Plan Review Details - Permit 16070837
Plan Review Stops For Permit 16070837
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-08 Cont ID  
Sent By jwitmer Date 2016-11-08 Time 15:11 Rev Time 0.00
Received By jwitmer Date 2016-11-08 Time   Sent To  
Notes
2016-11-08 15:11:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070837
 ADD: 309/317 N. ROSEMARY AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-456-7252
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. NOV. 08/2016
 ACTION: DENIED
  
 1) 2ND REQUEST. THE PERMIT APPLICATION HAS 2 DIFFERENT
 ADDRESSES LISTED FOR THE SITE, A SITE CAN ONLY HAVE ONE
 LEGAL ADDRESS. THE 2ND ISSUE OF UNITY OF TITLE,
 RESPONSE INDICATES SEE ATTACHED UNITY OF TITLE, NOT
 ATTACHED TO THE BUILDING RESPONSE DOCUMENT. NOTE A
 WARRANTY DEED WAS SUBMITTED FOR 3 LOTS!!!
  
 1ST REVIEW COMMENTS. PLEASE NOTE AN ADDRESSING PLAN
 REVIEW STOP WILL BE ADDED TO THE PLAN REVIEW CYCLE TO
 ASSIGN A SITE ADDRESS. IT APPEARS ON THE PALM BCH.
 COUNTY PROPERTY APPRAISERS WEBSITE THERE ARE 3 ACTUAL
 PROPERTIES THAT WILL BE MAKING UP THIS SITE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT. PLEASE CONTACT MR. ORIO FOR AN SITE ADDRESS.
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040.
 E-MAIL: [email protected]
  
 2) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/2014, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000
 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 3) 2ND REQUEST, THIS MAY HAVE TO WAIT UNTIL A
 CONTRACTOR SIGNS ON AND THE PERMIT VALUES TO BE
 SUBTRACTED WOULD BE ON THE CONTRACTORS LETTER HEAD.
 1ST ROUND OF COMMENTS. THIS MAIN BUILDING PERMIT WILL
 INCLUDE THE FEES FOR THE MECHANICAL, ELECTRICAL,
 PLUMBING & ROOFING PERMITS. WHEN THE GENERAL CONTRACTOR
 COMES IN FOR A BUILDING PERMIT WITH THE SIGNED PERMIT
 APPLICATION FORM BY THE QUALIFIER AND OWNER AND BRINGS
 IN THE LISTED SUB-PERMITS M-E-P & ROOFING PERMITS
 SIGNED BY THE QUALIFIER OF EACH COMPANY, THEIR
 INSURANCES AND LICENSURE UP TO DATE, THE M-E-P AND
 ROOFING PERMITS ARE FREE OF CHARGE. IF THE M-E-P &
 ROOFING PERMITS COME IN LATER THERE WILL BE AN $80.00
 ADMINISTRATIVE FEE FOR EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE ,
 IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR
 STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND
 ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR
 VALUE FROM THE OVERALL BUILDING VALUE OF $4,088000.00.
 THE REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF
 THE BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DOES NOT WANT TO COLLECT TWICE FOR THE VALUE
 OF THESE SUB-PERMITS NOT COVERED UNDER THE PRIME OR
 MASTER PERMIT.
  
 4)THIS BUILDING IS A THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 4A) 2ND REQUEST. RESPONSE DOCUMENT INDICATED 3 SETS OF
 THE THRESHOLD INSPECTION PLAN WERE SUBMITTED, ONLY IN
 REVIEWING THE DOCUMENTS ONLY 2 SETS OF DOCUMENTS WERE
 SUBMITTED.
 1ST ROUND OF COMMENTS. 109.3.6.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/
 TYPED) SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 4B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 FORMS E-MAILED TO: [email protected] DATE:
 11/08/2016 9:08 AM
  
  
 4C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 4E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 4G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 4H) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4I) PROVISO: 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 5) 2ND REQUEST. PERIMETER FENCING UNDER A SEPARATE
 PERMIT. PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B
 3306.5 BARRIERS. BARRIERS SHALL BE A MINIMUM OF 8 FEET
 (2438 MM) IN HEIGHT AND SHALL BE PLACED ON THE SIDE OF
 THE WALKWAY NEAREST THE CONSTRUCTION. BARRIERS SHALL
 EXTEND THE ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 6) 2ND REQUEST. 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY
 SHALL BE PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF
 EVERY CONSTRUCTION AND DEMOLITION SITE UNLESS THE
 APPLICABLE GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK
 TO BE FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT
 WIDTH TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO
 CASE SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE
 WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED?
  
 7) 2ND REQUEST. 2014 FBC-B 3306.7 COVERED WALKWAYS.
 COVERED WALKWAYS SHALL HAVE A CLEAR HEIGHT OF NOT LESS
 THAN 8 FEET (2438 MM) AS MEASURED FROM THE FLOOR
 SURFACE TO THE CANOPY OVERHEAD. ADEQUATE LIGHTING SHALL
 BE PROVIDED AT ALL TIMES. COVERED WALKWAYS SHALL BE
 DESIGNED TO SUPPORT ALL IMPOSED LOADS. IN NO CASE SHALL
 THE DESIGN LIVE LOAD BE LESS THAN 150 PSF FOR THE
 ENTIRE STRUCTURE.
  
 8) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH:
 POLLUTION PREVENTION PLAN. 2014 FBC-B 3307.1 PROTECTION
 REQUIRED. ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL
 BE PROTECTED FROM DAMAGE DURING CONSTRUCTION,
 REMODELING AND DEMOLITION WORK. PROVISIONS SHALL BE
 MADE TO CONTROL WATER RUNOFF AND EROSION DURING
 CONSTRUCTION OR DEMOLITION ACTIVITIES. THE PERSON
 MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL
 PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING
 BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE
 MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE
 PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT
 LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE
 OF THE EXCAVATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 9) 2ND REQUEST. PLEASE PROVIDE DETAILS SHOWING HOW
 COMPLIANCE WITH 2014 FBC-B 3306.9 ADJACENT TO
 EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) IN HEIGHT. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHERE REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16. SHEET A2.01A & S-1 SHOW PILING RIGHT
 ADJACENT TO THE PROPERTY LINE SEE COLUMN 1 AND ROW A .
  
 10A) 2ND REQUEST. PLEASE PROVIDE DETAILS SHOWING
 COMPLIANCE WITH 2014 FBC-B 3307.1 PROTECTION REQUIRED.
 ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL BE
 PROTECTED FROM DAMAGE DURING CONSTRUCTION AND
 DEMOLITION WORK. PROTECTION SHALL BE PROVIDED FOR
 FOOTINGS, FOUNDATIONS, PARTY WALLS, CHIMNEYS, SKYLIGHTS
 AND ROOFS. WITH THE EXCAVATION AND AUGER CAST PILE HOW
 WILL THE BUILDING TO THE SOUTH BE PROTECTED FROM
 SETTLEMENT?
 SHEET A2.01A & S-1 SHOW PILING RIGHT ADJACENT TO THE
 PROPERTY LINE SEE COLUMN 1 AND ROW A .
  
 10B) 2ND REQUEST. 2014 FBC-B 3307.1 THE PERSON MAKING
 OR CAUSING AN EXCAVATION TO BE MADE SHALL PROVIDE
 WRITTEN NOTICE TO THE OWNERS OF ADJOINING BUILDINGS
 ADVISING THEM THAT THE EXCAVATION IS TO BE MADE AND
 THAT THE ADJOINING BUILDINGS SHOULD BE PROTECTED. SAID
 NOTIFICATION SHALL BE DELIVERED NOT LESS THAN 10 DAYS
 PRIOR TO THE SCHEDULED STARTING DATE OF THE EXCAVATION.
 SHEET A2.01A & S-1 SHOW PILING RIGHT ADJACENT TO THE
 PROPERTY LINE SEE COLUMN 1 AND ROW A .
  
 11) 2ND REQUEST. WHEN EXCAVATING WILL THE EXCESS SOILS
 BE STORED ON SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO
 FILL OR OTHER SURCHARGE LOADS SHALL BE PLACED ADJACENT
 TO ANY BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR
 STRUCTURE IS CAPABLE OF WITHSTANDING THE ADDITIONAL
 LOADS CAUSED BY THE FILL OR SURCHARGE. EXISTING
 FOOTINGS OR FOUNDATIONS WHICH CAN BE AFFECTED BY ANY
 EXCAVATION SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE
 PROTECTED AGAINST SETTLEMENT AND SHALL BE PROTECTED
 AGAINST LATER MOVEMENT.
  
 12) 2ND REQUEST. PLEASE DOCUMENT COMPLIANCE WITH: 2014
 FBC-B 3313.1 WHERE REQUIRED. AN APPROVED WATER SUPPLY
 FOR FIRE PROTECTION, EITHER TEMPORARY OR PERMANENT,
 SHALL BE MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL
 ARRIVES ON THE SITE. PLEASE PROVIDE WHERE THIS
 CONNECTION WILL BE MADE.
  
 13) 2ND REQUEST. NOTICE: 2014 FBC-B [F] 3311.1 WHERE
 REQUIRED. IN BUILDINGS REQUIRED TO HAVE STANDPIPES BY
 SECTION 905.3.1, NOT LESS THAN ONE STANDPIPE SHALL BE
 PROVIDED FOR USE DURING CONSTRUCTION. SUCH STANDPIPES
 SHALL BE INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS
 NOT MORE THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE
 LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH
 STANDPIPE SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE
 CONNECTIONS AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE
 STAIRS. SUCH STANDPIPES SHALL BE EXTENDED AS
 CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR OF THE
 HIGHEST POINT OF CONSTRUCTION HAVING SECURED DECKING OR
 FLOORING.
  
 14A) 2ND REQUEST. 2014 FBC-B [F] 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED
 WITH NOT LESS THAN ONE APPROVED PORTABLE FIRE
 EXTINGUISHER IN ACCORDANCE WITH SECTION 906 AND SIZED
 FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 14B) 2ND REQUEST. 2014 FBC-B 3309.2 FIRE HAZARDS. THE
 PROVISIONS OF THIS CODE AND THE FLORIDA FIRE PREVENTION
 CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD AGAINST
 ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION
 OPERATIONS.
  
 15) 2ND REQUEST. 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 109.3.10.1 HURRICANE
 PROTECTION. IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS EQUIPMENT AND
 DEBRIS TO REMAIN LOOSE OR OTHERWISE UNSECURED AT A
 CONSTRUCTION SITE FROM 24 HRS. AFTER A HURRICANE WATCH
 HAS BEEN ISSUED UNTIL THE HURRICANE WATCH OR WARNING
 HAS BEEN LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO
 COMPLY TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A
 LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE
 SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS
 CHAPTER.
  
 16) SHEET L.S.101:
 16A) 2ND REQUEST. FIRE/ SMOKE DETECTION SYSTEM.
 RESPONSE INDICATES THE USE OF A NFPA 13 FIRE SPRINKLER
 SYSTEM. PLEASE REVIEW THE 2014 FBC-B 907.2.8.
 1ST ROUND COMMENTS. FIRE PROTECTION GENERAL NOTES # 1
 GC TO INSTALL FIRE/ SMOKE DETECTION SYSTEM AS
 APPLICABLE CODES FOR USE AND OCCUPANCY. PLEASES BE
 SPECIFIC TO THE 2014 FBC-B.
  
 16-17) COMPLIED.
  
 18) SHEET A2.01A. GROUND FLOOR;
 18A) COMPLIED.
  
 18B) SEMI-COMPLIED. THE PLAN STILL SHOW THIS WALL AS A
 4 INCH AND 6 INCH WALL, REMOVE THE 4 INCH DIMENSION.
 PLEASE SHOW THE MASONRY WALLS 4 INCH / 2 HR. RATED WITH
 THE CENTER CAVITY. THE DESIGN # 906 IS FOR 6INCH BLOCK
 EITHER HOLLOW OR SOLID BUT NOT FOR A 4 INCH BLOCK WALL.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. FBC-B TABLE
 722.3.2 MINIMUM EQUIVALENT THICKNESS (INCHES) OF
 BEARING OR NONBEARING CONCRETE MASONRY WALLS.
  
 18C) 2ND REQUEST, THE PERIMETER OF THE PARKING GARAGE
 IS 49+49+60+60=218 L.F. X 15 FT(H)= 3270 SQ. FT.
 OPENINGS, 60+18= 78(W) X 15(H)= 1170 SQ. FT. THIS IS
 ONLY 35.7 % OPEN. WILL REQUIRE MECHANICAL VENTILATION.
 THE ALLOWABLE 40 % OPENINGS ARE FOR UNIFORMLY
 DISTRIBUTED OPENINGS ON NO LESS THAN 2 WALLS FOR
 ADEQUATE VENTILATION. THESE OPENINGS ARE NOT UNIFORMLY
 DISTRIBUTED ON OPPOSITE WALLS THAT WOULD CREATE AIRFLOW
 NOR THE REQUIRED 40 %.
  
 1ST ROUND OF COMMENTS. THE L. S. SHEET NOR THE GROUND
 FLOOR SHOW THE PARKING GARAGE AS DESIGNED OPEN OR
 ENCLOSED. THE PLANS DO NOT APPEAR TO MAKE THE
 REQUIREMENTS FOR AN OPEN PARKING GARAGE UNDER SECTION
 FBC-B 406.5.2 AND WILL NEED TO MEET THE REQUIREMENTS
 FOR 406.6.2 VENTILATION AND 406.6.3 AUTOMATIC SPRINKLER
 SYSTEM.
 THE M1.1 SHEET ALSO DOES NOT SHOW ANY MECHANICAL
 EQUIPMENT FOR MECHANICAL EQUIPMENT. THERE SEAMS TO BE A
 OPENING MISSING IN THE GARAGE CEILING (HIDDEN DASHED
 LINE) ON THE GRID LINE C/ 5 THAT GOES VERTICALLY
 THROUGH TO THE ROOF. IF THE DESIGNERS INTENT IS O TAKE
 CREDIT FOR THE 3 VERTICAL OPENS IN THE CEILING AS WELL
 AS THE ONE ON GRID LINE C/5 AS EQUAL TO CROSS
 VENTILATION FOR AN OPEN PARKING GARAGE, THEN
 CALCULATIONS WILL BE NEEDED TO PROVIDE CODE COMPLIANCE
 UNDER SECTION 104.11 ALTERNATE MATERIALS, DESIGN AND
 METHODS OF CONSTRUCTION AND EQUIPMENT. A LETTER TO THE
 BUILDING OFFICIAL WOULD ALSO NEED TO FOLLOW ASKING THIS
 DESIGN TO BE REVIEWED UNDER 104.11 ALTERNATE MATERIALS,
 DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT.
  
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES.
  
 18D-K) COMPLIED.
  
 19) SHEET A2.02 THE SECOND FLOOR LEVEL:
  
 19A-B) COMPLIED.
  
 19C) PROVISO PROVIDE CHAIR LIFT SPECIFICATIONS. THE
 ACCESSIBLE SUITE DOES NOT INDICATE HOW COMPLIANCE WITH
 242.2 ACCESSIBLE SWIMMING POOLS ARE GOING TO BE
 ACHIEVED. SEE EXCEPTION 1 REQUIREMENT. WHERE A SWIMMING
 POOL HAS LESS THAN 300 LINEAR FEET OF SWIMMING POOL
 WALL, NO MORE THAN ONE ACCESSIBLE MEANS OF ENTRY SHALL
 BE REQUIRED PROVIDED THAT THE ACCESSIBLE MEANS OF ENTRY
 IS A SWIMMING POOL LIFT COMPLYING WITH 1009.2 OR SLOPED
 ENTRY COMPLYING WITH 1009.3.
  
 19D) THIS TO BE A DEFERRED SUBMITTAL 107. 3.4.2. THIS
 IS GOING TO BE A COMMENT FOR ALL UNITS NOT JUST THE
 ACCESSIBLE UNIT. THE PLANS SHOW SLIDING GLASS DOORS
 THAT LED FROM WITHIN THE SUITE OUT TO THE TERRACE DECK.
 THE COMPLETE OPENING BEING 14 FOOT 10 INCHES WIDE
 DIVIDE BY 3 EQUALS OR EACH PANEL 4 FT. 11 IINCHES
 APPROXIMATELY. THIS SIZE DOOR CAN BE USED IN A MEANS OF
 EGRESS WHEN THE OCCUPANT LOAD IS 10 OR LESS, 1008.1.2
 EXCEP. #9. THE DOOR IS 19/32 IN. LAMINATED GLASS.
 2014 FBC-B 1008.1.3 DOOR OPENING FORCE. THE FORCE FOR
 PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS,
 OTHER THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS (22
 N). FOR OTHER SWINGING DOORS, AS WELL AS SLIDING AND
 FOLDING DOORS, THE DOOR LATCH SHALL RELEASE WHEN
 SUBJECTED TO A 15-POUND (67 N) FORCE. THE DOOR SHALL BE
 SET IN MOTION WHEN SUBJECTED TO A 30-POUND (133 N)
 FORCE. THE DOOR SHALL SWING TO A FULL-OPEN POSITION
 WHEN SUBJECTED TO A 15-POUND (67 N) FORCE.
 FOR THE ACCESSIBLE UNIT THE OPENING FORCE FOR THE
 SLIDING GLASS DOOR WILL BE FBC-ACCESS. CODE 404.2.9
 DOOR AND GATE OPENING FORCE. FIRE DOORS SHALL HAVE A
 MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE
 ADMINISTRATIVE AUTHORITY. THE FORCE FOR PUSHING OR
 PULLING OPEN A DOOR OR GATE OTHER THAN FIRE DOORS SHALL
 BE AS FOLLOWS: 2. SLIDING OR FOLDING DOORS: 5 POUNDS
 (22.2 N) MAXIMUM.
  
