Plan Review Stops For Permit 16070876 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2016-11-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-11-08 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-11-08 |
Time |
15:45 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-09-14 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-09-14 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-09-14 |
Time |
10:34 |
Sent To |
M |
|
Notes |
2016-09-14 13:10:24 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | | | 1. ROOFING PERMIT REQUIRED. | | 2. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | 3. PROVIDE SOILS REPORT. | | 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND | | DOOR SUBMITTALS. | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | R401.4 SOIL TESTS. | | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL | | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, | | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE | | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL | | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE | | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. | | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN | | APPROVED METHOD. | | | | | | | | | | | | | | | | | 2016-08-10 08:57:12 | 8/10/16 RETURNED TO R29, NO REVIEW PERFORMED. CST |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-10-27 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-10-27 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-10-27 |
Time |
14:29 |
Sent To |
|
|
Notes |
2016-10-27 16:07:11 | WITH THE EXCEPTION OF A COUPLE OF COMMENTS MADE ON THE | | RISER DIAGRAM, ALL PREVIOUSLY MENTIONED DEFICIENCIES | | HAVE BEEN SATISFACTORILY ADDRESSED. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-08-03 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-08-03 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-08-02 |
Time |
18:21 |
Sent To |
|
|
Notes |
2016-08-03 10:20:51 | ELECTRICAL REVIEW NOTES | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | PROJECT NAME: 2836 FLAGLER | | JOB ADDRESS: 2836 FLAGLER | | DESCRIPTION: SFR ADDITION | | MASTER PERMIT:16070876 | | | | | | 1. PLEASE LABEL ALL SPACES ON THE ELECTRICAL FLOOR PLAN | | TO DETERMINE PROPER ELECTRICAL REQUIREMENTS. | | 2. NEC 210.52(H): HALLWAYS GREATER THAN 10? SHALL HAVE | | AT LEAST 1 RECEPTACLE. | | 3. NEC 210.52(A)(2): OUTLETS ARE MISSING IN THE GREAT | | ROOM. IF THERE IS NOT ENOUGH WALL SPACE TO MOUNT AN | | ELECTRICAL OUTLET, YOU SHALL INSTALL FLOOR BOXES TO | | MEET THE MINIMUM SPACING REQUIREMENTS. | | 4. NEC 210.70(A)(2)(B): A LIGHT CONTROLLED BY A WALL | | SWITCH IS REQUIRED ON THE EXTERIOR DOORS AT THE CABANA | | AND REAR STORAGE. | | 5. NEC 230.208: INDICATE THE SIZING OF THE PROTECTION | | DEVICE FOR THE SERVICE AT THE MDP ON THE RISER DIAGRAM. | | 6. NEC 408.36: INDICATE IF PANEL ?A? IS MCB OR MLO ON | | THE RISER DIAGRAM. IF MCB INDICATE THE SIZE. | | 7. NEC 250.94: YOU SHALL INCLUDE THE REQUIRED | | INTER-SYSTEM BONDING TERMINAL AT THE NEW SERVICE | | LOCATION AND SO REFLECTED ON THE RISER DIAGRAM. | | 8. NEC 210.63: THOUGHT THERE IS NO ELECTRICAL SHEET | | INDICATING THE LOCATION OF THE CONDENSING UNITS MOUNTED | | ON THE ROOF, I DETERMINED FROM SHEET ?A4? THAT THERE | | MAY BE MORE THAN THE REQUIRED 25? FROM THE SERVICE | | OUTLET FOR ONE OR TWO OF THE UNITS. MAKE MENTION OF | | THIS REQUIREMENT ON THE RESPECTIVE PAGE TO AVOID | | MISSING THE REQUIREMENT. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2016-10-20 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-10-20 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-10-20 |
Time |
14:10 |
Sent To |
|
|
Notes |
