINGS AND STRUCTURES
 OCCUPIED BY MORE THAN FIVE PERSONS OF ANY AGE WHO
 RECEIVE CUSTODIAL CARE FOR FEWER THAN 24 HOURS PER DAY
 BY PERSONS OTHER THAN PARENTS OR GUARDIANS, RELATIVES
 BY BLOOD, MARRIAGE OR ADOPTION, AND IN A PLACE OTHER
 THAN THE HOME OF THE PERSON CARED FOR. THIS GROUP SHALL
 INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
 CHILD DAY CARE
 ADULT DAY CARE
  
 3) 2014 FBC-B 1015.6 DAY CARE MEANS OF EGRESS. DAY CARE
 FACILITIES, ROOMS OR SPACES WHERE CARE IS PROVIDED FOR
 MORE THAN 10 CHILDREN THAT ARE 21/2 YEARS OF AGE OR
 LESS, SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR
 EXIT ACCESS DOORWAYS.
  
 4) 2014 FBC-B 466.2 CLOSET DOORS. EVERY CLOSET DOOR
 LATCH SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM
 INSIDE THE CLOSET.
  
 5) 2014 FBC-B 466.3 BATHROOM DOORS. EVERY BATHROOM DOOR
 LOCK SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED
 DOOR FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING
 DEVICE SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 6) PLEASE SHOW CODE COMPLIANCE WITH 466.7 DETECTION AND
 ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 907
 AND THIS SECTION, 466.7.1 & 466.7.1.1.
  
 7) 2014 FBC-B 466.7.2 DETECTION. A SMOKE DETECTION
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 WITH PLACEMENT OF DETECTORS IN EACH STORY IN FRONT OF
 DOORS TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL
 FLOORS OCCUPIED BY THE DAY CARE OCCUPANCY. DETECTORS
 ALSO SHALL BE INSTALLED IN LOUNGES, RECREATION AREAS
 AND SLEEPING ROOMS IN THE DAY CARE OCCUPANCY.
  
 8) 2014 FBC-B 466.8 CORRIDORS. EVERY INTERIOR CORRIDOR
 SHALL BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING.
 EXCEPTION: 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTIONS 901.6 AND 903.3.1.1, CORRIDOR
 WALLS SHALL NOT BE REQUIRED TO BE RATED, PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION 710.
 EXCEPTION: 2. 2. WHERE THE CORRIDOR CEILING IS AN
 ASSEMBLY HAVING 1-HOUR FIRE-RESISTANCE RATING WHERE
 TESTED AS A WALL, THE CORRIDOR WALLS SHALL BE PERMITTED
 TO TERMINATE AT THE CORRIDOR CEILING.
  
 9) ) PLEASE NOTE THE FBC-B CHAPTER 468 SECTION OF THE
 CODE ALSO DEALS WITH SCHOOLS AND WOULD NEED TO BE
 REVIEWED FOR CODE COMPLIANCE.
 9A) 468.2.2 PLAYGROUNDS AND EQUIPMENT.
 PLAYGROUNDS AND EQUIPMENT SHALL BE SAFE, STRUCTURALLY
 SOUND, VERMIN PROOF, AND SHALL NOT HAVE JAGGED OR SHARP
 PROJECTIONS. PLAYGROUND EQUIPMENT SHALL BE ANCHORED TO
 SUITABLE FOUNDATIONS TO PREVENT TOPPLING OR
 DISLODGEMENT. CUSHIONING MATERIALS SUCH AS MATS, WOOD
 CHIPS, OR SAND SHALL BE USED UNDER CLIMBING EQUIPMENT,
 SLIDES, AND SWINGS.
  
 9B) 468.2.3 OUTDOOR WASTE CONTAINERS. A SMOOTH
 NONABSORBENT SURFACE SHALL BE PROVIDED FOR OUTDOOR
 WASTE CONTAINERS.
  
 9C) 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING
 STATION SHALL BE LOCATED IN OR ADJACENT TO ANY
 CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN
 ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED
 WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE
 PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR
 TOUCHING A HANDLE.
  
 9D) 468.3.5.2 TEACHER TOILETS. FACULTY AND STAFF
 TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS.
  
 9E) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE
 IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM)
 ABOVE THE FLOOR. WALLS IN KITCHENS, SCULLERIES, CAN
 WASH AREAS, AND SHOWER ROOMS SHALL BE IMPERVIOUS TO A
 HEIGHT OF AT LEAST 6 FEET (1829 MM) ABOVE THE FLOOR.
 TOILET AND SHOWER PARTITIONS SHALL BE IMPERVIOUS.
  