 19E) THE DESIGN PROFESSIONAL WILL NEED TO SUBMIT THE
 LETTER FOR CONSIDERATION UNDER 104.1.1 ALTERNATE
 MATERIALS, DESIGN AND METHODS, ONCE APPROVED PROVIDE A
 COPY TO BE SCANNED INTO THE PERMIT RECORDS.
  
 THE OTHER ISSUE COMMON TO ALL UNITS WITH THE SLIDING
 DOOR TO THE POOL DECK IS: 404.2.7 DOOR AND GATE
 HARDWARE. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER
 OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH
 309.4. OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34
 INCHES (865 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. WHERE SLIDING DOORS
 ARE IN THE FULLY OPEN POSITION, OPERATING HARDWARE
 SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 EXCEPTIONS: 2. ACCESS GATES IN BARRIER WALLS AND FENCES
 PROTECTING POOLS, SPAS, AND HOT TUBS SHALL BE PERMITTED
 TO HAVE OPERABLE PARTS OF THE RELEASE OF LATCH ON
 SELF-LATCHING DEVICES AT 54 INCHES (1370 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PROVIDED THE
 SELF-LATCHING DEVICES ARE NOT ALSO SELF-LOCKING DEVICES
 AND OPERATED BY MEANS OF A KEY, ELECTRONIC OPENER, OR
 INTEGRAL COMBINATION LOCK.
  
 THE DOORS ARE TO BE SELF-CLOSING AND SELF-LATCHING.
 FBC-B 454.1.3.1.9 ACCESS THROUGH THE BARRIER OR FENCE
 FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS, MOTEL
 ROOMS AND HOTEL ROOMS, SHALL BE THROUGH SELF-CLOSING,
 SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM)
 MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH THE LATCH
 LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM THE
 BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM) BELOW
 THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND.
  
 19F) BUILDING PROVISO: PLEASE NOTE THE SLIDING GLASS
 DOOR, THE THRESHOLD INDICATES ONLY TO BE 1/2 INCH HIGH.
 404.2.5 THRESHOLDS. THRESHOLDS, IF PROVIDED AT
 DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH MAXIMUM.
 RAISED THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS
 SHALL COMPLY WITH ACCESS. CODE 302 AND 303. HOW WILL
 WATER INTRUSION BE HANDLED IN A HURRICANE?
  
 19G-H) COMPLIED
  
 20) THE ACCESSIBLE SUITE SHOWS A DETAIL # 1/ A7.2. THE
 ACCESSIBLE BATHROOM:
  
 20A-E)COMPLIED.
  
 20F)2ND REQUEST. RESPONSE INDICATES THE STEAM SHOWER
 REMOVED FROM THE UNIT LAYOUT. IT APPEARS THAT THE STEAM
 SHOWER HAS BEEN MOVED INTO THE ACCESSIBLE BATHROOM.
 THE STEAM SHOWER IN THE ACCESSIBLE GUEST UNIT WILL ALSO
 NEED TO SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE
 ;
 20F)(1) 612.2 BENCH. WHERE SEATING IS PROVIDED IN
 SAUNAS AND STEAM ROOMS, AT LEAST ONE BENCH SHALL COMPLY
 WITH 903. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED BY 903.2. EXCEPTION: A READILY REMOVABLE
 BENCH SHALL BE PERMITTED TO OBSTRUCT THE TURNING SPACE
 REQUIRED BY 612.3 AND THE CLEAR FLOOR OR GROUND SPACE
 REQUIRED BY 903.2.
  
 20F)(2) 612.3 TURNING SPACE. A TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN SAUNAS AND STEAM
 ROOMS.
  
 21) SHEET A2.07 THESE COMMENTS WILL BE COMMON TO ALL
 FLOORS 2-5;
  
 21A) 2ND REQUEST. RESPONSE INDICATES SEE SPECS FOR
 VERSA DECK SYSTEM, NOT SUBMITTED.
 1ST ROUND COMMENTS. NOTE # 14 INDICATES THE USE OF TREX
 DECK TERRACE AND CEILING. THERE IS NO PRODUCT
 INFORMATION FOR THE TREX DECK SYSTEM. PLEASE PROVIDE
 THE MANUFACTURERS SPECIFICATION, IF THIS IS A
 COMBUSTIBLE PRODUCT AND IF SO THE FLAME SPREAD AND TO
 WHAT STANDARD THE PRODUCT WAS TESTED TOO? SEE FBC-B
 SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION. 603.1 ALLOWABLE MATERIALS.
  
 21B) 2ND REQUEST. RESPONSE INDICATES SEE SPECS FOR
 VERSA DECK SYSTEM, NOT SUBMITTED.
 1ST ROUND OF COMMENTS. THERE ARE NO PLANS FOR THE TREX
 DECK DROP CEILING ASSEMBLY. TYPE OF FRAMING, MATERIAL,
 SPACING, SIZE OF FRAMING MEMBERS, ANCHORAGE TO THE DECK
 ABOVE IF STIFF BACKS ARE REQUIRED. 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL
 BUILDINGS: DROPPED EXTERIOR CEILING ASSEMBLIES.
  
 21C) 2ND REQUEST SHEET A2.07 SHOWS OVER THE BATHROOMS A
 MECHANICAL PLENUM. DETAILS 3 & 4 BOTH INDICATE THE USE
 OF INSULATION IN BOTH THE MECHANICAL PLENUM AS WELL AS
 THE DROPPED CEILING WITHIN THE TYPICAL SUITE. THE PLANS
 DOES NOT DECLARE WHAT TYPE OF INSULATION IS GOING TO BE
 INSTALLED? IS THIS INSULATION GOING TO BE FOR BOTH
 SOUND AND THERMAL VALUES? SEE FBC-B 720.1 & 720.2.
  
 21D) 2ND REQUEST, PLEASE PROVIDE CODE COMPLIANCE.
 DETAILS 3 & 4 WITHIN THE SUITE SHOW A DROPPED CEILING
 ASSEMBLY, FASTENED TO THE CONCRETE DECK ABOVE AS WELL
 AS A DROPPED CEILING ASSEMBLY WITH WHAT MAYBE A LIGHT
 TROUGH. THE INSULATION ABOVE WOULD STILL BE WITHIN THE
 ROOM PROPER. PLEASE PROVIDE ADDITIONAL DETAILS AS TO
 THE TYPE OF FRAMING MATERIALS, ANCHORAGE TO THE DECK
 ABOVE, SIZE OF FRAMING MEMBERS, SPACING OF FRAMING
 MEMBERS THE TYPE OF INSULATION, THE THICKNESS AND TYPE
 OF FINISH MATERIAL FOR THE DROPPED CEILING. . 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 107.3.5.1
 COMMERCIAL BUILDINGS: DROPPED EXTERIOR CEILING
 ASSEMBLIES.
 FBC-B 720.3 EXPOSED INSTALLATION. INSULATING MATERIALS,
 WHERE EXPOSED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
 FBC-B 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND
 CEILINGS ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE
 USED.
  
 21E-F) COMPLIED.
  
 21G) BUILDING PROVISO: POOLS AND ASSOCIATED EQUIPMENT
 WILL BE UNDER SEPARATE PERMITS FOR EACH UNIT FOR THE
 RECORDING OF INSPECTIONS. 105.1. PERMITS REQUIRED.
  
 22) BUILDING PROVISO: SHEET A3.03 THE GREEN SCREEN
 SYSTEM PANELS CAN BE A SUBMITTAL THAT COULD QUALIFY AS
 A DEFERRED SUBMITTAL, PLEASE PROVIDE THE WIND DESIGN
 PARAMETERS FOR THE SPECIALTY ENGINEERS CAN DESIGN TO
 THE PROPER WIND SPEED. 107.3.4.2 DEFERRED SUBMITTALS.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 23) SHEET A2.05 ROOF PLAN.
  
 23A) COMPLIED.
 23B) 2ND REQUEST. STAIR TOWER 1 & 2 BOTH SHOW OVERFLOW
 SCUPPERS BUT NO SECONDARY (EMERGENCY OVERFLOW) DRAINS
 OR SCUPPERS. FBC-B 1503.4.1.
  
 23C) SEMI-COMPLIED. THE DETAIL SHOW AN OVERFLOW SCUPPER
 4 INCHES OF THE FINISH ROOF BUT NOT A SCUPPER WHICH
 SHOULD BE FLUSH WITH THE ROOF. PLEASE PROVIDE DETAILS
 FOR SCUPPERS AND OVERFLOW SCUPPERS, THE BOTTOM OF EACH
 UNIT IN RELATIONSHIP WITH THE ROOF. FBC-B 1503.4.2
 SCUPPERS. OVERFLOW SCUPPERS ARE SHOWN.
  
 23D-E) PROVISO: DEFERRED SUBMITTAL 107.3.4.2. ROOF TOP
 A/C STANDS. CONTRACTOR IS TO PROVIDE APPROVED SIGNED
 AND SEALED SHOP DRAWINGS FOR REVIEW AND APPROVAL BY THE
 ENGINEER OF RECORD.
  
  
 23F-G) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. ROOFTOP
 SKYLIGHTS. SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I
 AND II CONSTRUCTION. 603.1 ALLOWABLE MATERIALS. 15.
 LIGHT-TRANSMITTING PLASTICS AS PERMITTED BY CHAPTER 26.
 PLEASE PROVIDE COMPLIANCE WITH: 2609.4 AREA
 LIMITATIONS. ROOF PANELS SHALL BE LIMITED IN AREA AND
 THE AGGREGATE AREA OF PANELS SHALL BE LIMITED BY A
 PERCENTAGE OF THE FLOOR AREA OF THE ROOM OR SPACE
 SHELTERED IN ACCORDANCE WITH TABLE 2609.4. CC1 OR CC2?
  
 23H) NOT APPLICABLE/ NO ACTION NEEDED.
  
 24) COMPLIED. FBC-B 3002.4 ELEVATOR CAR TO ACCOMMODATE
 AMBULANCE STRETCHER
  
 25-28) COMPLIED.
  
 29) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. FOR THE
 PRODUCT APPROVALS WITH GLAZED OPENINGS AND MULLIONS ,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE THE
 SUBMITTED PRODUCT APPROVALS THERE ARE TO MANY VARIABLE,
 CIRCLE TO IDENTIFY EACH COMPONENT. COMPONENTS &
 CLADDING.
  
 30) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. THE NOA
 15-0731.06 MIAMI ROLLING DOOR SUBMITTED REPORT GOOD FOR
 +/- 65 SHEET S-18 SHOWS PRESSURES OF -87, VASD OR VULT
 NOT GIVEN ON THE SHEET. ALL PRODUCT APPROVALS ARE IN
 VASD. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 31) .(2) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. ROOFING
 APPROVALS WERE SUBMITTED FOR THIS REVIEW.
 CARLISLE MIRASEAL FLUID APPLIED WATERPROOFING MEMBRANE
 NOA 13-0129.22
 CARLISLE CCW-500-R HOT APPLIED LIQUID MEMBRANE NOA
 12-0801.01
 IN BOTH APPROVALS THERE ARE MULTIPLE SUB-SYSTEMS AND
 ASSOCIATED PRESSURES. IN NEITHER REPORT WAS A
 SUB-SYSTEM AND ASSOCIATED PRESSURES INDICATED. ALSO IN
 BOTH REPORTS LIMITATION # 9 IS INDICATED NO ENHANCED
 FASTENING CAN OCCUR. THE PLANS DO NOT INDICATE ROOF TOP
 PRESSURES FOR ZONES 1,2 & 3. PLEASE PROVIDE PRESSURES
 IN VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. 2014
 FBC- B 1603.1.4 WIND DESIGN DATA.
  
 32) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 33) SOILS REPORTS ONLY ONE SIGNED AND SEALED DOCUMENT
 WAS SUBMITTED, 3 REQUIRED. THRESHOLD BUILDING.
  
 34) PLEASE PROVIDE WHAT AGENCY WILL BE MONITORING OF
 THE TEST PILING AS WELL AS THE PRODUCTION PILE. NOTE
 THE TEST PILE IS UNDER SEPARATE PERMIT.
  
 35) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 36) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By jwitmer Date 2016-08-09 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2016-08-07 Time 05:58 Sent To  
Notes
2016-08-09 15:41:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070837
 ADD: 309/317 N. ROSEMARY AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-456-7252
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SUN. AUGUST 07/2016
 ACTION: DENIED
  
 1) PLEASE NOTE AN ADDRESSING PLAN REVIEW STOP WILL BE
 ADDED TO THE PLAN REVIEW CYCLE TO ASSIGN A SITE
 ADDRESS. IT APPEARS ON THE PALM BCH. COUNTY PROPERTY
 APPRAISERS WEBSITE THERE ARE 3 ACTUAL PROPERTIES THAT
 WILL BE MAKING UP THIS SITE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJECT. PLEASE CONTACT MR. ORIO FOR AN SITE ADDRESS.
 CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/
 INFORMATION TECHNOLOGY
 TEL: 561-494-1040.
 E-MAIL: [email protected]
  
 2) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/2014,
 AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO
 OR GREATER THAN $750,000
 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 3) THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR
 THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE ,
 IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR
 STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND
 ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR
 VALUE FROM THE OVERALL BUILDING VALUE OF $4,088000.00.
 THE REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF
 THE BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DOES NOT WANT TO COLLECT TWICE FOR THE VALUE
 OF THESE SUB-PERMITS NOT COVERED UNDER THE PRIME OR
 MASTER PERMIT.
  
 4)THIS BUILDING IS A THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 4A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 4G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 4H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 5) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE
 PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 6) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE
 PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY
 CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE
 GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE
 FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH
 TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE
 SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE
 WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED?
  
 7) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS
 SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438
 MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY
 OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL
 TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT
 ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE
 LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE.
  
 8) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION
 PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING
 PUBLIC AND PRIVATE PROPERTY SHALL BE PROTECTED FROM
 DAMAGE DURING CONSTRUCTION, REMODELING AND DEMOLITION
 WORK. PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF
 AND EROSION DURING CONSTRUCTION OR DEMOLITION
 ACTIVITIES. THE PERSON MAKING OR CAUSING AN EXCAVATION
 TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS
 OF ADJOINING BUILDINGS ADVISING THEM THAT THE
 EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 9) PLEASE PROVIDE DETAILS SHOWING HOW COMPLIANCE WITH
 2014 FBC-B 3306.9 ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) IN HEIGHT. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHERE REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16. SHEET A2.01A & S-1 SHOW PILING RIGHT
 ADJACENT TO THE PROPERTY LINE SEE COLUMN 1 AND ROW A .
  
 10A) PLEASE PROVIDE DETAILS SHOWING COMPLIANCE WITH
 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC
 AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE
 DURING CONSTRUCTION AND DEMOLITION WORK. PROTECTION
 SHALL BE PROVIDED FOR FOOTINGS, FOUNDATIONS, PARTY
 WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. WITH THE
 EXCAVATION AND AUGER CAST PILE HOW WILL THE BUILDING TO
 THE SOUTH BE PROTECTED FROM SETTLEMENT?
 SHEET A2.01A & S-1 SHOW PILING RIGHT ADJACENT TO THE
 PROPERTY LINE SEE COLUMN 1 AND ROW A .
  
 10B) 2014 FBC-B 3307.1 THE PERSON MAKING OR CAUSING AN
 EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO
 THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT
 THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION. SHEET A2.01A
 & S-1 SHOW PILING RIGHT ADJACENT TO THE PROPERTY LINE
 SEE COLUMN 1 AND ROW A .
  
 11) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON
 SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER
 SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 12) PLEASE DOCUMENT COMPLIANCE WITH: 2014 FBC-B 3313.1
 WHERE REQUIRED. AN APPROVED WATER SUPPLY FOR FIRE
 PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE
 MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES
 ON THE SITE. PLEASE PROVIDE WHERE THIS CONNECTION WILL
 BE MADE.
  
 13) NOTICE: 2014 FBC-B [F] 3311.1 WHERE REQUIRED. IN
 BUILDINGS REQUIRED TO HAVE STANDPIPES BY SECTION
 905.3.1, NOT LESS THAN ONE STANDPIPE SHALL BE PROVIDED
 FOR USE DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE
 INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE
 THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST
 LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE
 SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS
 AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
  
 14A) 2014 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 14B) 2014 FBC-B 3309.2 FIRE HAZARDS. THE PROVISIONS OF
 THIS CODE AND THE FLORIDA FIRE PREVENTION CODE SHALL BE
 STRICTLY OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS
 ATTENDANT UPON CONSTRUCTION OPERATIONS.
  