2016-10-20 14:12:41 | GAS PLAN REVIEW | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION. | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-11-09 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-11-09 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-09-22 |
Time |
10:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-09-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-09-15 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2016-07-22 |
Time |
11:18 |
Sent To |
|
|
Notes |
2016-07-26 08:07:30 | R29 | 2016-07-22 11:18:18 | LIBRARY |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2016-11-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-11-15 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-11-09 |
Time |
12:20 |
Sent To |
|
|
Notes |
2016-11-15 14:53:39 | MU 2016 - 28009. NO FEES WERE DUE. | 2016-11-09 12:21:18 | CAROL CHECKED OUT ONE SET TO TAKE FOR IMPACT FEE | | REVIEW. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2016-11-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-11-08 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-11-08 |
Time |
15:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-09-14 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-09-14 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-09-14 |
Time |
11:28 |
Sent To |
|
|
Notes |
2016-09-14 13:31:52 | | | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | | | 1. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2016-11-09 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-11-09 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-11-09 |
Time |
12:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-11-08 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-11-08 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-11-08 |
Time |
16:30 |
Sent To |
|
|
Notes |
2016-11-08 17:17:07 | PROVO: | | PLANS SHOW 1025 CFM OFSUPPLY AIR FROM SUPPLY OUTLETS. | | AS PER TRANE WEBSITE AHU SPECIFIED ON PLANS PROVIDES | | 1698 CFM ON MEDIUM SPEED. REVISE PLANS SHOWING PROPER | | AIR DISTRIBUTION AT FINAL INSPECTION. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-09-14 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-09-14 |
Time |
17:18 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-09-14 |
Time |
16:41 |
Sent To |
|
|
Notes |
2016-09-14 17:18:37 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENT | | | | (1) IDENTIFY ALL AREAS, ROOMS ON THE MECHANICAL PLANS. | | (2) AIR HANDLER UNIT MODEL #TEM4A0C48S41SA IS 48000 | | BTU. MAKE CORRECTION ON PLANS | | (3) PROVIDE KITCHEN EXHAUST DUCT DETAIL ON PLANS. SHOW | | TERMINATION TO EXTERIOR OF HOME. | | (4) PROVIDE ANCHORING DETAIL FOR CONDENSER STAND TO | | ROOF AND CONDENSER TO CONDENSER STAND. MUST MEET FBC | | 2014 WIND LOAD REQUIREMENTS. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (5) FORMS R405 - 2014 MUST BE SIGNED BY OWNER/AGENT. | | (6) PROVIDE TWO SETS OF HEATLOAD CALCULATIONS FOR THE | | NEW ADDITION AREA. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-10-20 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-10-20 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-10-20 |
Time |
14:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-08-23 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-08-23 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-08-23 |
Time |
13:52 |
Sent To |
|
|
Notes |