 4F) 2014 FBC-ACCESS. CODE 604.1 GENERAL. WATER CLOSETS
 AND TOILET COMPARTMENTS SHALL COMPLY WITH 604.2 THROUGH
 604.8. EXCEPTION: WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE SHALL BE PERMITTED TO COMPLY WITH
 604.9. 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
 9G)(1)603.2.1 TURNING SPACE. TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 9G)(2) 603.2.2 OVERLAP. REQUIRED CLEAR FLOOR SPACES,
 CLEARANCE AT FIXTURES, AND TURNING SPACE SHALL BE
 PERMITTED TO OVERLAP. THIS NOTE IS FOR THE SINGLE
 BATHROOM, MISSING CLEARANCE AROUND THE WATER CLOSET.
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 9H) LOCATION OF PORTABLE FIRE EXTINGUISHERS 2014 FBC-B
 906.1 WHERE REQUIRED.
  
 10) PLEASE NOTE THIS IS A CHANGE IN OCCUPANCY FROM
 MERCANTILE TO EDUCATIONAL. UNDER THE 2014 EXISTING
 BUILDING CODE 1012.4 MEANS OF EGRESS.
 EXST. BLDG CODE 1012.4.2 MEANS OF EGRESS FOR CHANGE OF
 USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF
 OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL OR LESSER
 HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE
 1012.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 905 FOR THE NEW
 OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS
 SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR
 MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE.
  
 2014 EXST. BLDG. CODE. 805.4.4.1 SUPPLEMENTAL
 REQUIREMENTS FOR PANIC HARDWARE. WHERE THE WORK AREA
 EXCEEDS 50 PERCENT OF THE FLOOR AREA, PANIC HARDWARE
 SHALL COMPLY WITH SECTION 805.4.4 THROUGHOUT THE FLOOR.
  
 11) THE SUBMITTED PLANS INDICATES THE REAR EXIT LEADS
 INTO A FENCED EXTERIOR PLAYGROUND WITH A GATE. THERE IS
 NO GATE TO GET OUT OF THE REAR EXIT TO THE PUBLIC WAY.
  
 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF
 EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF
 THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF
 EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR
 DOORS.
  
 12) 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF
 50 OR MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE
 PROVIDED WITH A LATCH OR LOCK UNLESS IT IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE.
  
 13) 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF
 EGRESS IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM
 ANY ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE
 SPACE SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF
 EGRESS.
  
 PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE MET FROM THE
 REAR EXIT DOOR (EXIT DISCHARGE) TO THE PUBLIC WAY.
  
 14) PLEASE NOTE THERE ARE NO DETAILS FOR THE ACCESSIBLE
 ELEMENTS SUCH AS REST ROOMS, LAVS, .2014 FBC-ACCESS.
 CODE 606.3 HEIGHT OF 34 INCHES TO THE RIM OR COUNTER
 SURFACE.
  
 15) SHEET A-1.01 THE RESTROOMS IF THIS IS A FACILITY
 FOR YOUNG CHILDREN ARE GOING TO BE FACILITIES AGE
 APPROPRIATE FACILIIES THAT WILL SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBLITY CODE 604.9.
  
 16) ) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By albarran Date 2016-07-28 Time 12:21 Rev Time 0.00
Received By albarran Date 2016-07-28 Time 11:55 Sent To  
Notes
2016-07-28 12:21:30ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: BRIGHT FROM THE START CHILD CARE
 JOB ADDRESS: 1254 PALM BEACH LAKES BLVD.
 DESCRIPTION: CHANGE OF OCCUPANCY FROM RETAIL TO CHILD
 DAYCARE
 MAST. PERMIT: 16071041
 REVISION:
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE
 THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 2. FOR PROPER DETERMINATION OF MINIMUM REQUIREMENTS,
 THE NUMBER OF BEDS (CHILD COUNT) ACCEPTED AT ONE TIME
 AND THE AGE GROUPS.
 3. AS PART OF THE REQUIRED DRAWINGS, YOU SHALL PROVIDE
 ELECTRICAL SHEETS AS INDICATED IN THE FBC-B 107.3.5
 ELECTRICAL. INCLUDE THE LOCATION OF EVERY ELECTRICAL
 OUTLET, LUMINAIRE AND ITS RESPECTIVE SWITCH. THE
 LOCATION OF THE ELECTRICAL PANEL SHALL BE SO INDICATED
 AS WELL.
 4. THE LIGHTING SHALL COMPLY WITH THE REQUIREMENTS OF
 THE FBC-ENERGY CONSERVATION.
 5. NEC 215.5: ELECTRICAL RISER DIAGRAM WITH LOAD CALCS.
 6. NEC 408.4: PANEL SCHEDULE
 7. THE ABOVE IS NOT A COMPREHENSIVE LIST OF ALL THE
 ELECTRICAL SUBMITTAL REQUIREMENTS. THE ASSISTANCE OF A
 DESIGN PROFESSIONAL WILL FACILITATE THE SUBMITTAL.
 8. FIRE ALARM SHALL BE PROVIDED UNDER A SEPARATE PERMIT
 AND SUBMITTAL PACKAGE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By wjolin Date 2016-07-28 Time 09:35 Rev Time 0.00
Received By wjolin Date 2016-07-28 Time 08:59 Sent To  
Notes
2016-07-28 09:35:241254 PALM BEACH LAKES BOULEVARD
 PERMIT #16071041
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 NO AGE GROUPS, NUMBER OF CLIENTS OR NUMBER OF STAFF
 PROVIDED. PER SECTION 16.7.5 DAY-CARE STAFF. ADEQUATE
 ADULT STAFF SHALL BE ON DUTY IN THE FACILITY AND ALERT
 AT ALL TIMES WHERE CLIENTS ARE PRESENT.
  