 15) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 16) SHEET L.S.101:
 16A) FIRE PROTECTION GENERAL NOTES # 1 GC TO INSTALL
 FIRE/ SMOKE DETECTION SYSTEM AS APPLICABLE CODES FOR
 USE AND OCCUPANCY. PLEASES BE SPECIFIC TO THE 2014
 FBC-B.
  
 16B) UNDER THE HEADING CONSTRUCTION TYPE/ OCCUPANCY THE
 BUILDING CONSTRUCTION TYPE IS LISTED AS A TYPE IIB/ R1
 OCCUPANCY TYPE. THE TYPE OF AUTOMATIC FIRE SPRINKLER
 SYSTEM IS NOT MENTIONED IN THE CONSTRUCTION TYPE NOR IN
 THE FIRE PROTECTION PLANS. PLEASE DESIGNATE WHAT TYPE
 OF FIRE SPRINKLER SYSTEM IS DESIGNED FOR THIS BUILDING.
 NOTE TABLE 503 ONLY ALLOWS 4 STORIES FOR A IIA/ R1
 OCCUPANCY. DECLARE THE TYPE OF FIRE SPRINKLERS AND AREA
 INCREASES TAKEN UNDER FBC-B 506.1 AND EQUATION 5-1 FOR
 AREA AND SPRINKLER INCREASES.
  
 16C) BUILDING OCCUPANCY CLASSIFICATION HEADING:
 16C)(1) PLEASE REVIEW BASEMENT RESIDENTIAL CATEGORY &
 OCCUPANCY COUNT. SEE FBC-B TABLE 1004.1.2 FUNCTION
 ACCESSORY STORAGE AREAS AND OCCUPANT LOAD FACTOR 300
 GROSS.
  
 16C)(2) PLEASE REVIEW THE GROUND FLOOR AND THE
 RESIDENTIAL CATEGORY R1. THE LOBBY AREA INCLUDING THE
 DELI AREA ARE ALL CONSIDERED A BUSINESS OCCUPANCY @ 100
 SQ. FT./ OCCUPANT. SEE FBC-B TABLE 1004.1.2. UPDATE
 PLANS.
  
 16 C)(3) PLEASE PROVIDE THE TOTAL SQ. FT. OF THE
 BUILDING AREA AND REVISED TOTAL OCCUPANT LOAD FOR THE
 BUILDING.
  
 16D) PLEASE UPDATE BOTH EGRESS REQUIREMENTS AND FIXTURE
 COUNT SINCE THE OCCUPANCY LOADS WILL BE INCREASED.
 FBC-B TABLE 1004.1.2.
  
 16E) THE PLANS INDICATE THIS IS A R1 OCCUPANCY BUT
 PLEASE CONFIRM THAT THE UNITS THEMSELVES ARE TO BE
 CONSIDERED EITHER SLEEPING UNITS OR DWELLING UNITS. THE
 PLANS ARE VAGUE AS TO IF THERE IS TO BE A KITCHEN OR
 KITCHENETTE. IF THE SUITES ARE TO BE CONSIDERED A
 DWELLING UNIT THEN COMPLIANCE WITH THE FOLLOWING 3 CODE
 SECTIONS WOULD BE REQUIRED FOR BUILDING TYPE IIA/ R1-
 IF (DWELLING UNIT).
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 8 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 16E)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16E)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 16E)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 16F) PLEASE REVIEW THE TRAVEL DISTANCE FROM THE
 FURTHEST POINT IN THE LAUNDRY. THIS POINT IS TO BE
 TAKEN FROM THE FURTHEST POINT IN THE LAUNDRY ROOM AND
 THEN THE TRAVEL ROUTE TO BE TAKEN 1 FOOT FROM THE WALL
 LINE FURNITURE OR EQUIPMENT TO THE EXIT DOOR WAY.
 COMMON PATH OF TRAVEL, FBC-B TABLE 1014.3. STORAGE
 OCCUPANCY < 30 OCCUPANCY ALLOWS FOR 100 FT. TRAVEL
 DISTANCE/ SPRINKLERED BUILDING.
  
 16F) THE LIFE SAFETY SHEET IS SILENT AS TO THE FIRE
 RATING REQUIREMENTS FOUND IN FBC-B TABLE 601 & 602.
  
 704.2 COLUMN PROTECTION. WHERE COLUMNS ARE REQUIRED TO
 HAVE PROTECTION TO BE FIRE-RESISTANCE RATED, THE ENTIRE
 COLUMN SHALL BE PROVIDED INDIVIDUAL ENCASEMENT
 PROTECTION BY PROTECTING IT ON ALL SIDES FOR THE FULL
 COLUMN LENGTH, INCLUDING CONNECTIONS TO OTHER
 STRUCTURAL MEMBERS, WITH MATERIALS HAVING THE REQUIRED
 FIRE-RESISTANCE RATING. WHERE THE COLUMN EXTENDS
 THROUGH A CEILING, THE ENCASEMENT PROTECTION SHALL BE
 CONTINUOUS FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW THROUGH THE CEILING SPACE
 TO THE TOP OF THE COLUMN.
  
 704.3 PROTECTION OF THE PRIMARY STRUCTURAL FRAME OTHER
 THAN COLUMNS. MEMBERS OF THE PRIMARY STRUCTURAL FRAME
 OTHER THAN COLUMNS THAT ARE REQUIRED TO HAVE PROTECTION
 TO ACHIEVE A FIRE-RESISTANCE RATING AND SUPPORT MORE
 THAN TWO FLOORS OR ONE FLOOR AND ROOF, OR SUPPORT A
 LOAD-BEARING WALL OR A NONLOAD-BEARING WALL MORE THAN
 TWO STORIES HIGH, SHALL BE PROVIDED INDIVIDUAL
 ENCASEMENT PROTECTION BY PROTECTING THEM ON ALL SIDES
 FOR THE FULL LENGTH, INCLUDING CONNECTIONS TO OTHER
 STRUCTURAL MEMBERS, WITH MATERIALS HAVING THE REQUIRED
 FIRE-RESISTANCE RATING.
  
 704.4 PROTECTION OF SECONDARY MEMBERS. SECONDARY
 MEMBERS THAT ARE REQUIRED TO HAVE A FIRE-RESISTANCE
 RATING SHALL BE PROTECTED BY INDIVIDUAL ENCASEMENT
 PROTECTION, BY THE MEMBRANE OR CEILING OF A HORIZONTAL
 ASSEMBLY IN ACCORDANCE WITH SECTION 711, OR BY A
 COMBINATION OF BOTH.
  
 17) SHEET A2.01B BASEMENT LEVEL;
 17A) THE LAUNDRY TERMINATION ROOM, LAUNDRY ROOM ARE IN
 THE SAME ROOM. THE PLANS DO NOT INDICATE WHERE THE
 LAUNDRY TERMINATION ROOM ENDS AND WHERE THE CORRIDOR
 BEGINS. THE PLANS DO NOT INDICATE WHERE THE DIRTY
 LAUNDRY CARTS ARE GOING TO BE STORED EITHER. THE PLANS
 ALSO SHOW THE SAME LAUNDRY TERMINATION ROOM AS THE
 LAUNDRY ROOM. THE PLANS ARE SILENT AS TO WHERE THE
 CLEAN LINENS ARE TO BE STORED, NOR DO THE PLANS
 INDICATE WHAT WILL BE STORED IN THE BASEMENT LEVEL
 STORAGE ROOM. THIS WHOLE AREA NEEDS TO SHOW HOW
 COMPLIANCE WITH ALL THESE CONCERNS ARE GOING TO BE
 ADDRESSED.
 PLEASE SEE FBC-B 1014.2 EGRESS THROUGH INTERVENING
 SPACES. EGRESS THROUGH INTERVENING SPACES SHALL COMPLY
 WITH THIS SECTION. 4. EGRESS SHALL NOT PASS THROUGH
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 17B) 2014 FBC-B 713.13.4 TERMINATION ROOM. REFUSE,
 RECYCLING, AND LAUNDRY CHUTES SHALL DISCHARGE INTO AN
 ENCLOSED ROOM SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH.
  
 17C) 713.13.4 TERMINATION ROOM. OPENINGS INTO THE
 TERMINATION ROOM SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING EQUAL TO
 THE PROTECTION REQUIRED FOR THE SHAFT ENCLOSURE. 2 HOUR
 SHAFT ENCLOSURES REQUIRE 1 ? HOUR OPENING PROTECTIVES
 TABLE 716.5.
  
 17D) 713.13.4 TERMINATION ROOM. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3. DOOR NOT SHOWN ON
 THE PLANS.
  
 17E)LAUNDRY CHUTE DETAILS. SEE SHEET A6.05 THESE
 DETAILS SEEM TO BE TAKEN FROM A DETAIL SHEET PAGE 2 AND
 3 WHERE THEY ARE NOTE SHOWN. NOTES 1,2,3,8,9,12 & 13.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 17F) PLEASE NOTE IN THIS DETAIL THE 2 HOUR FIRE RATED
 SHAFT IS NOT SHOWN. IT IS NOT CLEAR IF THE SHAFT
 CONTINUES DOWN INTO THE TERMINATION ROOM AND THE 1 ?
 HOUR PROTECTIVE IS THE NOTE(3) DISCHARGE DOOR. THE
 PLANS DO NOT INDICATE ANY FIRE RATING.
  
 17G)(1) THE PLANS ARE NOT CLEAR WITH NOTE 7 AND NOTE 12
 IF THESE ARE A SEPARATE ITEM NOT DEALING WITH THE
 REQUIREMENTS FOR 713.13.6 AUTOMATIC SPRINKLER SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2.
 17G)(2) FBC-B 903.2.11.2 RUBBISH AND LINEN CHUTES. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES SHALL HAVE ADDITIONAL SPRINKLER HEADS
 INSTALLED AT ALTERNATE FLOORS AND AT THE LOWEST INTAKE.
 WHERE A RUBBISH CHUTE EXTENDS THROUGH A BUILDING MORE
 THAN ONE FLOOR BELOW THE LOWEST INTAKE, THE EXTENSION
 SHALL HAVE SPRINKLERS INSTALLED THAT ARE RECESSED FROM
 THE DROP AREA OF THE CHUTE AND PROTECTED FROM FREEZING
 IN ACCORDANCE WITH SECTION 903.3.1.1. SUCH SPRINKLERS
 SHALL BE INSTALLED AT ALTERNATE FLOORS, BEGINNING WITH
 THE SECOND LEVEL BELOW THE LAST INTAKE AND ENDING WITH
 THE FLOOR ABOVE THE DISCHARGE. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 17H) THE SOILED LINEN WHERE TO STORE? VERSES THE CLEAN
 LINEN ROOMS. TABLE 509 INCIDENTAL USES.
  
 17I) INTERIOR WALLS DO NOT HAVE IDENTIFICATION TAGS
 IDENTIFYING WALL TYPES. 107.3.5.1.1 MINIMUM COMMERCIAL
 PLAN REVIEW REQUIREMENTS. (4) FIRE RESISTANT
 CONSTRUCTION.
  
 18) SHEET A2.01A. GROUND FLOOR;
 18A) THIS FLOOR DOES HAVE WALL IDENTIFICATION TAGS.
 WALL TYPES ARE FOUND ON SHEET A8.03.
 THERE ARE (2) ISSUES WITH THE WALL TYPES FOUND ON THIS
 SHEET.
  
 18A)(1) FOR THE METAL STUD FIRE RATED WALLS THESE WALL
 TYPES LIST A UL FIRE RATING AND HOUR RATING. WHAT THE
 DESIGNER OF RECORD DIDN?T INCLUDE WAS A SHEET THAT
 GIVES EACH OF THE WALL ASSEMBLY BREAK DOWNS AS IN THE
 UL LISTING BOOK. THE INSPECTORS NEED THIS INFORMATION
 TO VERIFY THE WALLS WERE BUILT CORRECTLY ACCORDING TO
 THE WALL ASSEMBLY AS TESTED. FBC-B 703.2
 FIRE-RESISTANCE RATINGS.
  
 18B) PLEASE SHOW THE MASONRY WALLS 4 INCH / 2 HR. RATED
 WITH THE CENTER CAVITY. THE DESIGN # 906 IS FOR 6INCH
 BLOCK EITHER HOLLOW OR SOLID BUT NOT FOR A 4 INCH BLOCK
 WALL. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. FBC-B
 TABLE 722.3.2 MINIMUM EQUIVALENT THICKNESS (INCHES) OF
 BEARING OR NONBEARING CONCRETE MASONRY WALLS.
  
 18C) THE L. S. SHEET NOR THE GROUND FLOOR SHOW THE
 PARKING GARAGE AS DESIGNED OPEN OR ENCLOSED. THE PLANS
 DO NOT APPEAR TO MAKE THE REQUIREMENTS FOR AN OPEN
 PARKING GARAGE UNDER SECTION FBC-B 406.5.2 AND WILL
 NEED TO MEET THE REQUIREMENTS FOR 406.6.2 VENTILATION
 AND 406.6.3 AUTOMATIC SPRINKLER SYSTEM.
 THE M1.1 SHEET ALSO DOES NOT SHOW ANY MECHANICAL
 EQUIPMENT FOR MECHANICAL EQUIPMENT. THERE SEAMS TO BE A
 OPENING MISSING IN THE GARAGE CEILING (HIDDEN DASHED
 LINE) ON THE GRID LINE C/ 5 THAT GOES VERTICALLY
 THROUGH TO THE ROOF. IF THE DESIGNERS INTENT IS O TAKE
 CREDIT FOR THE 3 VERTICAL OPENS IN THE CEILING AS WELL
 AS THE ONE ON GRID LINE C/5 AS EQUAL TO CROSS
 VENTILATION FOR AN OPEN PARKING GARAGE, THEN
 CALCULATIONS WILL BE NEEDED TO PROVIDE CODE COMPLIANCE
 UNDER SECTION 104.11 ALTERNATE MATERIALS, DESIGN AND
 METHODS OF CONSTRUCTION AND EQUIPMENT. A LETTER TO THE
 BUILDING OFFICIAL WOULD ALSO NEED TO FOLLOW ASKING THIS
 DESIGN TO BE REVIEWED UNDER 104.11 ALTERNATE MATERIALS,
 DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT.
  
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES.
  
 18D) THE NORTH PROPERTY LINE THERE IS A GATE MARKED #
 3, THIS MOTORIZED GATE SHOWS IN THE OPEN POSITION ON
 BOTH THE GRADE PLAN AND LIFE SAFETY SHEET LS1.01. WHEN
 YOU LOOK AT THE ELEVATION SHEET A3.04 WHEN THE GATE IS
 IN THE CLOSED POSITION IT BLOCKS THE MEANS OF EGRESS
 FROM THE NORTH STAIR TOWER.
  
 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF
 EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF
 THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF
 EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR
 DOORS.
 2014 FBC-B 1008.1.2 DOOR SWING. EXCEPTION 9. IN OTHER
 THAN GROUP H OCCUPANCIES, MANUALLY OPERATED HORIZONTAL
 SLIDING DOORS ARE PERMITTED IN A MEANS OF EGRESS FROM
 SPACES WITH AN OCCUPANT LOAD OF 10 OR LESS.
  
 DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE SERVING A ROOM OR AREA CONTAINING AN OCCUPANT
 LOAD OF 50 OR MORE PERSONS OR A GROUP H OCCUPANCY.
  
 18E) THIS SAME AREA THERE IS A DELIVERY SERVICE AREA 10
 FT. X 25 FT. PLEASE SHOW WHERE THE EXIT DISCHARGE PATH
 OF EGRESS WILL OCCUR SINCE THE DELIVERY LANE IS 10 FEET
 WIDE AND FROM THE BUILDING TO THE PROPERTY LINE
 THERE IS ONLY 11 FEET .
  
 1027.4.1 WIDTH. THE MINIMUM WIDTH OF EGRESS COURTS
 SHALL BE DETERMINED AS SPECIFIED IN SECTION 1005.1, BUT
 SUCH WIDTH SHALL NOT BE LESS THAN 44 INCHES (1118 MM),
 EXCEPT AS SPECIFIED HEREIN. EGRESS COURTS SERVING GROUP
 R- 3 AND U OCCUPANCIES SHALL NOT BE LESS THAN 36 INCHES
 (914 MM) IN WIDTH. THE REQUIRED WIDTH OF EGRESS COURTS
 SHALL BE UNOBSTRUCTED TO A HEIGHT OF 7 FEET (2134 MM).
  
 1027.4.2 CONSTRUCTION AND OPENINGS. WHERE AN EGRESS
 COURT SERVING A BUILDING OR PORTION THEREOF IS LESS
 THAN 10 FEET (3048 MM) IN WIDTH, THE EGRESS COURT WALLS
 SHALL HAVE NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION FOR A DISTANCE OF 10 FEET (3048 MM) ABOVE
 THE FLOOR OF THE COURT. OPENINGS WITHIN SUCH WALLS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR.
  
 18F) THE SOUTH STAIRWAY THE WALKWAY IS NOT DIMENSIONED
 AS TO WIDTH. PLEASE NOTE THE STORAGE DOORS 121 BEING 3
 FOOT WIDE DOORS. SEE SECTION 1005.7.1 DOORS. DOORS IN
 ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY
 MORE THAN ONE-HALF THE REQUIRED EGRESS PATH.
  