2016-08-23 14:13:24 | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | | | PLUMBING COMMENTS: 1ST REVIEW | | | | 1. SHT A-7 SANITARY RISER SIZE BRANCH TO LAUNDRY . PER | | WPB AMEND TO FBC 107.2.1 | | | | 2. THE STACK, P- TRAP-AND STAND PIPE FOR WASHING | | MACHINE SHALL BE MIN OF 2IN. PER FBC RES. TABLE P3201.7 | | | | 3. AT LEAST ONE OF THE VENTS SHALL EXTEND THROUGH ROOF | | . PER FBC RES. | | P3102.1 REQUIRED VENT EXTENSION. | | THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE | | AT LEAST ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. | | | | 4. PROVIDE CLEAN OUT OUT SIDE BUILDING PER FBC RES. | | P3005.2.7 BUILDING DRAIN AND BUILDING SEWER JUNCTION. | | THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE | | BUILDING DRAIN AND BUILDING SEWER. THIS CLEANOUT SHALL | | BE EITHER INSIDE OR OUTSIDE THE BUILDING WALL, PROVIDED | | THAT IT IS BROUGHT UP TO FINISH GRADE OR TO THE LOWEST | | FLOOR LEVEL. AN APPROVED TWO-WAY CLEANOUT SHALL BE | | PERMITTED TO SERVE AS THE REQUIRED CLEANOUT FOR BOTH | | THE BUILDING DRAIN AND THE BUILDING SEWER. THE CLEANOUT | | AT THE JUNCTION OF THE BUILDING DRAIN AND BUILDING | | SEWER SHALL NOT BE REQUIRED WHERE A CLEANOUT ON A | | 3-INCH (76 MM) OR LARGER DIAMETER SOIL STACK IS LOCATED | | WITHIN A DEVELOPED LENGTH OF 10 FEET (3048 MM) OF THE | | BUILDING DRAIN AND BUILDING SEWER JUNCTION. | | | | 5. SHOW LOCATION OF RELOCATED TANKLESS WATER HEATER ON | | ELEVATION DRAWING AND FLOOR PLAN TO SHOW COMPLIANCE | | WITH CLEARANCE TO OPENINGS IN MANUFACTURE INSTALLATION | | GUIDE. PER WPB AMEND.TO FBC 107.2.1 | | | | | | |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
P |
Date |
2022-08-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2022-08-02 |
Time |
|
Rev Time |
0.00 |
Received By |
shill |
Date |
2022-08-02 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2016-11-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-11-09 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-11-09 |
Time |
12:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2016-09-14 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-09-14 |
Time |
13:31 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-09-14 |
Time |
11:28 |
Sent To |
|
|
Notes |
2016-09-14 13:34:12 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER ? PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | | | 1. ROOFING PERMIT REQUIRED. | | 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM | | COMPONENTS. | | 3. PROVIDE DESIGN WIND LOADS FOR NEW ROOF. | | 4. PROVIDE ROOF SHEATHING FASTENER SCHEDULE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2016-11-15 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2016-11-15 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2016-11-15 |
Time |
15:32 |
Sent To |
I |
|
Notes |
2016-11-15 15:34:06 | 11/15/16- PASSED | | | | ADDITION AREA HAS A GRILLE ONLY CANNOT NO SECOND | | KITCHEN. | | | | PLEASE CONTACT | | NATHAN WIRA | | [email protected] | | (561)822-1442 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2016-10-20 |
|
|
Cont ID |
|
Sent By |
njwira |
Date |
2016-10-20 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2016-10-20 |
Time |
15:38 |
Sent To |
|
|
Notes |
2016-10-20 16:09:21 | 10/20/2016- FAILED | | | | 1. YOU HAVE TWO KITCHEN'S MAKING THIS TWO UNITS IN A | | SF-7 DISTRICT IS NOT PERMITTED | | | | PASSED | | | | 1. TREE ALTERATION PERMIT FILED. | | | | PLEASE CONTACT | | NATHAN WIRA | | [email protected] | | (561)822-1442 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2016-07-28 |
|
|
Cont ID |
|
Sent By |
nwair |
Date |
2016-07-28 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
njwira |
Date |
2016-07-27 |
Time |
15:13 |
Sent To |
E |
|
Notes |
2016-07-28 13:40:07 | 7/28/16- FAILED | | | | ZONE SF-7 | | | | | | 1. TREE ALTERATION PERMIT REQUIRED TO REMOVE TREES. | | 2. ONLY ONE UNIT ALLOWED ON THE PROPERTY TWO KITCHENS | | MEANS THERE ARE TWO UNITS. | | | | PASSED | | 1. BUILDING HEIGHT IS 16FT. ALLOWED 30FT. | | 2. SIDE SETBACK IS 5FT. MINIMUM AND 15FT. TOTAL MEETING | | THE SIDE SETBACK REQUIREMENT. | | 3. FRONT SETBACK IS 50FT. MEETING THE 25FT. FRONT | | SETBACK. | | 4. REAR SETBACK IS 45FT MEETING THE 15FT. REAR SETBACK | | REQUIREMENT. | | | | PLEASE CONTACT: | | NATHAN WIRA | | (561)822-1442 | | [email protected] | | |
|
|