Plan Review Details - Permit 16070877
Plan Review Stops For Permit 16070877
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-10-17 Cont ID  
Sent By shill Date 2016-10-17 Time 08:41 Rev Time 0.00
Received By shill Date 2016-10-17 Time 08:41 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By shill Date 2016-07-26 Time 08:02 Rev Time 0.00
Received By shill Date 2016-07-26 Time 08:02 Sent To P
Notes
2016-07-26 08:40:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, PROVIDE A SITE PLAN SHOWING LOCATION OF
 PROPOSED WORK.
  
 2. PROVIDE A PLAN (DETAILS) WHICH SHOW PROPOSED WORK.
 THE PERMIT DOCUMENTS ARE TO BE CLEAR AS TO SCOPE,
 NATURE, LOCATION. "REMOVE THE EXISTING LINEAR CEILING
 MATERIAL . . . " DOES NOT INCLUDE INFORMATION SUCH AS -
 WHAT IS THE MATERIAL? IS IT SUBJECT TO WIND LOADS? IS
 IT FIRE RATED? IF OUTDOORS, HOW WITH THE "NEW LINEAR
 CEILING" BE FASTENED TO RESIST WIND LOADS? ENGINEERING
 (FASTENING TO RESIST WIND LOADS) FOR A PUBLIC
 COMMERCIAL BUILDING IS REQUIRED BY FLORIDA STATUTE TO
 BE PREPARED BY A DESIGN PROFESSIONAL. NOT ENOUGH
 INFORMATION HAS BEEN PROVIDED TO PROVIDE A COMPLETE
 CHECKLIST.
  
 3. THE PLAN IS TO INCLUDE ALL INFORMATION REQUIRED TO
 DEMONSTRATE CODE COMPLIANCE, WHICH SHOULD INCLUDE: WIND
 DESIGN CRITERIA, BUILDING TYPE (FBC CHAPTER 6),
 BUILDING HEIGHT, GOVERNING CODE AND VERSION (SHOULD
 INCLUDE ALL APPLICABLE CODES WHICH APPEARS TO INCLUDE
 FBC EXISTING BUILDING AND BUILDING, PLUMBING),
 MATERIALS EXISTING, MATERIALS PROPOSED, STRUCTURAL
 DETAIL FOR THE "LINEAR VENEER CEILING".
  
 4. IF THIS IS TYPE I OR II CONSTRUCTION, SEE ALSO FBC
 603. PLAN IS TO INCLUDE THE EXCEPTION AND SUPPORTING
 DATA IS TO INCLUDE SPEC SHEETS WHICH DEMONSTRATE
 COMPLIANCE. THE PLAN IS TO INCLUDE INFORMATION
 REGARDING THE SPACE WHICH OPENS INTO THE PROPOSED WORK
 AREA (APPEARS TO BE AN EXIT, AND THE PROPOSED WORK AREA
 IS IN THE EXIT DISCHARGE).
  
 5. BASED ON THE DESCRIPTION, IT IS NOT CLEAR WHETHER OR
 NOT THE EXISTING ROOF DRAIN SYSTEM IS ADEQUATE. PROVIDE
 MORE INFORMATION REGARDING THE DRAIN SYSTEM AND THE
 PROPOSED ADDITION TO THE DRAIN SYSTEM, FBC 1503.
  
 6. FBC 5TH EDITION EXISTING BUILDING, PLAN SHOULD
 INCLUDE METHOD OF COMPLIANCE 301.1.
  
 7. ROOF AND PLUMBING SUB PERMITS ARE REQUIRED, FS489.
  
 8. THE PLAN IS TO INCLUDE ALL PERTINENT INFORMATION
 REGARDING THE PROPOSED REROOF - ROOF PITCH, MEAN ROOF
 HEIGHT, PARAPET INFO AND, IF APPLICABLE, PARAPET
 HEIGHT. A PRODUCT APPROVAL WAS PROVIDED, A SYSTEM
 HIGHLIGHTED, BUT IT DOES NOT APPEAR TO COMPLY WITH THE
 DESIGN PRESSURES REQUIRED FOR THIS PROJECT. IT IS NOT
 POSSIBLE TO DO A COMPLETE REVIEW WITHOUT THE
 INFORMATION LISTED, FBC 1609. IF ENHANCED FASTENING IS
 REQUIRED, PROVIDE AT THIS TIME (PREPARED BY A DESIGN
 PROFESSIONAL).
  
 9. IF INFORMATION REGARDING THE EXISTING BUILDING IS
 NEEDED, A RECORDS RESEARCH REQUEST MAY BE SUBMITTED VIA
 EMAIL TO [email protected].
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-27 Cont ID  
Sent By pleduc Date 2016-09-27 Time   Rev Time 0.00
Received By pleduc Date 2016-09-27 Time 14:21 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-08-04 Cont ID  
Sent By pleduc Date 2016-08-04 Time   Rev Time 0.00
Received By pleduc Date 2016-08-04 Time 14:35 Sent To PC
Notes
2016-08-04 14:46:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROVIDED SHEETS DO NOT PROVIDE SUFFICIENT DETAIL
 FOR A COMPLETE PROJECT REVIEW, SEE ALSO BUILDING
 COMMENTS.
  
 NFPA 1, 5TH EDITION
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.11.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4.
  
 1.7.11.3 THE CONSTRUCTION DOCUMENTS FOR EACH PHASE
 SHALL BE COMPLETE IN THEMSELVES, SO THAT REVIEW AND
 INSPECTION CAN PROPERLY BE MADE. PRELIMINARY PLANS OF
 THE TOTAL BUILDING SHALL BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS, AND WITH SUFFICIENT DETAIL, SO
 THAT PROPER EVALUATION CAN BE MADE. AREAS AND ITEMS NOT
 INCLUDED IN THE PHASE TO BE PERMITTED SHALL BE SHOWN AS
 NOT INCLUDED.
  