 18G) THE GATE # 101 IS A OUT SWING GATE AND HAS LESS
 THAN 18 INCHES ON THE PULL SIDE OF THE LATCH. SEE 2014
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
  
 18H) PLEASE REVIEW THE ENTRY INTO THE PARKING GARAGE
 SOUTH SIDE OF THE BUILDING THERE IS A MOTORIZED GATE.
 THE LOCATION OF THE GATE MOTOR WILL BLOCK ACCESS FOR
 PEOPLE EXITING THE GARAGE TO THE PUBLIC WAY, THE GATE
 IN THE CLOSED POSITION WOULD STILL HAVE TO HAVE A FRAME
 WORK OVER THIS EXIT DISCHARGE. WHEN THE GATE IS IN THE
 OPEN POSITION THE GATE FRAMEWORK WOULD EXTEND PAST THE
 PROPERTY LINE. THE SECOND ISSUE IS FOR THIS WALKWAY TO
 BE ACCESSIBLE THERE CANNOT BE A STEP FROM THE GARAGE UP
 TO THE LANDING FOR THE VERTICAL EXIT.
 THIS IS THE ONLY EXIT OUT OF THE GARAGE. 2014
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 18I) THERE SEEMS TO BE A DISCREPANCY IN PLANS WITH THE
 LOCATION OF GATE # 101. PLEASE ALSO SEE THE SOUTH
 ELEVATION A4.03 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 18J) GATE # 103 SWINGS BACK IN THE FLOW OF EGRESS.
 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF EGRESS
 SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION. GATES USED AS A COMPONENT IN A MEANS OF EGRESS
 SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR DOORS.
 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A
 GROUP H OCCUPANCY.
  
 18K) THE PLANS DO NOT INDICATE A CUT SECTION THROUGH
 THE FRONT COUNTER FOR REGISTERING. PLEASE SHOW HOW
 COMPLIANCE WITH ACCESS. CODE 904.3.2 COUNTER & 904.4
 SALES AND SERVICE COUNTERS. , 904.3.3 CHECK WRITING
 SURFACES & WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3.
  
 19) SHEET A2.02 THE SECOND FLOOR LEVEL:
 19A) THE ACCESSIBLE SUITE # 2 IS MISSING THE 18 INCHES
 ON THE INTERIOR SIDE OF THE MAIN ENTRY DOOR. SEE 2014
 ACCESS. CODE 404.2.4.
  
 19B) THE ACCESSIBLE SUITE SHOWS A DETAIL # 1/ A7.2
 SHOULD INCLUDE THE KITCHENETTE UNIT SINCE IT IS WITHIN
 THE DETAIL, NOT INCLUDED. PLEASE PROVIDE ELEVATION
 DETAILS FOR THE KITCHENETTE AREA AND COMPLIANCE WITH;
 ACCESS. CODE 606.3 HEIGHT. LAVATORIES AND SINKS SHALL
 BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 19C) THE ACCESSIBLE SUITE DOES NOT INDICATE HOW
 COMPLIANCE WITH 242.2 ACCESSIBLE SWIMMING POOLS ARE
 GOING TO BE ACHIEVED. SEE EXCEPTION 1 REQUIREMENT.
 WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET OF
 SWIMMING POOL WALL, NO MORE THAN ONE ACCESSIBLE MEANS
 OF ENTRY SHALL BE REQUIRED PROVIDED THAT THE ACCESSIBLE
 MEANS OF ENTRY IS A SWIMMING POOL LIFT COMPLYING WITH
 1009.2 OR SLOPED ENTRY COMPLYING WITH 1009.3.
  
 19D) THIS IS GOING TO BE A COMMENT FOR ALL UNITS NOT
 JUST THE ACCESSIBLE UNIT. THE PLANS SHOW SLIDING GLASS
 DOORS THAT LED FROM WITHIN THE SUITE OUT TO THE TERRACE
 DECK. THE COMPLETE OPENING BEING 14 FOOT 10 INCHES WIDE
 DIVIDE BY 3 EQUALS OR EACH PANEL 4 FT. 11 ? INCHES
 APPROXIMATELY. THIS SIZE DOOR CAN BE USED IN A MEANS OF
 EGRESS WHEN THE OCCUPANT LOAD IS 10 OR LESS, 1008.1.2
 EXCEP. #9. THE DOOR IS 19/32 IN. LAMINATED GLASS.
 2014 FBC-B 1008.1.3 DOOR OPENING FORCE. THE FORCE FOR
 PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS,
 OTHER THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS (22
 N). FOR OTHER SWINGING DOORS, AS WELL AS SLIDING AND
 FOLDING DOORS, THE DOOR LATCH SHALL RELEASE WHEN
 SUBJECTED TO A 15-POUND (67 N) FORCE. THE DOOR SHALL BE
 SET IN MOTION WHEN SUBJECTED TO A 30-POUND (133 N)
 FORCE. THE DOOR SHALL SWING TO A FULL-OPEN POSITION
 WHEN SUBJECTED TO A 15-POUND (67 N) FORCE.
 FOR THE ACCESSIBLE UNIT THE OPENING FORCE FOR THE
 SLIDING GLASS DOOR WILL BE FBC-ACCESS. CODE 404.2.9
 DOOR AND GATE OPENING FORCE. FIRE DOORS SHALL HAVE A
 MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE
 ADMINISTRATIVE AUTHORITY. THE FORCE FOR PUSHING OR
 PULLING OPEN A DOOR OR GATE OTHER THAN FIRE DOORS SHALL
 BE AS FOLLOWS: 2. SLIDING OR FOLDING DOORS: 5 POUNDS
 (22.2 N) MAXIMUM.
  
 19E) THE OTHER ISSUE COMMON TO ALL UNITS WITH THE
 SLIDING DOOR TO THE POOL DECK IS: 404.2.7 DOOR AND GATE
 HARDWARE. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER
 OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH
 309.4. OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34
 INCHES (865 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. WHERE SLIDING DOORS
 ARE IN THE FULLY OPEN POSITION, OPERATING HARDWARE
 SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 EXCEPTIONS: 2. ACCESS GATES IN BARRIER WALLS AND FENCES
 PROTECTING POOLS, SPAS, AND HOT TUBS SHALL BE PERMITTED
 TO HAVE OPERABLE PARTS OF THE RELEASE OF LATCH ON
 SELF-LATCHING DEVICES AT 54 INCHES (1370 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PROVIDED THE
 SELF-LATCHING DEVICES ARE NOT ALSO SELF-LOCKING DEVICES
 AND OPERATED BY MEANS OF A KEY, ELECTRONIC OPENER, OR
 INTEGRAL COMBINATION LOCK.
  
 THE DOORS ARE TO BE SELF-CLOSING AND SELF-LATCHING.
 FBC-B 454.1.3.1.9 ACCESS THROUGH THE BARRIER OR FENCE
 FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS, MOTEL
 ROOMS AND HOTEL ROOMS, SHALL BE THROUGH SELF-CLOSING,
 SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM)
 MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH THE LATCH
 LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM THE
 BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM) BELOW
 THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND.
  
 19F) PLEASE NOTE THE SLIDING GLASS DOOR, THE THRESHOLD
 INDICATES ONLY TO BE ? INCH HIGH. 404.2.5 THRESHOLDS.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN
 LEVEL AT DOORWAYS SHALL COMPLY WITH ACCESS. CODE 302
 AND 303. HOW WILL WATER INTRUSION BE HANDLED IN A
 HURRICANE?
  
 19G) COMMON COMMENT FOR ALL FLOORS. THE SHAFT WALLS FOR
 THE LAUNDRY CHUTE DO NOT HAVE WALL IDENTIFICATION TAGS.
 FBC-B 713.4 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES
 SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2
 HOURS WHERE CONNECTING FOUR STORIES OR MORE, AND NOT
 LESS THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR
 STORIES.
  
 19H) COMMON COMMENT FOR ALL FLOORS. PLEASE SEE DOOR # 8
 TO THE HOSE KEEPING ROOM IN THE DOOR SCHEDULE MISSING
 THE FIRE RATING. FBC-B 713.13.3 REFUSE, RECYCLING AND
 LAUNDRY CHUTE ACCESS ROOMS.
 ACCESS OPENINGS FOR REFUSE, RECYCLING AND LAUNDRY
 CHUTES SHALL BE LOCATED IN ROOMS OR COMPARTMENTS
 ENCLOSED BY NOT LESS THAN 1-HOUR FIRE BARRIERS
 CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH. OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. DOORS
 SHALL BE SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION
 OF SMOKE IN ACCORDANCE WITH SECTION 716.5.9.3.
  
 20) THE ACCESSIBLE SUITE SHOWS A DETAIL # 1/ A7.2. THE
 ACCESSIBLE BATHROOM:
 20A) THIS SHEET STATES MANY TIMES ON THE SHEET THIS IS
 A ADA COMPLIANT. PLEASE NOTE THE DESIGN MAYBE ADA
 COMPLIANT BUT THE STATE OF FLORIDA USES THE 2014
 FLORIDA ACCESSIBILITY CODE THAT HAS BEEN APPROVED BY
 THE DEPARTMENT OF JUSTICE. THE FLORIDA ACCESSIBILITY
 CODE IS A MORE STRINGENT CODE THAN THE ADA. PLEASE
 REVIEW THE CLEAR FLOOR SPACE REQUIRED FOR THE WATER
 CLOSET.
 2014 FBC-ACCESS. CODE 604.3.2 OVERLAP. THE REQUIRED
 CLEARANCE AROUND THE WATER CLOSET SHALL BE PERMITTED TO
 OVERLAP THE WATER CLOSET, ASSOCIATED GRAB BARS,
 DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS,
 SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND
 CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE TURNING
 SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 20B) DETAIL D NOTE 11 INDICATES BACKING IS REQUIRED FOR
 ADAPTABLE BATHROOMS. TABLE 224.2 WILL REQUIRE AT LEAST
 ONE GUESTROOM/ BATHROOM TO COMPLY WITH GUEST ROOM WITH
 MOBILITY FEATURES, 609.8 STRUCTURAL STRENGTH. ALLOWABLE
 STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN
 A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS IS APPLIED
 AT ANY POINT ON THE GRAB BAR, FASTENER, MOUNTING
 DEVICE, OR SUPPORTING STRUCTURE.
  
 20C) PLEASE NOTE ON THE GRAB BAR DIMENSIONS THE 2014
 FBC-ACCESSIBILITY CODE TAKES THE DIMENSIONS FROM THE
 TOP OF THE GRASPING SURFACE NOT CENTERLINE. 609.4.
  
 20D) TOWEL BARS ARE NOT DIMENSIONED BUT SHOULD BE IN
 THE REACH RANGES FOR EITHER FORWARD OR SIDE APPROACH
 SEE FBC-ACCESS. CODE 308.1.
 20E) COAT HOOKS AND SHELVING TO COMPLY WITH 604.2.
  
 20F) THE STEAM SHOWER IN THE ACCESSIBLE GUEST UNIT WILL
 ALSO NEED TO SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS.
 CODE ;
 20F)(1) 612.2 BENCH. WHERE SEATING IS PROVIDED IN
 SAUNAS AND STEAM ROOMS, AT LEAST ONE BENCH SHALL COMPLY
 WITH 903. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED BY 903.2. EXCEPTION: A READILY REMOVABLE
 BENCH SHALL BE PERMITTED TO OBSTRUCT THE TURNING SPACE
 REQUIRED BY 612.3 AND THE CLEAR FLOOR OR GROUND SPACE
 REQUIRED BY 903.2.
  
 20F)(2) 612.3 TURNING SPACE. A TURNING SPACE COMPLYING
 WITH 304 SHALL BE PROVIDED WITHIN SAUNAS AND STEAM
 ROOMS.
  
 21) SHEET A2.07 THESE COMMENTS WILL BE COMMON TO ALL
 FLOORS 2-5;
 21A) NOTE # 14 INDICATES THE USE OF TREX DECK TERRACE
 AND CEILING. THERE IS NO PRODUCT INFORMATION FOR THE
 TREX DECK SYSTEM. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATION, IF THIS IS A COMBUSTIBLE PRODUCT AND IF
 SO THE FLAME SPREAD AND TO WHAT STANDARD THE PRODUCT
 WAS TESTED TOO? SEE FBC-B SECTION 603 COMBUSTIBLE
 MATERIAL IN TYPE I AND II CONSTRUCTION. 603.1 ALLOWABLE
 MATERIALS.
  
 21B) THERE ARE NO PLANS FOR THE TREX DECK DROP CEILING
 ASSEMBLY. TYPE OF FRAMING, MATERIAL, SPACING, SIZE OF
 FRAMING MEMBERS, ANCHORAGE TO THE DECK ABOVE IF STIFF
 BACKS ARE REQUIRED. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL BUILDINGS:
 DROPPED EXTERIOR CEILING ASSEMBLIES.
  
 21C) DETAILS 3 & 4 BOTH INDICATE THE USE OF INSULATION
 IN BOTH THE MECHANICAL PLENUM AS WELL AS THE DROPPED
 CEILING WITHIN THE TYPICAL SUITE. THE PLANS DOES NOT
 DECLARE WHAT TYPE OF INSULATION IS GOING TO BE
 INSTALLED? IS THIS INSULATION GOING TO BE FOR BOTH
 SOUND AND THERMAL VALUES? SEE FBC-B 720.1 & 720.2.
  
 21D) DETAILS 3 & 4 WITHIN THE SUITE SHOW A DROPPED
 CEILING ASSEMBLY, FASTENED TO THE CONCRETE DECK ABOVE
 AS WELL AS A DROPPED CEILING ASSEMBLY WITH WHAT MAYBE A
 LIGHT TROUGH. THE INSULATION ABOVE WOULD STILL BE
 WITHIN THE ROOM PROPER. PLEASE PROVIDE ADDITIONAL
 DETAILS AS TO THE TYPE OF FRAMING MATERIALS, ANCHORAGE
 TO THE DECK ABOVE, SIZE OF FRAMING MEMBERS, SPACING OF
 FRAMING MEMBERS THE TYPE OF INSULATION, THE THICKNESS
 AND TYPE OF FINISH MATERIAL FOR THE DROPPED CEILING. .
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: DROPPED EXTERIOR
 CEILING ASSEMBLIES.
 FBC-B 720.3 EXPOSED INSTALLATION. INSULATING MATERIALS,
 WHERE EXPOSED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
 FBC-B 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND
 CEILINGS ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR
 NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR
 CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED
 IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN
 ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE
 USED.
  
 21E) PLEASE NOTE THE PLANS DO NOT ADDRESS THE FRAMING
 MEMBERS FOR THE POOL DECK. SHEET S-13 SECTION SHOWS
 3X12?S AT 16 INCHES ON CENTER. THIS BUILDING IS
 CLASSIFIED AS A BUILDING TYPE IIA.
  
 FBC-B SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION. 603.1 ALLOWABLE MATERIALS. EXCEPTION; 12.
 STAGES AND PLATFORMS CONSTRUCTED IN ACCORDANCE WITH
 SECTIONS 410.3 AND 410.4, RESPECTIVELY.
 410.4 PLATFORM CONSTRUCTION. PERMANENT PLATFORMS SHALL
 BE CONSTRUCTED OF MATERIALS AS REQUIRED FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING IN WHICH THE PERMANENT
 PLATFORM IS LOCATED. PERMANENT PLATFORMS ARE PERMITTED
 TO BE CONSTRUCTED OF FIRE-RETARDANT-TREATED WOOD FOR
 TYPES I, II AND IV CONSTRUCTION WHERE THE PLATFORMS ARE
 NOT MORE THAN 30 INCHES (762 MM) ABOVE THE MAIN FLOOR,
 AND NOT MORE THAN ONE-THIRD OF THE ROOM FLOOR AREA AND
 NOT MORE THAN 3,000 SQUARE FEET (279 M2) IN AREA. WHERE
 THE SPACE BENEATH THE PERMANENT PLATFORM IS USED FOR
 STORAGE OR ANY PURPOSE OTHER THAN EQUIPMENT, WIRING OR
 PLUMBING, THE FLOOR ASSEMBLY SHALL BE NOT LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE
 SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR
 EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE
 PERMANENT PLATFORM NEED NOT BE PROTECTED.
  
 21F) THE S-13 SHEET DOES NOT PROVIDE THE TYPE OF
 ANCHORS TO HOLD THE LEDGER BOARD NOR THE TYPE OF
 BUCKETS TO HOLD THE FRAMING MEMBERS. 107.3.5 MINIMUM
 PLAN REVIEW CRITERIA FOR BUILDINGS. 107.3.5.1
 COMMERCIAL BUILDINGS. FLOOR SYSTEMS.
  
 21G) POOLS AND ASSOCIATED EQUIPMENT WILL BE UNDER
 SEPARATE PERMITS FOR EACH UNIT FOR THE RECORDING OF
 INSPECTIONS. 105.1. PERMITS REQUIRED.
  
 22) SHEET A3.03 THE GREEN SCREEN SYSTEM PANELS CAN BE A
 SUBMITTAL THAT COULD QUALIFY AS A DEFERRED SUBMITTAL,
 PLEASE PROVIDE THE WIND DESIGN PARAMETERS FOR THE
 SPECIALTY ENGINEERS CAN DESIGN TO THE PROPER WIND
 SPEED. 107.3.4.2 DEFERRED SUBMITTALS. 2014 FBC-B
 1603.1.4 WIND DESIGN DATA.
  