 PER SECTION 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM
 DOOR LOCK SHALL BE DESIGNED TO ALLOW OPENING OF THE
 LOCKED DOOR FROM THE OUTSIDE BY AN OPENING DEVICE THAT
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 PER SECTION 16.7.3 INSPECTIONS. FIRE PREVENTION
 INSPECTIONS SHALL BE CONDUCTED MONTHLY BY A TRAINED
 SENIOR MEMBER OF THE STAFF, AFTER WHICH A COPY OF THE
 LATEST INSPECTION REPORT SHALL BE POSTED IN A
 CONSPICUOUS PLACE IN THE DAY-CARE FACILITY.
  
 PER SECTION 16.7.3.3 IT SHALL BE THE DUTY OF SITE
 ADMINISTRATORS AND STAFF MEMBERS TO INSPECT ALL EXIT
 FACILITIES DAILY TO ENSURE THAT ALL STAIRWAYS, DOORS,
 AND OTHER EXITS ARE IN PROPER CONDITION.
  
 THE TWO BATHROOM DOORS OBSTRUCT EGRESS. DURING ITS
 SWING, ANY DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT
 LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE,
 CORRIDOR, HALLWAY OR LANDING UNOBSTRUCTED AND SHALL
 PROJECT NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH
 OF THE EGRESS PATH WHEN FULLY OPEN.
  
 NO EMERGENCY LIGHTING PROVIDED.
  
 REAR EXIT LEADS TO A FENCED ENCLOSURE. FENCED
 PLAYGROUND AREA SHALL BE PROVIDED WITH TWO SEPARATED
 EXITS. NO DETAILS OF PLAYGROUND AREA SUBMITTED.
  
 PLANS DO NOT INDICATE A FIRE RATING BETWEEN THE
 DAY-CARE OCCUPANCY AND THE NEIGHBORING TENTANTS PER
 TABLE 6.1.14.4.1(A).
  
 WILL THE DAY-CARE BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR A FIRE ALARM SYSTEM?
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By cpuell Date 2016-10-03 Time 13:06 Rev Time 0.00
Received By cpuell Date 2016-07-25 Time 11:13 Sent To  
Notes
2016-07-26 11:14:24B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-03 Cont ID  
Sent By jwitmer Date 2016-08-03 Time 09:36 Rev Time 0.00
Received By jwitmer Date 2016-08-03 Time 09:36 Sent To  
Notes
2016-08-03 09:37:01BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-23 Cont ID  
Sent By gjohnson Date 2016-08-23 Time 15:29 Rev Time 0.00
Received By gjohnson Date 2016-08-23 Time 15:29 Sent To  
Notes
2016-08-23 15:29:191ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. WHAT TYPE OF DAY CARE WILL THIS BE, IF IT IS FOR
 CHILDREN PROVIDE A LIST OF THE AGE GROUP ALONG WITH THE
 OCCUPANT LOAD. IF THE FACILITY IS FOR CHILD DAYCARE YOU
 WILL NEED SEPARATE FACILITIES FOR THE BOYS AND GIRLS
 AND ONE FOR THE STAFF. WPB AMEND. TO FBC 107.2.1
  
 2. SHOW COMPLIANCE WITH FBC ACC CHAPTER 6
  
 3. A DRINKING FOUNTAIN IS REQUIRED. PR FBC PL TABLE
 403.1
  
 4. PLAN SHALL COMPLY WITH FBC EXISTING BUILDING CHAPTER
 10
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-09-14 Cont ID  
Sent By awooten Date 2016-09-14 Time 10:58 Rev Time 0.00
Received By awooten Date 2016-09-12 Time 08:32 Sent To  
Notes
2016-09-14 10:57:55****ZONING REVIEW FAILED*****
  
 A DAYCARE FACILITIES FOR CHILDREN AS A PRINCIPAL USE IS
 PERMITTED AT THIS LOCATION, BUT ARE SUBJECT TO
 ADDITIONAL STANDARDS (PXR).
  
 ADDITIONAL REQUIREMENTS:
 A.) PROVIDE A WRITTEN STATEMENT THAT THE PROPOSED DAY
 CARE CENTER WILL COMPLY WITH ALL APPLICABLE COUNTY AND
 STATE REGULATIONS.
 B.) APPLICATIONS TO ESTABLISH CHILD DAY CARE CENTER
 SHALL COMPLY WITH THE REQUIREMENTS OF LAWS OF FLA. CH.
 59 (1968), AS AMENDED.
  
 PLEASE FEEL FREE TO CONTACT ME WITH ANY QUESTIONS YOU
 MAY HAVE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  
  