  
 PLEASE PROVIDE SUFFICIENT PLAN DRAWING DETAIL AND
 SCALE.
  
  
 2) THE TECHICAL DATA SHEET FOR PRODUCT GL -5992 FR,
 FIRE RETARDANT COATING, PAGE 2 OF 3, SECTION 4.1
 PERFORMANCE DATA UNDER RECOMMENDED USAGE INDICATES
 "INTERIOR USE". THE APPLICATION SUBMITTED APPEARS TO BE
 EXTERIOR.
  
 PLEASE CORRECT OR CLARIFY.
  
  
  
  
 3) PROVIDE THE APPLICABLE LISTING OR PRODUCT SHEET FOR
 THE APPLICABLE ENVIROMENT IN COMPLIANCE WITH NFPA
 STANDARDS.
  
 12.5.7* FIRE-RETARDANT COATINGS.
 12.5.7.1* THE REQUIRED FLAME SPREAD OR SMOKE
 DEVELOPMENT CLASSIFICATION OF EXISTING SURFACES OF
 WALLS, PARTITIONS, COLUMNS, AND CEILINGS SHALL BE
 PERMITTED TO BE SECURED BY APPLYING APPROVED
 FIRE-RETARDANT COATINGS TO SURFACES HAVING HIGHER FLAME
 SPREAD RATINGS THAN PERMITTED. SUCH TREATMENTS SHALL BE
 TESTED, OR SHALL BE LISTED AND LABELED FOR APPLICATION
 TO THE MATERIAL TO WHICH THEY ARE APPLIED, AND SHALL
 COMPLY WITH THE REQUIREMENTS OF NFPA 703, STANDARD FOR
 FIRE RETARDANT?TREATED WOOD AND FIRE-RETARDANT COATINGS
 FOR BUILDING MATERIALS. [101:10.2.6.1]
 12.5.7.2 IN NEW CONSTRUCTION, SURFACES OF WALLS,
 PARTITIONS, COLUMNS, AND CEILINGS SHALL BE PERMITTED TO
 BE FINISHED WITH FACTORY-APPLIED FIRE-RETARDANT COATED
 ASSEMBLIES THAT HAVE BEEN LISTED AND LABELED TO
 DEMONSTRATE COMPLIANCE WITH THE FOLLOWING:
 (A) A FLAME SPREAD INDEX OF 25 OR LESS, WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84, STANDARD TEST METHOD OF
 SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS,
 OR ANSI/UL 723, STANDARD FOR TEST FOR SURFACE BURNING
 CHARACTERISTICS OF BUILDING MATERIALS,
 (B) SHOW NO EVIDENCE OF SIGNIFICANT PROGRESSIVE
 COMBUSTION WHEN THE TEST IS CONTINUED FOR AN ADDITIONAL
 20-MINUTE PERIOD, AND
 (C) RESULT IN A FLAME FRONT THAT DOES NOT PROGRESS MORE
 THAN 10 FT 6 IN. (3.2 M) BEYOND THE CENTERLINE OF THE
 BURNERS AT ANY TIME DURING THE TEST.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-18 Cont ID  
Sent By tklarge Date 2016-10-18 Time 05:41 Rev Time 0.00
Received By tklarge Date 2016-09-22 Time 13:02 Sent To  
Notes
2016-10-17 08:43:2110/17 TO TL DESK
  
2016-09-22 13:02:38RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-22 Cont ID  
Sent By lmarchan Date 2016-09-22 Time 13:01 Rev Time 0.00
Received By lmarchan Date 2016-07-22 Time 11:47 Sent To  
Notes
2016-07-26 09:00:097/26 TO PLUMBING BOX
  
  
2016-07-22 11:47:39SHILL'S DESK

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-18 Cont ID  
Sent By tklarge Date 2016-10-18 Time 05:41 Rev Time 0.00
Received By tklarge Date 2016-10-18 Time 05:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By tklarge Date 2016-07-28 Time 05:39 Rev Time 0.00
Received By tklarge Date 2016-07-28 Time 05:24 Sent To  
Notes
2016-07-28 05:38:461) SUBMIT A LEGIBLE PLAN FOR REVIEW. THE PLAN SHALL
 CLEARLY SHOW THE LOCATION AND SIZE OF THE ROOF DRAINS
 TO BE REPLACED AND SHOW THE SQUARE FOOT AREA THAT IS
 DRAINING INTO EACH ROOF DRAIN. THE SIZING OF THE ROOF
 DRAINS AND THE DRAIN PIPING SHALL COMPLY WITH 2014 FBC
 - PLUMBING SECS. 1106.2 & 1106.3. SIZING SHALL BE BASED
 ON A RAINFALL RATE OF 5 INCHES PER HOUR.
 2) PROVIDE A STORM DRAINAGE RISER THAT REFLECTS THE
 SCOPE OF WORK TO BE DONE.
  
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6692 OR [email protected]
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2016-10-17 Cont ID  
Sent By shill Date 2016-10-17 Time 08:41 Rev Time 0.00
Received By shill Date 2016-10-17 Time 08:41 Sent To  
Notes
2016-10-17 08:43:01A ROOF SUB PERMIT IS REQUIRED
 AN INCOMPLETE PRODUCT APPROVAL FOR FLAT ROOF WAS
 SUBMITTED.
 THE COMPLETE ROOF PRODUCT APPROVAL AND ENGINEERING ARE
 TO BE SUBMITTED WITH THE ROOF PERMIT APPLICATION
 (REVISION FEES APPLICABLE) PRIOR TO INSTALLATION.
  