 23) SHEET A2.05 ROOF PLAN.
  
 23A) THE ROOF DRAINS 2 & 3 BOTH ARE MISSING
 SECONDARY(EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. FBC-B
 1503.4.1.
  
 23B) STAIR TOWER 1 & 2 BOTH SHOW OVERFLOW SCUPPERS BUT
 NO SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS.
 FBC-B 1503.4.1.
  
 23C) PLEASE PROVIDE DETAILS FOR SCUPPERS AND OVERFLOW
 SCUPPERS, THE BOTTOM OF EACH UNIT IN RELATIONSHIP WITH
 THE ROOF. FBC-B 1503.4.2 SCUPPERS. OVERFLOW SCUPPERS
 ARE SHOWN.
  
 23D) PLEASE PROVIDE A ANCHORING DETAIL FOR THE ROOF TOP
 A/C STANDS FOR THE APPROPRIATE SIZE OF ROOF TOP
 COMPRESSOR. PLEASE ALSO INCLUDE THE ATTACHMENT OF THE
 COMPRESSOR TO THE STAND. FBC-B 2014 FBC-B 1604.4
 ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS?
  
 23E) PLEASE PROVIDE THE MINIMUM HEIGHT REQUIREMENTS FOR
 THE A/C STANDS IN COMPLIANCE WITH FBC-B TABLE 1509.6.5.
  
 23F) ROOFTOP SKYLIGHTS. SECTION 603 COMBUSTIBLE
 MATERIAL IN TYPE I AND II CONSTRUCTION. 603.1 ALLOWABLE
 MATERIALS. 15. LIGHT-TRANSMITTING PLASTICS AS PERMITTED
 BY CHAPTER
 26. PLEASE PROVIDE COMPLIANCE WITH: 2609.4 AREA
 LIMITATIONS. ROOF PANELS SHALL BE LIMITED IN AREA AND
 THE AGGREGATE AREA OF PANELS SHALL BE LIMITED BY A
 PERCENTAGE OF THE FLOOR AREA OF THE ROOM OR SPACE
 SHELTERED IN ACCORDANCE WITH TABLE 2609.4. CC1 OR CC2?
  
 23G) SHEET A4.03 SHOWS A CUT SECTION THROUGH THE
 SKYLIGHT WITH A CMU CURB. THERE ARE NO DETAILS OF THIS
 CURB IN THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL
 SHEETS. 107.2.1.3 ADDITIONAL INFORMATION IS ENQUIRED.
  
 23H) PLEASE REVIEW NOTES ON THE RIGHT SIDE OF THE PAGE
 1-15 THESE DEAL WITH THE FLOORS BELOW. NEED TO BE
 DELETED. 107.2.1.3 DISCREPANCY IN PLANS.
  
 24) SHEET A6.03, ELEVATOR, PLEASE SHOW COMPLIANCE WITH
 FBC-B 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER. THE ELEVATOR CAR SHALL BE OF SUCH A SIZE AND
 ARRANGEMENT TO ACCOMMODATE AN AMBULANCE STRETCHER 24
 INCHES BY 76 INCHES (610 MM BY 2134 MM) WITH NOT LESS
 THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
  
 DO NOT QOUTE CODE. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART,?
  
 25) SHEET A4.03 PLEASE PROVIDE DETAILS FOR THE EYEBROW,
 ANCHORING AND TYPE OF MATERIALS CONSTRUCTED AT
 ELEVATION 71.416 FT. 1406.2.1 TYPE I, II, III AND IV
 CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS,
 COMPLYING WITH THE FOLLOWING LIMITATIONS: 2.
 COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
  
 26) SHEET A8.11: DETAILS SHOULD BE TO THE 2014 FLORIDA
 ACCESSIBILITY CODE NOT THE ADA.
  
 26A) THE TOWEL BAR IS INDICATED TO BE 54 INCHES HIGH
 (ADA). MUST BE IN THE REACH RANGES FOR ACCESSIBILITY.
 SEE ACCESS. CODE 308.2.1 UNOBSTRUCTED FORWARD. 308.3.2
 OBSTRUCTED SIDE REACH.
  
 26B) ALL OF THE DETAILS FOR GRAB BARS ARE TAKEN AT THE
 CENTERLINE. PLEASE BE AWARE OF THE 2014
 FBC-ACCESSIBILITY CODE 609.4 THE MEASUREMENTS ARE TO BE
 TAKEN FROM FINISH FLOOR TO THE TOP OF THE GRASPABLE
 SURFACE 33-36 INCHES.
  
 26C) HIGH/ LOW DRINKING FOUNTAIN. 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. 602.7 DRINKING FOUNTAINS
 FOR STANDING PERSONS.
  
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 27) SHEETS S-16 THROUGH S-19 INDICATE POSITIVE AND
 NEGATIVE PRESSURES FOR THE COMPONENTS AND CLADDING. THE
 PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA NOR DOES
 THE PLANS INDICATE IF THE PRESSURES ARE IN VULT OR
 VASD.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. >60 FT. TALL/
 ASCE 7-10.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 28) PLEASE PROVIDE WHERE ON THE STRUCTURAL SHEETS THE
 PRESSURES FOR ROOF ZONES 1, 2 & 3. MISSING IN THE
 PLANS. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. >60 FT.
 TALL/ ASCE 7-10.
  
 29) FOR THE PRODUCT APPROVALS WITH GLAZED OPENINGS AND
 MULLIONS , PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE THE SUBMITTED PRODUCT APPROVALS THERE ARE TO MANY
 VARIABLE, CIRCLE TO IDENTIFY EACH COMPONENT. COMPONENTS
 & CLADDING.
  
 30) THE NOA 15-0731.06 MIAMI ROLLING DOOR SUBMITTED
 REPORT GOOD FOR +/- 65 SHEET S-18 SHOWS PRESSURES OF
 -87, VASD OR VULT NOT GIVEN ON THE SHEET. ALL PRODUCT
 APPROVALS ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION
 VULT TO VASD.
  
 31) .(2) ROOFING APPROVALS WERE SUBMITTED FOR THIS
 REVIEW.
 CARLISLE MIRASEAL FLUID APPLIED WATERPROOFING MEMBRANE
 NOA 13-0129.22
 CARLISLE CCW-500-R HOT APPLIED LIQUID MEMBRANE NOA
 12-0801.01
 IN BOTH APPROVALS THERE ARE MULTIPLE SUB-SYSTEMS AND
 ASSOCIATED PRESSURES. IN NEITHER REPORT WAS A
 SUB-SYSTEM AND ASSOCIATED PRESSURES INDICATED. ALSO IN
 BOTH REPORTS LIMITATION # 9 IS INDICATED NO ENHAANCED
 FASTENING CAN OCCUR. THE PLANS DO NOT INDICATE ROOF TOP
 PRESSURES FOR ZONES 1,2 & 3. PLEASE PROVIDE PRESSURES
 IN VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. 2014
 FBC- B 1603.1.4 WIND DESIGN DATA.
  
 32) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 33) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 34) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-18 Cont ID  
Sent By vperez Date 2016-10-18 Time 16:45 Rev Time 0.00
Received By vperez Date 2016-10-18 Time 16:45 Sent To  
Notes
2016-10-18 16:47:08PROVISO: SUBMIT AVAILABLE FAULT CURRENT FPL LETTER AT
 TRANSFORMER AND AIC CALCULATIONS ON AS BUILTS
  
 VAL PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By vperez Date 2016-07-28 Time 07:17 Rev Time 0.00
Received By vperez Date 2016-07-27 Time 08:15 Sent To  
Notes
2016-07-28 07:17:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM,
 ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS,
 POOLS IN UNITS, ETC. A NOTE WILL SUFFICE.
 2. SHEET E1.00- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET E1.00- ADD A NOTE TO MAINTAIN ALL ELECTRICAL
 EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE
 AND CITY REGULATORY AGENCIES.
 4. ADDRESS ALL FIRE COMMENTS RELATED TO ELECTRICAL
 DESIGN. FBC 107.3.5
 5. PER FBC ENERGY CONSERVATION 2014 C405.7 PROVIDE
 REQUIRED VOLTAGE DROP CALCULATIONS FOR FEEDERS AND
 BRANCH CIRCUIT
 6. PER NEC 110.16 ARC FLASH WARNING- SEE CODE. GENERAL
 NOTE WILL SUFFICE AT RISER DIAGRAM
 7. PER NEC 110.24A- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS. ADD GENERAL NOTE INDICATING REQUIREMENTS AT
 THE SERVICE. A NOTE WILL SUFFICE
 8. PROVIDE AIC CALCULATIONS PER NEC 110.9 AND 110.10-
 SHOW AIC AT THE FPL TRANSFORMER WITH FPL LETTERHEAD
 INDICATING AVAILABLE FAULT CURRENT. FBC 107.3.5
 9. SUBMIT 1/2" DETAIL OF MAIN ELECTRICAL ROOM NOT 1/4"
 AS SHOWN. NEED TO VERIFY IF PER NEC 110.26C2
 UNOBSTRUCTED EGRESS IS MET PER DEPTH OF DISTANCE FROM
 EQUIPMENT TO DOOR PER AHJ PERMISSION.
 10. CORRECT TYPO AT RISER DIAGRAM TO SHOW ID PANEL MDPB
 NOT MDBA FOR MAIN #2.
 11. ADD A NOTE TO UNITS PER NEC 406.13- ALL GUEST UNITS
 TO HAVE TAMPER RESISTANT RECEPTACLES.
 12. PROVIDE A GENERAL NOTE TO UNITS TO INDICATE FOR NOW
 THE REQUIREMENTS OF NEC 680 POOLS EQUIPMENT LOCATION TO
 MAINTAIN DISTANCES REQUIRED FOR RECEPTACLES AND
 LIGHTING (DIMENSIONS MAY REQUIRE GFCI PROTECTION).
 SEPARATE POOL PERMITS WILL THEN BE REVIEWED PER SCOPE.
 FBC 107.3.5
 13. PLEASE CONFIRM IF PARKING AREA WILL HAVE
 VENTILATION FOR CO EXHAUST, SEE FIRE REVIEW AND ADDRESS
 ELECTRICAL SCOPE. FBC 107.3.5
 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By Mgonzale Date 2016-10-03 Time   Rev Time  
Received By mgonzale Date 2016-10-03 Time   Sent To I
Notes
2016-10-03 16:36:29COMPLY WITH ZONING AND FIRE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-21 Cont ID  
Sent By pleduc Date 2016-10-21 Time   Rev Time 0.00
Received By pleduc Date 2016-10-19 Time 16:04 Sent To  
Notes
2016-10-21 10:26:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) PLEASE PROVIDE OFFICIAL REVISIONS FOR THE MECHANICAL
 SMOKE CONTROL/VENTILATION OF THE BASEMENT FOR APPROVAL.
  
  
 2) PLEASE COORDINATE AN ALTERNATIVE LOCATION FOR THE
 FACP WITH BUREAU.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By pleduc Date 2016-08-01 Time   Rev Time 0.00
Received By pleduc Date 2016-07-22 Time 15:28 Sent To  
Notes
2016-07-27 11:13:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.01 - CONTRUCTION TYPE/OCCUPANCY. PLEASE
 PROVIDE INDICATIONS/ VERIFICATIONS/CLARIFICATONS AS TO
 THE OCCUPANCY CLASSIFICATION OF THE HOTEL AND THE THE
 PARKING GARAGE. THE PARKING GARAGE IS A PARKING
 STRUCTURE IN ACCORDANCE OF NFPA 88A AND APPLICABLE
 REQUIRMENTS.
  
  
 28.1.3 MULTIPLE OCCUPANCIES.
 28.1.3.1 MULTIPLE OCCUPANCIES SHALL BE IN ACCORDANCE
 WITH 6.1.14.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCER
 RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
  
 PLEASE PROVIDE VERIFICATION AND THE APPLICABLE
 REQUIRMENTS.
  
  
 2) SHEET LS 1.01 - A PARKING GARAGE IS INDICATED ON THE
 GROUND FLOOR. IS IT AN OPEN PAKING STRUCUTRE OR CLOSED
 PARKING STRUCTURE?
  
 PER NFPA 88A STANDARD FORPARKING STRUCTURES 2011
 EDITION- 3.3 GENERAL DEFINITIONS. 3.3.2* PARKING
 STRUCTURE. A BUILDING, STRUCTURE, OR PORTION THEREOF
 USED FOR THE PARKING, STORAGE, OR BOTH, OF MOTOR
 VEHICLES.
 3.3.2.3 PARKING STRUCTURE, ENCLOSED. ANY PARKING
 STRUCTURE THAT IS NOT AN OPEN PARKING STRUCTURE.
 3.3.2.4 PARKING STRUCTURE, OPEN. A PARKING STRUCTURE
 THAT MEETS THE REQUIREMENTS OF SECTION 5.5.
  
 PLEASE PROVIDE INDICATIONS/JUSTIFICATION OF TYPE OF
 PARKING STRUCTURE AND COMPLIANCE WITH THE REQUIRMENTS.
  
  
  
 3) SHEET LS 1.01 & 2-5 FLOOR PLAN SHEETS. THE MEANS OF
 EGRESS SHALL COMPLY WITH NFPA 101 CHAPTER 28, NEW
 HOTELS AND DORMITORIE AND ALL APPLICABLE CODES.
 EXIT FROM THE HOTEL ROOM CORRIDOR APPEARS TO BE OEPNING
 INTO AN OPEN CORRIDOR.
  
 28.2.2 MEANS OF EGRESS COMPONENTS.
 28.2.2.1 GENERAL.
 28.2.2.1.1 COMPONENTS OF MEANS OF EGRESS SHALL BE
 LIMITED TO THE TYPES DESCRIBED IN 28.2.2.2 THROUGH
 28.2.2.12.
 28.2.2.1.2 IN BUILDINGS, OTHER THAN HIGH-RISE
 BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 28.3.5, EXIT ENCLOSURES SHALL HAVE A
 MINIMUM 1-HOUR FIRE RESISTANCE RATING, AND DOORS SHALL
 HAVE A MINIMUM 1-HOUR FIRE PROTECTION RATING.
  
 28.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 28.2.5.1 ACCESS TO ALL REQUIRED EXITS SHALL BE IN
 ACCORDANCE WITH SECTION 7.5, AS MODIFIED BY 28.2.5.2.
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS.
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO THAT EXITS ARE READILY ACCESSIBLE AT
 ALL TIMES.
 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE
 FROM AN OPEN FLOOR AREA, CONTINUOUS PASSAGEWAYS,
 AISLES, OR CORRIDORS LEADING DIRECTLY TO EVERY EXIT
 SHALL BE MAINTAINED AND SHALL BE ARRANGED TO PROVIDE
 ACCESS FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY
 SEPARATE WAYS OF TRAVEL, UNLESS OTHERWISE PROVIDED IN
 7.5.1.1.3 AND 7.5.1.1.4.
  
 28.3.6 CORRIDORS.
 28.3.6.1 WALLS.
 28.3.6.1.1 EXIT ACCESS CORRIDOR WALLS SHALL COMPLY WITH
 28.3.6.1.2 OR 28.3.6.1.3.
 28.3.6.1.2 IN BUILDINGS NOT COMPLYING WITH 28.3.6.1.3,
 EXIT ACCESS CORRIDOR WALLS SHALL CONSIST OF FIRE
 BARRIERS IN ACCORDANCE WITH SECTION 8.3 THAT HAVE NOT
 LESS THAN A 1-HOUR FIRE RESISTANCE RATING.
 28.3.6.1.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 28.3.5, CORRIDOR WALLS SHALL HAVE A
 MINIMUM?-HOUR FIRE RESISTANCE RATING.
  
 THE ARRANGEMENTS OF THE EXITS ARE NOT IMMEDIATELY
 ACCESSIBLE AND DO NOT MEET THE PROVISIONS INDICATED.
  
 A PROTECTED CORRIDOR IS REQUIRED OR EACH FLOOR LEVEL.
  
  
  
 4) SHEET LS 1.01 & A 2.01B - A BASEMENT IS INDICATED
 WITH ONLY ONE (1) EXIT.
  
 PER NFPA 101, CHAPTER 28,
  
 28.2.4 NUMBER OF MEANS OF EGRESS.
 28.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING, EXCEPT AS OTHERWISE PERMITTED BY 28.2.4.2
 AND 28.2.4.3:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY PART OF EVERY STORY.
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET.
 7.4.1.2 THE NUMBER OF MEANS OF EGRESS FROM ANY STORY OR
 PORTION THEREOF, OTHER THAN FOR EXISTING BUILDINGS AS
 PERMITTED IN CHAPTERS 11 THROUGH 43, SHALL BE AS
 FOLLOWS:
 (1) OCCUPANT LOAD MORE THAN 500 BUT NOT MORE THAN 1000
 ? NOT LESS THAN 3
 (2) OCCUPANT LOAD MORE THAN 1000 ? NOT LESS THAN 4
  
 PLEASE PROVIDE A SECOND (2ND) EXIT FORM THE BASEMENT.
  
  
 5) SHEET LS 1.01 & M 1.00 - THERE IS NO INDICATIONS OF
 SMOKE VENTING IN/FROM THE BASEMENT AREA.
  
 NFPA 101 CHAPTER 11 SPECIAL STRUCTURES AND HIGH-RISE
 BUILDINGS
 11.7 UNDERGROUND AND LIMITED ACCESS STRUCTURES.
 11.7.4 ADDITIONAL PROVISIONS FOR UNDERGROUND
 STRUCTURES.
 11.7.4.1 A STRUCTURE OR PORTION OF A STRUCTURE SHALL
 NOT BE CONSIDERED AN UNDERGROUND STRUCTURE IF THE STORY
 IS PROVIDED, ON NOT LESS THAN TWO SIDES, WITH NOT LESS
 THAN 20 FT2 (1.9 M2) OF EMERGENCY ACCESS OPENING
 LOCATED ENTIRELY ABOVE THE ADJOINING FINISHED GROUND
 LEVEL IN EACH 50 LINEAL FT (15 LINEAL M) OF EXTERIOR
 ENCLOSING WALL AREA.
 11.7.4.2 THE REQUIREMENTS OF 11.7.3 SHALL APPLY.
 11.7.4.4 THE UNDERGROUND PORTIONS OF AN UNDERGROUND
 STRUCTURE,OTHER THAN AN EXISTING UNDERGROUND STRUCTURE,
 SHALL BE PROVIDED WITH APPROVED AUTOMATIC SMOKE VENTING
 IN ACCORDANCE WITH SECTION 9.3 WHERE THE UNDERGROUND
 STRUCTURE HAS THE FOLLOWING FEATURES:
 (1) OCCUPANT LOAD OF MORE THAN 100 PERSONS IN THE
 UNDERGROUND PORTIONS OF THE STRUCTURE
 (2) FLOOR LEVEL USED FOR HUMAN OCCUPANCY LOCATED MORE
 THAN 30 FT (9.1 M) BELOW THE LOWEST LEVEL OF EXIT
 DISCHARGE, OR MORE THAN ONE LEVEL LOCATED BELOW THE
 LOWEST LEVEL OF EXIT DISCHARGE
 (3) COMBUSTIBLE CONTENTS, COMBUSTIBLE INTERIOR FINISH,
 OR COMBUSTIBLE CONSTRUCTION
  
 PLEASE PROVIDE SMOKE VENTING FOR THE BASEMANT AREA AS
 REQUIRED PER (3).
  
  
  
 6) SHEET LS 1.01 & 2-5 FLOOR PLAN SHEETS - THERE
 APPEARS TO BE TWO(2) UNPROTECTED VERICAL OPENINGS:
  
 A.THE AREA ON THE WEST SIDE OPENING FROM THE PARKING
 GARAGE UP THROUGH THE ROOF.
 B. THE AREA LOCATED MORE NORTH INTERIOR FROM THE SECOND
 (2ND) FLOOR THROUGH THE ROOF.
  
 NFPA 101, CHAPTER 28
 28.3 PROTECTION.
 28.3.1 PROTECTION OF VERTICAL OPENINGS.
 28.3.1.1 VERTICAL OPENINGS SHALL COMPLY WITH 28.3.1.1.1
 THROUGH 28.3.1.2.
 28.3.1.1.1 VERTICAL OPENINGS SHALL BE ENCLOSED OR
 PROTECTED IN ACCORDANCE WITH SECTION 8.6.
 28.3.1.1.2 VERTICAL OPENINGS IN ACCORDANCE WITH 8.6.9.1
 SHALL BE PERMITTED.
 28.3.1.1.3 IN BUILDINGS, OTHER THAN HIGH-RISE
 BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 28.3.5, THE WALLS ENCLOSING VERTICAL
 OPENINGS SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING, AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE
 PROTECTION RATING.
  
 8.6 VERTICAL OPENINGS.
 8.6.1 FLOOR SMOKE BARRIERS. EVERY FLOOR THAT SEPARATES
 STORIES IN A BUILDING SHALL MEET THE FOLLOWING
 CRITERIA:
 (1) IT SHALL BE CONSTRUCTED AS A SMOKE BARRIER IN
 ACCORDANCE WITH SECTION 8.5.
 (2) IT SHALL BE PERMITTED TO HAVE OPENINGS AS DESCRIBED
 BY 8.6.6, 8.6.7, 8.6.8, 8.6.9, OR CHAPTERS 11 THROUGH
 43. 8.6.2* CONTINUITY. OPENINGS THROUGH FLOORS SHALL BE
 ENCLOSED WITH FIRE BARRIER WALLS, SHALL BE CONTINUOUS
 FROM FLOOR TO FLOOR, OR FLOOR TO ROOF, AND SHALL BE
 PROTECTED AS APPROPRIATE FOR THE FIRE RESISTANCE RATING
 OF THE BARRIER.
  
 PLEASE PROVIDE THE REQUIRED PROTECTION AS INDICATED.
  
  
  
 7) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT
 INCLUDES A LAUNDRY CHUTE. NO DIMENSIONS ARE INDICATED
 OF THE SIZE OF ROOM.
  
 PER NFPA 101 CHAPTER 28
 28.5.4 RUBBISH CHUTES, INCINERATORS, AND LAUNDRY
 CHUTES. RUBBISH CHUTES, INCINERATORS, AND LAUNDRY
 CHUTES SHALL COMPLY WITH THE PROVISIONS OF SECTION 9.5.
  
 9.5 RUBBISH CHUTES, INCINERATORS, AND LAUNDRY CHUTES.
 9.5.1 ENCLOSURE.
 9.5.1.1 RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE
 SEPARATELY ENCLOSED BY WALLS OR PARTITIONS IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 8.3.
  
 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING
 SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH
 SECTION 8.7.
 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4
 SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE
 FOLLOWING:
 (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED
 SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED
 SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN
 TO A CORRIDOR OR NORMALLY OCCUPIED SPACE.
 (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE
 PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37
 M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM
 IS PROTECTED BY AUTOMATIC SPRINKLERS.
  
 THOUGH IT APPEARS TO COMPLY, PLEASE PROVIDE DIMENSIONS
 TO ENSURE COMPLAINCE WITH THE ABOVE (2).
  
  
  
 8) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT
 INCLUDES A LAUNDRY CHUTE. THE ROOM IS NOT INDICATED AS
 BEING PROTECTED UNDER THE REQUIREMENTS OF THE
 FOLLOWING.
  
 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING
 SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH
 SECTION 8.7.
  
 8.7.1.2 IN NEW CONSTRUCTION, WHERE PROTECTION IS
 PROVIDED WITH AUTOMATIC EXTINGUISHING SYSTEMS WITHOUT
 FIRE-RESISTIVE SEPARATION, THE SPACE PROTECTED SHALL BE
 ENCLOSED WITH SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION 8.4, UNLESS OTHERWISE PERMITTED BY ONE OF THE
 FOLLOWING CONDITIONS:
 (1) WHERE MERCANTILE OCCUPANCY GENERAL STORAGE AREAS
 AND STOCKROOMS ARE PROTECTED BY AUTOMATIC SPRINKLERS IN
 ACCORDANCE WITH SECTION 9.7
 (2) WHERE HAZARDOUS AREAS IN INDUSTRIAL OCCUPANCIES ARE
 PROTECTED BY AUTOMATIC EXTINGUISHING SYSTEMS IN
 ACCORDANCE WITH 40.3.2
 (3) WHERE HAZARDOUS AREAS IN DETENTION AND CORRECTIONAL
 OCCUPANCIES ARE PROTECTED BY AUTOMATIC SPRINKLERS IN
 ACCORDANCE WITH 22.3.2
  
 NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING
 SYSTEMS AND EQUIPMENT
  
 5.2.5 SERVICE OPENING ROOMS.
 5.2.5.1 GENERAL.
 5.2.5.1.1 EVERY SERVICE OPENING SHALL BE IN A ROOM OR
 COMPARTMENT THAT IS SEPARATED FROM THE OTHER PARTS OF
 THE BUILDING BY WALLS, PARTITIONS, FLOORS, AND
 FLOOR-CEILING ASSEMBLIES HAVING A FIRE RESISTANCE
 RATING OF NOT LESS THAN THE REQUIRED RATING OF
 THE CHUTE ENCLOSURE.
 5.2.5.1.2 WHERE SERVICE OPENING ROOMS ARE PROTECTED BY
 AUTOMATIC SPRINKLERS, THE ROOM SHALL BE ENCLOSED IN A
 MINIMUM OF 1-HOUR CONSTRUCTION, AND OPENINGS SHALL BE
 PROTECTED WITH 3?4-HOUR FIRE-RATED DOORS.
 5.2.5.1.3 OPENINGS INTO SUCH A ROOM OR COMPARTMENT
 SHALL BE PROTECTED BY APPROVED SELF-CLOSING DOORS THAT
 ARE APPROPRIATE FOR PROTECTING THE OPENINGS OR ARE OF
 NOT LESS THAN A 1?HOUR PARTITION RATING WITH A 3?4-HOUR
 FIRE-RATED DOOR.
 5.2.5.1.4 THE SIZE OF THE SERVICE OPENING ROOM OR
 COMPARTMENT SHALL NOT BE LESS THAN THAT REQUIRED TO
 MAINTAIN A MINIMUM 152.4 MM (6 IN.) CLEARANCE BETWEEN
 THE INTAKE OPENING AND THE CLOSED SERVICE OPENING ROOM
 DOOR.
  
 PLEASE PROVIDE PROTECTION AS REQUIRED FOR ALL WALLS
 SURROUNDING THE LAUNDRY CHUTE ROOM, INCLUDING THE
 CORRIDOR WALL AND JANITOR/MECHANICAL ROOMS.
  
  
  
 9) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT
 INCLUDES A LAUNDRY CHUTE. THE DOOR TO THE LAUNDRY CHUTE
 ROOM; 8, AND MECHANICAL ROOM; 10, ARE NOT INDICATED AS
 HAVING ANY RATING OR CLSING DEVICES PER DOOR SCHEDULE
 SHHET A 9.02.
  
 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING
 SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH
 SECTION 8.7.
  
 8.7.1.3 DOORS IN BARRIERS REQUIRED TO HAVE A FIRE
 RESISTANCE RATING SHALL HAVE A MINIMUM ?-HOUR FIRE
 PROTECTION RATING AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8.
  
 PLEASE PROVIDE FOR THE DOOR REQUIREMENTS.
  
  
  
 10) SHEET A 6.05 & A 2.02 - A 2.04 - THE LINEN CHUTE
 CHASE DOES NOT INDICATE AND FIRE RATING.
  
 NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING
 SYSTEMS AND EQUIPMENT
  
 5.2.3 CHUTE ENCLOSURE (CHASE).
 5.2.3.1 GENERAL.
 5.2.3.1.1 VERTICAL WASTE OR LINEN CHUTES IN ALL STORIES
 ABOVE THE STORAGE OR COMPACTING ROOM SHALL BE ENCLOSED
 WITHIN A CONTINUOUS FIRE-RATED ENCLOSURE CONSISTENT
 WITH THE CONSTRUCTION TYPE.
 5.2.3.1.2 THE WALLS OF THE ENCLOSURE SHALL HAVE A FIRE
 RESISTANCE RATING OF NOT LESS THAN 2 HOURS IF THE
 BUILDING IS FOUR OR MORE STORIES IN HEIGHT AND NOT LESS
 THAN 1 HOUR IF THE BUILDING IS LESS THAN FOUR STORIES
 IN HEIGHT.
 5.2.3.1.3 OPENINGS IN THE FIRE-RATED ENCLOSURE SHALL BE
 AS FOLLOWS:
 (1) 11?2-HOUR FIRE RESISTANCE RATING FOR 2 HOUR?RATED
 ENCLOSURES
 (2) 1-HOUR FIRE RESISTANCE RATING FOR 1 HOUR?RATED
 ENCLOSURES
  
 PLEASE PROVIDE THE INDICATED FIRE RATED PROTECTION.
  
  
  
 11) SHEET B - THE LAUNDRY CHUTE DISCHARPE ROOM DOES NOT
 INDICATED AN FIRE RATING.
  
 NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING
 SYSTEMS AND EQUIPMENT
  
 5.2.4 CHUTE DISCHARGE ROOMS.
 5.2.4.1 GENERAL.
 5.2.4.1.1 WASTE AND LINEN CHUTES SHALL TERMINATE OR
 DISCHARGE DIRECTLY INTO A ROOM HAVING A MINIMUM FIRE
 RESISTANCE RATING NOT LESS THAN THAT SPECIFIED FOR THE
 CHUTE.
 5.2.4.1.2 OPENINGS INTO SUCH A ROOM OR COMPARTMENT
 SHALL BE PROTECTED BY APPROVED SELF-CLOSING FIRE DOORS
 HAVING A MINIMUM FIRE PROTECTION RATING NOT LESS THAN
 SPECIFIED FOR THE CHUTE.
  
 PLEASE PROVIDE FIRE RATING AS REQUIRED.
  
  
  
 12) SHEETS A 2.02 - 2.03 - THE H.K. ROOM APPEARS TO
 HAVE A TRASH RECEPTICLE LOCATED WITHIN IT. THE ROOM CAN
 BE USED FOR STORAGE BUT IT CAN NOT BE USED AS A TRASH
 ROOM.
  
 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING
 SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH
 SECTION 8.7.
 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4
 SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE
 FOLLOWING:
 (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED
 SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED
 SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN
 TO A CORRIDOR OR NORMALLY OCCUPIED SPACE.
 (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE
 PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37
 M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM
 IS PROTECTED BY AUTOMATIC SPRINKLERS.
  
 FOR PURPOSES OF IDENTIFYING STORAGE:
 3.3.188.15* STORAGE OCCUPANCY. AN OCCUPANCY USED
 PRIMARILY FOR THE STORAGE OR SHELTERING OF GOODS,
 MERCHANDISE, PRODUCTS, OR VEHICLES.
  
 PER (2), THE ROOM CAN BE USED FOR STORAGE PURPOSES.
 TRASH IS NOT CONSIDERED AS ALLOWABLE WITHIN THIS ROOM.
  
  
  
 13) SHEET A 2.04 - THE H.K. ROOM IS INDICATED AS HAVING
 A MECHANICAL ROOM; SHEET E 1.03 INDICATES IT AS A
 BOILER ROOM, WITH WHAT APPEARS TO BE WATER HEATERS. THE
 H.K. ROOM IS DIFFERENT THAN ALL OTHER FLOORS LEVELS.
 PLEASE CONFIRM AND PROVIDE CLARIFYING NARRATIVE.
  
 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING
 SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH
 SECTION 8.7.
 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4
 SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE
 FOLLOWING:
 (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED
 SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED
 SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN
 TO A CORRIDOR OR NORMALLY OCCUPIED SPACE.
 (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE
 PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37
 M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM
 IS PROTECTED BY AUTOMATIC SPRINKLERS.
  
 A. PER (2), THE ROOM CAN BE USED FOR STORAGE PURPOSES.
 WATER HEATERS ARE NOT CONSIDERED AS ALLOWABLE WITHIN
 THIS ROOM.
 B. HOW WILL THE WATER HEATERS BE POWERED?
 C. WHERE IS THE TRASH RECEPTICLE LOCATED ON THIS FLOOR.
  
  
  
  
 14) SHEETS FP 2.01 - 2.03 - THE ROOMS INDICATED AS
 SUANA ARE NOT PROVIDED WITH FIRE SPRINKLER PROTECTION.
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 LEVEL OF PROTECTION. A BUILDING, WHERE PROTECTED BY
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLATION, SHALL BE
 PROVIDED WITH SPRINKLERS IN ALL AREAS EXCEPT WHERE
 SPECIFIC SECTIONS OF THIS STANDARD PERMIT THE OMISSION
 OF SPRINKLERS.
  
 THERE IS NO OMISSION OF SPRINKLERS FOR THIS ROOM.
  
 PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION.
  
  
  
  
 15) COMMENT # 6 RESTATED FOR SHEETS FP - THE IS NO
 INDICATIONS OF FIRE PROTECTION OF THE VERITCAL OPENINGS
 ALONG THE WEST SIDE AND FLOORS 2-5 OPENING IN THE NORTH
 INTRERIOR AREA.
  
 28.3 PROTECTION.
 28.3.1 PROTECTION OF VERTICAL OPENINGS.
 28.3.1.1 VERTICAL OPENINGS SHALL COMPLY WITH 28.3.1.1.1
 THROUGH 28.3.1.2.
 28.3.1.1.1 VERTICAL OPENINGS SHALL BE ENCLOSED OR
 PROTECTED IN ACCORDANCE WITH SECTION 8.6.
 28.3.1.1.2 VERTICAL OPENINGS IN ACCORDANCE WITH 8.6.9.1
 SHALL BE PERMITTED.
 28.3.1.1.3 IN BUILDINGS, OTHER THAN HIGH-RISE
 BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 28.3.5, THE WALLS ENCLOSING VERTICAL
 OPENINGS SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE
 RATING, AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE
 PROTECTION RATING.
  
 8.6 VERTICAL OPENINGS.
 8.6.1 FLOOR SMOKE BARRIERS. EVERY FLOOR THAT SEPARATES
 STORIES IN A BUILDING SHALL MEET THE FOLLOWING
 CRITERIA:
 (1) IT SHALL BE CONSTRUCTED AS A SMOKE BARRIER IN
 ACCORDANCE WITH SECTION 8.5.
 (2) IT SHALL BE PERMITTED TO HAVE OPENINGS AS DESCRIBED
 BY 8.6.6, 8.6.7, 8.6.8, 8.6.9, OR CHAPTERS 11 THROUGH
 43. 8.6.2* CONTINUITY. OPENINGS THROUGH FLOORS SHALL BE
 ENCLOSED WITH FIRE BARRIER WALLS, SHALL BE CONTINUOUS
 FROM FLOOR TO FLOOR, OR FLOOR TO ROOF, AND SHALL BE
 PROTECTED AS APPROPRIATE FOR THE FIRE RESISTANCE RATING
 OF THE BARRIER.
  
 PLEASE PROVIDE THE REQUIRED PROTECTION AS INDICATED.
  
  
  
 16) SHEET FP 1.04 - A ROOF MANIFOLD IS INDICATED ON THE
 NORTH WEST SIDE OF THE ROOF. THE IS INSUFFICIENT AREA
 IN FRONT OF THE MANIFOLD TO ALLOW FOR FIRE OPERATIONS.
  
 13.1.3 OBSTRUCTIONS SHALL NOT BE PLACED OR KEPT NEAR
 FIRE HYDRANTS, FIRE DEPARTMENT INLET CONNECTIONS, OR
 FIRE PROTECTION SYSTEM CONTROL VALVES IN A MANNER THAT
 WOULD PREVENT SUCH EQUIPMENT OR FIRE HYDRANTS FROM
 BEING IMMEDIATELY VISIBLE AND ACCESSIBLE.
 13.1.4 A MINIMUM 36 IN. (91 MM) OF CLEAR SPACE SHALL BE
 MAINTAINED TO PERMIT ACCESS TO AND OPERATION OF FIRE
 PROTECTION EQUIPMENT, FIRE DEPARTMENT INLET
 CONNECTIONS, OR FIRE PROTECTION SYSTEM CONTROL VALVES.
 THE FIRE DEPARTMENT SHALL NOT BE DETERRED OR HINDERED
 FROM GAINING IMMEDIATE ACCESS TO FIRE PROTECTION
 EQUIPMENT.
 13.1.4.1 AN APPROVED CLEAR AND UNOBSTRUCTED PATH SHALL
 BE PROVIDED AND MAINTAINED FOR ACCESS TO THE FIRE
 DEPARTMENT INLET CONNECTIONS.
  
 PLEASE PROVIDE FOR THE MINMIMUM REQUIREMENT BY
 REPOSITIONING, TURNING, RELOCATION OTHER OTHER SIMILAR
 REMEDY.
  
  
  
 17) ROOF SHEETS - THE ROOF IS INDICATED WITH A SPACE
 THAT IS OPEN TO THE 2ND FLLOR BELOW. FOR FIREFIGHTER
 FIRE OPERATIONAL SAFETY, THOUGH THIS OPENING APPEARS TO
 HAVE A PARAPET WALL, PLEASE PROVIDE REFLECTIVE SIGNAGE
 ON ALL FOUR SIDES "DANGER, OPENING THROUGH TO 2ND
 FLOOR" OR SIMILAR.
  
  
  
 18) ROOF SHEETS - THERE IS A PARAPET WALL INDICATED ON
 THE EAST AND WEST SIDES WITH OPEN TRELLIS CONSTRUCTION
 ON THE OTHER SIDE. FOR FIREFIGHTER FIRE OPERATIONAL
 SAFETY, PLEASE PROVIDE REFLECTIVE SIGNAGE, "DANGER,
 OPEN TRELLS BEAMS ON OTHER SIDE" OR SIMILAR IN MULTIPLE
 LOCATIONS.
  
  
  
 19) SHEET A 2.01A & A 9.02 - GATE DOORS AND GATES ARE
 INDICATED ON THE PERIMETER OF THE BUILDING SITE. THESE
 GATES ARE LOCATED IN THE EGRESS PATH OF TRAVEL. THE
 DOOR SCHEDULE INDICATES THERE ARE LOCKED. THESE GATES
 SHALL IMPEDE EGRESS AND SHALL COMPLY WITH NFPA
 101,CHAPTER 28 & CHAPTER 7, MEANS OF EGRESS
  
 28.2.2.2 DOORS.
 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH
 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR
 28.2.2.2.2.4.
 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE
 LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER
 EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE
 LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18
 THROUGH 23.
  
 PLEASE PROVIDE LOCKS/LATCHES IN COMPLIANCE WITH THE
 REQUIRMENT.
  
  
  
 20) SHEET A 8.02 - A GREEN SCREEN PANEL IS INDICATED ON
 THE WEST OUTSIDE WALL ATTACHED TO AN ALUMINUM
 STRUCTURE.
  
 PLEASE PROVIDE THE SCREEN FABRIC SPECIFICATION SHEET
 THAT INDICATES ANY FLAME AND SMOKE SPREAD RATING, FIRE
 RATINGS, FIRE PROTECTION FEATURES, ETC.
  
  
  
 21) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-11-02 Cont ID  
Sent By gjohnson Date 2016-11-02 Time 15:07 Rev Time 0.00
Received By gjohnson Date 2016-11-02 Time 15:07 Sent To  
Notes
2016-11-02 15:20:18GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 GAS COMMENTS:
  
 1. IDENTIFY THE TYPE PIPING. UNDER SUMMERY IT SAID SEE
 RISER BUT THERE IS NOTHING ON THE RISER. WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
  
 2. IDENTIFY TYPE OF GAS SUMMERY SAID UTILITIES THIS IS
 NOT A TYPE OF GAS. WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. SHOW DIRT-LEG AT APPLIANCE. PER FBC FUEL GAS 408.4
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-21 Cont ID  
Sent By lmarchan Date 2017-03-21 Time 09:41 Rev Time 0.00
Received By lmarchan Date 2016-10-14 Time 16:30 Sent To  
Notes
2016-10-14 16:30:46C32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By cpuell Date 2016-10-03 Time 15:34 Rev Time 0.00
Received By cpuell Date 2016-07-21 Time 13:33 Sent To  
Notes
2016-07-21 13:33:42C32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-11-08 Cont ID  
Sent By jwitmer Date 2016-11-08 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2016-11-08 Time   Sent To  
Notes
2016-11-08 09:34:20BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By jwitmer Date 2016-08-09 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2016-08-07 Time 05:58 Sent To  
Notes
2016-08-09 15:45:48BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-24 Cont ID  
Sent By ccole Date 2016-10-24 Time 11:57 Rev Time 0.00
Received By ccole Date 2016-10-24 Time 11:57 Sent To  
Notes
2016-10-24 12:20:052ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070837
 10/24/16
  
 1) SHEET M-100: REFER TO TABLE 6-4 ASHRAE 62.1-2010 AND
 PROVIDE EXHAUST VENTILATION AND CALCULATIONS FOR THE
 SOILED LINEN STORAGE ROOM. THIS REQUIREMENT WAS MISSED
 IN THE FIRST REVIEW DUE TO THE ROOMS NOT IDENTIFIED ON
 THE MECHANICAL PLANS. PLEASE IDENTIFY ALL ROOMS ON ALL
 FLOORS OF THE BUILDING.
  
 2) M3.01: PLEASE INCLUDE THE BOH ROOM IN THE
 VENTILATION CALCULATIONS.
  
 3) M1.01: PROVIDE A MOTORIZED DAMPER FOR THE 12X10 O/A
 INTAKE DUCT TO FCU-B.
  
 4) FCU-B HEATING CAPACITY AT 12 KW IS UNDERSIZED PER
 THE CALCS WHCIH INDICATE A 16.5 KW LOAD.
  
 5 ) PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR ALL THE
 REQUIRED WALL AND CEILING FIRE DAMPERS, AND PROVIDE
 INSTALLTION DETAILS ON THE PLANS.
  
 6) IN REFERENCE TO COMMENT #4 REQUESTING SPECS FOR THE
 DRYER, PLEASE NOTE THAT THE LENGTH OF EXHAUST RUN
 APPEARS TO EXCEED THE 35 FT. MAXIMUM LENGTH PER SECTION
 504.6.4.1. THE MANUFACTURERS SPECIFICATIONS MUST
 INDICATE THIS MAXIMUM LENGTH CAN BE EXCEEDED.
  
 7) LABEL THE ACCESS PANELS TO THE FCU'S OR PROVIDE A
 GENERAL NOTE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-29 Cont ID  
Sent By ccole Date 2016-07-29 Time 15:15 Rev Time 0.00
Received By ccole Date 2016-07-29 Time 15:10 Sent To  
Notes
2016-07-29 15:53:221ST REVIEW MECHANICAL- FBC-2014
 PERMIT #16070837
 7/29/16
  
 1) SHEETS A2.01A & M1.01: THE PLANS APPEAR TO INDICATE
 AN ENCLOSED PARKING GARAGE WHICH IS REQUIRED TO HAVE AN
 EXHAUST VENTILATION SYSTEM PER SECTION 406.6.2 FBC-14
 BUILDING. PROVIDE A SYSTEM DESIGNED IN ACCORDANCE WITH
 SECTION 404.1, 404.2, & 404.3.FBC-14 MECHANICAL.
  
 2) A2.01A: PROVIDE AN EXHAUST SYSTEM FOR THE TRASH ROOM
 PER TABLE 6-4 ASHRAE 62.1-2010.
  
 3) A2.01B: THE PLAN INDICATES A MECHANICAL ROOM IN THE
 BASEMENT. PLEASE SHOW ALL EQUIPMENT AND PROVIDE
 EQUIPMENT LISTS AND SCHEDULES.
  
 4) M-1.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYER WITH REVIEW SIGNATURE BY THE ENGINEER OF RECORD.
  
 5) M-1.00 & M-1.01: CLARIFY WHERE THE AIR INLET OPENING
 IS LOCATED FOR THE FCU-A OUTDOOR AIR DUCT.
  
 6) M-1.01: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF FCU-B- SECTION 606.2.1.
  
 7) M-1.01: THE 24X48 RETURN GRILL APPEARS UNDERSIZED
 FOR THE 3440 CFMS (ADJUSTED TO 2992 CFMS USING
 PERCENTAGE OF OUTDOOR AIR) OF SUPPLY AIR SHOWN ON THE
 PLAN. THE INDUSTRY STANDARD IS TYPICALLY 200 SQ. INCHES
 PER TON.
  
 8) M-3.01: REFER TO SECTION C404.2.2 FBC-14 ENERGY
 CONSERVATION: THE COOLING AND HEATING OUTPUT CAPACITIES
 OF FCU-B EXCEED THE SYSTEM SUMMARY LOADS CALCULATED BY
 THE EOR.
  
 9) M-3.01:THE COOLING AND HEATING CAPACITIES OF FCU-1 &
 FCU-2 EXCEED THE SYSTEM SUMMARY LOADS CALCULATED FOR
 2ND, 3RD, AND 4TH FLOOR SUITES. A) THE HEATING
 CAPACITIES OF FCU-1 & FCU-2 EXCEED THE SYSTEM SUMMARY
 LOADS CALCULATED FOR THE 5TH FLOOR SUITES- SECTION
 C404.2.2.
  
 10) M-3.01: THE AC UNIT SCHEDULE DOES NOT LIST THE
 TOTAL CFMS OF SUPPLY AIR FOR FCU-1 & FCU-2.
  
 11 ) M-2.01: PLEASE LABEL THE AC SYSTEMS AS EITHER
 FCU-1 OR 2.
  
 12) M-2.01: THE RETURN AIR GRILLS APPEAR UNDERSIZED FOR
 THE AMOUNT OF SUPPLY AIR FOR EACH SYSTEM, WITH
 ADJUSTMENT FACTOR FOR OUTDOOR AIR. THE INDUSTRY
 STANDARD IS TYPICALLY 200 SQ. INCHES PER TON.
  
 13) M-2.01: MOTORIZED DAMPERS ARE REQUIRED FOR THE
 OUTDOOR AIR SUPPLY TO THE GUEST SUITE SYSTEMS- SECTION
 C403.2.4.4.
  
 14) M-3.01: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR THE JANITOR AND STORAGE ROOMS- TABLE 403.3.
  
 15) M-3.01: A VENTILATION RATE OF 0.48 CFMS PER SQ. FT.
 IS REQUIRED FOR SWIMMING POOLS AND POOL DECK AREAS PER
 TABLE 403.3, HOWEVER IT APPEARS THAT THE POOLS ARE OPEN
 PARTIALLY ON ONE SIDE TO THE OUTDOORS. PLEASE PROVIDE A
 CALCULATION FOR NATURAL VENTILATION IF APPLICABLE.
  
 16) M-4.01, REFRIGERANT PIPING RISERS: PLEASE INDICATE
 THE TYPE OF PIPING, PIPE SIZES, AND THE LENGTHS OF THE
 PIPING RUNS. VERIFY COMPLIANCE WITH MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS.
  
 17) M-4.02: PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING
 FOR ALL ROOFTOP MECHANICAL EQUIPMENT INCLUDING CU-A & B
 WHICH ARE NOT SHOWN IN THE DRAWING- SECTION 301.15.
 SUBMIT NOA #15-0902.05 WITH SHOP DRAWING APPROVAL
 SIGNATURE BY THE EOR.
  
 18) PROVIDE A SUBMITTAL PACKAGE FOR MECHANICAL
 EQUIPMENT THAT INCLUDING BUT NOT LIMITED TO THE AC
 SYSTEMS, MOTORIZED DAMPERS, DUCT SMOKE DETECTORS, FIRE
 DAMPERS, THE WATER HEATERS AND FLUE EXHAUST/AIR INTAKE
 DUCTS, LOUVERS ETC. PLEASE NOTE A FLORIDA PRODUCT
 APPROVAL AND/OR A MIAMI-DADE NOA MUST BE SUBMITTED FOR
 THE LOUVERS SHOWN AT THE JANITOR'S CLOSETS.
  
 19) PLEASE INDICATE THE LOCATIONS OF THE POOL HEATERS
 AND PROVIDE EQUIPMENT SCHEDULES AND MANUFACTURER'S
 SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-02 Cont ID  
Sent By gjohnson Date 2016-11-02 Time 12:53 Rev Time 0.00
Received By gjohnson Date 2016-10-29 Time 13:28 Sent To  
Notes
2016-11-02 13:23:441)2ND REQUEST THE CIVIL DRAWINGS ARE NOT SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE
 61G15-23.001. IT APPEARS THE CIVIL PAGES WHERE STAMPED
 BUT THEY MUST BE PERSONALLY SIGNED AND DATED
  
  
 19) 2ND REQUEST THE SEAT IN THE ACCESSIBLE SHOWER SHALL
 COMPLY WITH THE FAC SEC. 610.3. SUBMIT DETAILS. THE
 SEAT SHALL BE OF A FOLDING TYPE.
 SEAT SHOWN AT 15" SHOW COMPLIANCE WITH FBC ACC
 610.3 SHOWER COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
  
 20) 2ND REQUEST THE WET BAR/SINK IN THE HANDICAPPED
 ACCESSIBLE UNIT SHALL COMPLY WITH THE FAC SECS.212.2,
 606. NO ACCESSIBILITY SHOWN FOR SINK
  
 24) 2ND REQUEST THE SHOWER CONTROLS IN THE ACCESSIBLE
 SHOWER SHALL COMPLY WITH THE FAC SECS.608.5.3.SHOW THE
 DISTANCE OF THE CONTROLS IN RELATION TO THE SEAT, FROM
 ADJACENT WALLS, ABOVE THE FLOOR, ETC.
 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND
 SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL
 ADJACENT TO THE SEAT WALL AND SHALL BE LOCATED 27
 INCHES (685 MM) MAXIMUM FROM THE SEAT WALL ABOVE THE
 GRAB BAR, BUT NO HIGHER THAN 48 INCHES.
  
 26) 2ND REQUEST SHT. A8.11 DETAIL #5 REFERENCES THE
 2010 FBC /FHA. THESE DETAILS DO NOT APPLY. THE CODE IN
 EFFECT IS THE 2014 FBC-ACCESSIBILITY.
  
 29) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE
 SUBMIT SPECIFICATIONS FOR THE PUMPS FOR THE LAUNDRY.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 30) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE
 SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE GAS WATER
 HEATERS. SUBMIT VENT DETAILS (SIZE, TYPE OF PIPE,
 ETC.).COMPLY WITH FGC SEC.502, 503, 504.
  
 31) 2ND REQUEST COULD NOT LOCATE ON MECHANICAL PAGES
 SUBMIT CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE
 WITH THE 2014 FBC-GAS SEC.304.
  
 32) 2ND REQUEST NOT COMPLIED SHOW THE DISTANCE OF THE
 GAS WATER HEATER VENTS FROM BUILDING OPENINGS. COMPLY
 WITH FGC SEC. 503.6.4.
  
 33) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE
 SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE DRYERS.
 SUBMIT VENT DETAILS (SIZE, TYPE OF MATERIAL,
 TERMINATION POINTS, ETC.).
  
 34) 2ND REQUEST COULD NOT LOCATE ON MECHANICAL PAGES
 CARBON MONOXIDE SENSORS ARE REQUIRED PER THE 2014 FBC
 SEC. 908.7.
  
 NEW COMMENTS:
  
 1. SHT. A7.02 THE ROLL IN SHOWER SHALL BE MIN 30" X 60"
 PER FBC ACC SEC 608.2.2
  
 2. SHT 7.02 SHOW CLEAR FLOOR SPACE FOR ROLL IN SHOWER.
 PER FBC ACC 608.2.2.1
  
 3. THE ACCESSIBLE SUITE #2 ON THE 2ND FLOOR IS SHOWN AS
 A STANDARD ROOM ON THE PLUMBING SHEETS PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. ON THE PLUMBING SHEETS IT SHOWS A SINK INSIDE THE
 SAUNA ON SHT, A7.02 IT SHOWS A SAUNA HEATER PLEASE
 CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 5. MODEL PS-15-B LINT TRAP IS EQUIPPED WITH A 2" INLET
 AND OUTLET YOU WILL BE REQUIRED TO USE A MODEL THAT IS
 EQUIPPED WITH A 3" INLET AND OUTLET THE DRAIN FROM THE
 LAUNDRY IS REQUIRED TO-BE 3' AND YOU CAN NOT REDUCE THE
 PIPE SIZE IN THE DIRECTION OF FLOW. PER FBC PL 406.2 /
 704.2
  
 6. THE PLUMBING SCHEDULE SHOWS P-3 AS A TUB AND IT
 SHOWS P-4 AS A SHOWER ON THE FLOOR PLAN AND THE RISER
 THE SHOWER IS SHOWN AS A P-3 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 7. THE VENT FOR THE HUB DRAIN IN THE TRASH ROOM THAT IS
 TERMINATING OUT OF THE SIDE WALL SHALL COMPLY WITH FBC
 PL903.5 / 903.6
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-22 Cont ID  
Sent By tklarge Date 2016-08-22 Time 09:24 Rev Time 0.00
Received By tklarge Date 2016-08-18 Time 09:12 Sent To  
Notes
2016-08-22 04:50:511) THE CIVIL DRAWINGS ARE NOT SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE 61G15-23.001.
 2) SEPARATE PLANS/SPECIFICATIONS AND PERMIT WILL BE
 REQUIRED FOR THE BACKFLOW PREVENTERS.
 3) THE HUB DRAIN RECEIVING THE DISCHARGE FROM THE
 ELEVATOR SUMP SHALL BE EQUIPPED WITH A FLOOR DRAIN.
 2014 FPC SEC. 1002.4.
 4) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) SUBMIT A DETAIL FOR THE " CONCRETE SHOWER PAN" AT
 THE TERRACE REFERENCED ON THE ARCHITECTURAL SHEETS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT A DETAIL FOR THE "PLENUM DRAINAGE" REFERENCED
 ON THE PLANS.
 7) SHT.A2.05 - IDENTIFY THE PARAMETERS OF THE
 INDIVIDUAL ROOF AREAS A-D.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SHT. A2.05 - CALLS OUT 8 INCH BY 4 INCH SCUPPERS AND
 SHT. P1.05 SHOWS 6 INCH BY 4 INCH. CLARIFY.
 9) ROOF DRAINS #2 & #3 APPEAR TO BE MISSING EMERGENCY
 OVERFLOW DRAINS/SCUPPERS. SHOW THE LOCATION OF THE
 OVERFLOW DRAINS ON THE PLAINS.2014 FPC SEC. 1108.
 10) SUBMIT ROOF DRAINAGE CALCULATIONS THAT SHOW THAT
 ONE-HALF THE AREA OF ALL VERTICAL WALLS THAT DIVERT
 RAINWATER TO THE ROOF HAS BEEN ADDED TO THE PROJECTED
 ROOF AREA FOR THE REQUIRED SIZING OF THE VERTICAL
 CONDUCTORS, LEADERS AND HORIZONTAL STORM DRAINAGE
 PIPING. FPC SEC.1106.4.
 11) PROVIDE OVERFLOW STORM DRAIN DETAILS FOR STAIR
 TOWERS #1 & #2. FPC SEC. 1108.
 12) SUBMIT DETAILS FOR THE SCUPPERS AND OVERFLOW
 SCUPPERS. COMPLY WITH 2014 FBC SEC.1503.4.2.
 13) SHT. A7.01 & A8.11 - AS AN FYI, FLORIDA DOES NOT
 ENFORCE THE ADA. FLORIDA HAS ITS OWN ACCESSIBILITY CODE
 AND CAN BE FOUND IN THE 2014 (5TH EDITION) OF THE
 FLORIDA BUILDING CODE, NOT THE 2010 EDITION. ALL
 HANDICAPPED ITEMS SHALL COMPLY WITH THE FBC.
 14) COAT HOOKS AND TOWEL BARS SHALL COMPLY AND BE
 LOCATED WITHIN THE REACH RANGES MANDATED IN SECS.
 213.3.7, 308.2.1, 308.3.2, 604.8.3, 603.4.
 15) GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR
 TO THE TOP OF THE GRIPPING SURFACE PER THE FAC SEC.
 609.4.
 16) THE TOILET PAPER DISPENSER SHALL BE LOCATED IN
 ACCORDANCE WITH THE FAC SEC. 604.7.
 17) WHERE ARE THE REQUIRED DRINKING FOUNTAINS ON THE
 GROUND FLOOR? COMPLY WITH THE 2014 FPC TABLE 403.1. A
 MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED IN
 ACCORDANCE WITH 2014 FPC TABLE 403.1, FOOTNOTE # (E)
 AND THE FAC SEC. 211.2, 602.4, 602.7.
 18) SHT. A7.02 - DETAIL #1 -THE CLEAR FLOOR SPACE FOR
 THE WATER CLOSET SHALL COMPLY WITH THE FAC SEC.604.3.
 SHOW THIS ON THE PLAN.
 19) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH
 THE FAC SEC. 610.3. SUBMIT DETAILS. THE SEAT SHALL BE
 OF A FOLDING TYPE.
 20) THE WET BAR/SINK IN THE HANDICAPPED ACCESSIBLE UNIT
 SHALL COMPLY WITH THE FAC SECS.212.2, 606.
 21) SUBMIT SPECIFICATIONS FOR THE "STEAM SHOWER." IS
 THIS A SAUNA ALSO? THE STEAM SHOWER IN THE ACCESSIBLE
 UNIT SHALL COMPLY WITH FAC SECS. 241, 302, 404.2 & 612.
 SUBMIT AN ENLARGED FLOOR PLAN FOR THIS SHOWER.
 22) THE POOL IN THE ACCESSIBLE SUITE SHALL COMPLY WITH
 2014 FAC SEC. 242.
 23) SHT. A7.02 - THE ACCESSIBLE LAVATORY SHALL BE
 DESIGNED FOR A FORWARD APPROACH. FAC SECS. 213.3.4 &
 606.
 24) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWER SHALL
 COMPLY WITH THE FAC SECS.608.5.3.SHOW THE DISTANCE OF
 THE CONTROLS IN RELATION TO THE SEAT, FROM ADJACENT
 WALLS, ABOVE THE FLOOR, ETC.
 25) SHT. A7.02 REFERS TO FAIR HOUSING REQS. THIS
 PROJECT DOES FALL UNDER THE PURVIEW OF THE FAIR HOUSING
 ACT. REVISE NOTE TO READ 2014 FBC-ACCESSIBILITY VOLUME.
 26) SHT. A8.11 REFERENCES THE 2010 FBC /FHA. THESE
 DETAILS DO NOT APPLY. THE CODE IN EFFECT IS THE 2014
 FBC-ACCESSIBILITY.
 27) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE LAUNDRY INTERCEPTOR. 2014 FBC SEC. 1003.2.
 28) THE CONNECTION OF THE LAUNDRY SUMP DRAIN TO THE
 SANITARY SYSTEM SHALL COMPLY WITH FPC SEC. 712.3.5.
 29) SUBMIT SPECIFICATIONS FOR THE PUMPS FOR THE
 LAUNDRY. WPB AMEND. TO FBC SEC. 107.2.1.
 30) SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE GAS
 WATER HEATERS. SUBMIT VENT DETAILS (SIZE, TYPE OF PIPE,
 ETC.).COMPLY WITH FGC SEC.502, 503, 504.
 31) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN
 ACCORDANCE WITH THE 2014 FBC-GAS SEC.304.
 32) SHOW THE DISTANCE OF THE GAS WATER HEATER VENTS
 FROM BUILDING OPENINGS. COMPLY WITH FGC SEC. 503.6.4.
 33) SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE
 DRYERS. SUBMIT VENT DETAILS (SIZE, TYPE OF MATERIAL,
 TERMINATION POINTS, ETC.).
 34) CARBON MONOXIDE SENSORS ARE REQUIRED PER THE 2014
 FBC SEC. 908.7.
 35) SEPARATE PERMITS ARE REQUIRED FOR THE SWIMMING
 POOLS.
 36) SHT. P3.02 - SIZE THE IRRIGATION BRANCHES ON THE
 RISER.
 37) SHT. P3.02 - COLD WATER RISERS SHALL HAVE SHUTOFF
 VALVES PER FPC SEC.606.1. SEE RISER CW /1 WHICH
 SUPPLIES FIXTURE P-6.
 38) SHUT OFF VALVES ARE REQD. ON THE WATER SUPPLIES TO
 FIXTURE P-7 IN THE BASEMENT. FPC SEC. 606.1 (5).
 39) SHT. P3.03 - SHOWS RISER S/2 FOR FIXTURE P-4 & SHT.
 P1.02 SHOWS RISER S/2 FOR P-3. CLARIFY.
 40) SHT. P1.02 SHOWS RISER S/3 FOR FIXTURE P-4 AND SHT.
 P3.03 SHOWS FIXTURE P-3. CLARIFY.
 41) SHT. P3.04 - SIZE THE VENT FOR THE HUB DRAIN AND
 SHOW THE CONTINUATION/TERMINATION POINT OF THE VENT.
 WPB AMEND. TO FBC SEC. 107.2.1.
 42) SHT. P3.04 - SIZE THE FORCE MAIN FROM THE SANITARY
 EJECTOR ON THE RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 43) SHT. P1.01 APPEARS TO SHOW A 2 INCH FORCE MAIN
 INSIDE STAIR FS-1. PENETRATIONS OTHER THAN THOSE
 NECESSARY FOR THE PURPOSE OF THE EXIT ACCESS STAIRWAY
 ENCLOSURE ARE PROHIBITED PER THE 2014 FBC
 SEC.1009.3.1.5.1.
 44) SHT. P4.01 - INDICATE THE SIZE OF THE EXPANSION FOR
 THE WATER HEATERS.
 45) SHT.P4.01 - WATER HEATER DETAIL - PAN DRAINS ARE
 REQUIRED FOR THE WATER HEATERS. DRAINS SHALL COMPLY
 WITH FPC SEC.504.7.1 & 504.7.2.
 46)SHT. P4.01 - A FULL OPEN VALVE SHALL BE INSTALLED ON
 THE WATER HEATERS. 2014 FPC SEC.606.1 (8).
 47)SHT. P3.05 SHOWS A ONE HALF-INCH DISCHARGE LINE FROM
 THE STORM SUMP. THIS IS OBVIOUSLY A TYPOGRAPHICAL
 ERROR. PLEASE CORRECT.
 48)INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAINAGE
 PIPING ON THE PLANS. COMPLY WITH TABLE 1106.3 OF THE
 FPC.
 49)SHT. P3.05 - THERE ARE ROOF DRAINS THAT DO NOT SHOW
 THE SQUARE FOOTAGE BEING DRAINED. CLARIFY.
 50)SHT. P3.05 - THE SQUARE FOOTAGE BEING DRAINED BY
 EACH DRAIN IS LABELED AS ?FU?. PLEASE CORRECT.
 51)SHOW THE LOCATION OF THE POOL HEATERS ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 52)SHT.A.201B SHOWS A MECHANICAL ROOM. SUPPLY
 INFORMATION AS TO WHAT TYPE OF EQUIPMENT WILL BE
 LOCATED IN THIS ROOM AND PROVIDE AN EQUIPMENT SCHEDULE.
 WPB AMEND. TO FBC SEC. 107.2.1.
 53) INDICATE ON THE PLANS WHAT TYPE OF MATERIALS/ITEMS
 WILL BE PLACED IN THE STORAGE ROOM.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-11-08 Cont ID  
Sent By jwitmer Date 2016-11-08 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2016-11-08 Time 15:12 Sent To  
Notes
2016-11-08 15:15:36ROOFING PLAN REVIEW
 W. P. B. PERMIT: 16070837
 ADD: 309/317 N. ROSEMARY AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-456-7252
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SUN. AUGUST 07/2016
 ACTION: DEFERRED SUBMITTAL 107.3.4.2.
 .(2) ROOFING APPROVALS WERE SUBMITTED FOR THIS REVIEW.
 CARLISLE MIRASEAL FLUID APPLIED WATERPROOFING MEMBRANE
 NOA 13-0129.22
 CARLISLE CCW-500-R HOT APPLIED LIQUID MEMBRANE NOA
 12-0801.01
 IN BOTH APPROVALS THERE ARE MULTIPLE SUB-SYSTEMS AND
 ASSOCIATED PRESSURES. IN NEITHER REPORT WAS A
 SUB-SYSTEM AND ASSOCIATED PRESSURES INDICATED. ALSO IN
 BOTH REPORTS LIMITATION # 9 IS INDICATED NO ENHANCED
 FASTENING CAN OCCUR. THE PLANS DO NOT INDICATE ROOF TOP
 PRESSURES FOR ZONES 1,2 & 3. PLEASE PROVIDE PRESSURES
 IN VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. 2014
 FBC- B 1603.1.4 WIND DESIGN DATA.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By jwitmer Date 2016-08-09 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2016-08-07 Time 05:58 Sent To  
Notes
2016-08-09 15:45:18ROOFING PLAN REVIEW
 W. P. B. PERMIT: 16070837
 ADD: 309/317 N. ROSEMARY AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-456-7252
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SUN. AUGUST 07/2016
 ACTION: DENIED
 .(2) ROOFING APPROVALS WERE SUBMITTED FOR THIS REVIEW.
 CARLISLE MIRASEAL FLUID APPLIED WATERPROOFING MEMBRANE
 NOA 13-0129.22
 CARLISLE CCW-500-R HOT APPLIED LIQUID MEMBRANE NOA
 12-0801.01
 IN BOTH APPROVALS THERE ARE MULTIPLE SUB-SYSTEMS AND
 ASSOCIATED PRESSURES. IN NEITHER REPORT WAS A
 SUB-SYSTEM AND ASSOCIATED PRESSURES INDICATED. ALSO IN
 BOTH REPORTS LIMITATION # 9 IS INDICATED NO ENHANCED
 FASTENING CAN OCCUR. THE PLANS DO NOT INDICATE ROOF TOP
 PRESSURES FOR ZONES 1,2 & 3. PLEASE PROVIDE PRESSURES
 IN VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. 2014
 FBC- B 1603.1.4 WIND DESIGN DATA.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2016-11-08 Cont ID  
Sent By jwitmer Date 2016-11-08 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2016-11-08 Time   Sent To  
Notes
2016-11-08 09:33:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070837
 ADD: 309/317 N. ROSEMARY AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-456-7252
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. NOV. 08/2016
 ACTION: DENIED
  
 1A) 2ND REQUEST. RESPONSE DOCUMENT INDICATED 3 SETS OF
 THE THRESHOLD INSPECTION PLAN WERE SUBMITTED, ONLY IN
 REVIEWING THE DOCUMENTS ONLY 2 SETS OF DOCUMENTS WERE
 SUBMITTED.
 1ST ROUND OF COMMENTS. 109.3.6.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/
 TYPED) SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 1B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 FORMS E-MAILED TO: [email protected] DATE:
 11/08/2016 9:08 AM
  
  
 1C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 1E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) PROVISO: 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By jwitmer Date 2016-08-09 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2016-08-07 Time 05:59 Sent To  
Notes
2016-08-09 15:43:34THRESHOLD BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070837
 ADD: 309/317 N. ROSEMARY AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-456-7252
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SUN. AUGUST 07/2016
 ACTION: DENIED
 4)THIS BUILDING IS A THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 4A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 4G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 4H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 4I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-11-30 Cont ID  
Sent By   Date 2016-11-30 Time   Rev Time 0.00
Received By kmartin Date 2016-11-30 Time 16:12 Sent To  
Notes
2016-11-30 16:12:44THIS PROJECT IS PENDING SITE PLAN APPROVAL WITH THE
 PLANNING DIVISION (REFERENCE: FSPR 15-09). PLEASE NOTE
 THAT ZONING WILL NOT APPROVE ANY PERMITS RELATED TO
 THIS PROJECT UNTIL SITE PLAN APPROVAL IS GRANTED.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT [email protected].
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By llouie Date 2016-08-25 Time   Rev Time 0.00
Received By kmartin Date 2016-08-25 Time 08:42 Sent To  
Notes
2016-08-25 08:43:29THIS PROJECT IS PENDING SITE PLAN APPROVAL WITH THE
 PLANNING DIVISION (REFERENCE: FSPR 15-09). PLEASE NOTE
 THAT ZONING WILL NOT APPROVE ANY PERMITS RELATED TO
 THIS PROJECT UNTIL SITE PLAN APPROVAL IS GRANTED.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT [email protected].
  