Plan Review Details - Permit 16070830
Plan Review Stops For Permit 16070830
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-08-09 Cont ID  
Sent By tklarge Date 2016-08-09 Time 13:59 Rev Time 0.00
Received By tklarge Date 2016-08-09 Time 13:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-08-08 Cont ID  
Sent By tklarge Date 2016-08-08 Time 06:43 Rev Time 0.00
Received By tklarge Date 2016-08-08 Time 06:12 Sent To  
Notes
2016-08-08 06:27:441) THERE ARE TWO DIFFERENT SETS OF PLANS THAT ARE IN
 THE PERMIT FILE. WHICH PLANS ARE BEING SUBMITTED FOR
 PERMIT? THE CONTRACTOR NEEDS TO COME IN AND STRAIGHTEN
 OUT THIS SUBMITTAL AND SUBMIT TWO COMPLETE SETS OF
 PLANS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1.
 2) INDICATE ON THE APPLIANCE SPECIFICATIONS THE
 SPECIFIC MODEL BEING INSTALLED ( TANKLESS WATER
 HEATER).2ND REQUEST.
 3) THERE ARE THREE PERMIT APPLICATIONS FOR THE GAS
 INSTALLATION. THE CONTRACTOR INFORMATION ON ONE OF THE
 APPLICATIONS HAS BEEN ERASED. CLARIFY. 2ND REQUEST.
 4) INFORMATION HAS BEEN SUBMITTED THAT INDICATES THIS
 IS LESS THAN 2 PSI SYSTEM YET ONE SET OF GAS RISER
 DIAGRAMS SHOWS A REGULATOR AT EACH APPLIANCE. THIS
 MAKES ABSOLUTELY NO SENSE. CLARIFY.
 5) THE SPECIFICATION SHEETS FOR THE SAMSUNG GAS
 EQUIPMENT DOES NOT SHOW THAT THE EQUIPMENT IS LISTED
 AND LABELED PER 2014 FUEL GAS CODE SEC. 301.3.SUBMIT
 SPEC SHEETS THAT SHOWS THE APPLIANCES ARE LISTED AND
 LABELED.2ND REQUEST.
 6) INDICATE THE DELIVERY PRESSURE OF THE SYSTEM.
 7) THE DRYER SHALL BE PROVIDED WITH COMBUSTION AIR
 SINCE IT IS IN A ROOM WHERE THE DOOR CAN BE SHUT. 2014
 FGC SEC.304.1, 614.5.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By tklarge Date 2016-07-25 Time 05:47 Rev Time 0.00
Received By tklarge Date 2016-07-25 Time 05:12 Sent To  
Notes
2016-07-25 05:35:361.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2. IS ALL THE PIPE BEING INSTALLED SCH. 40 METAL PIPE?
 INDICATE ALL TYPE OF PIPE MATERIAL ON THE PLANS. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 3..SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE
 SUBMITTED SPECS FOR THE RANGE AND WATER HEATER DO NOT
 SSHOW THE APPLIANCES ARE LISTED AND LABELED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 8. SUBMIT COPIES OF THE SIZING TABLES BEING USED TO
 DESIGN THE SYSTEM OR INDICATE WHICH SIZING TABLES FROM
 WHICH STANDARD ARE BEING USED TO DESIGN THE SYSTEM. WPB
 AMEND. TO FBC SEC. 107.3.5.3, FBCR SEC.G2413.3, FGC
 SEC. 402.3.
  
 9) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF ALL GAS
 APPLIANCES.WPB AMEND. TO FBC SEC. 107.2.1.
  
 10) INDICATE ON THE APPLIANCE SPECIFICATIONS THE
 SPECIFIC MODEL BEING INSTALLED ( TANKLESS WATER
 HEATER).
  
 11) SHOW THE LOCATION ON THE GAS RISER DIAGRAM AND ALSO
 ON THE REQUESTED FLOOR PLAN.WPB AMEND. TO FBC SEC.
 107.2.1.
  
 12) THERE ARE TWO PERMIT APPLICATIONS FOR THE GAS
 INSTALLATION. THE CONTRACTOR INFORMATION ON ONE OF THE
 APPLICATIONS HAS BEEN ERASED. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-09 Cont ID  
Sent By tklarge Date 2016-08-09 Time 13:59 Rev Time 0.00
Received By tklarge Date 2016-08-09 Time 13:59 Sent To  
Notes
2016-08-09 13:59:35MET WITH CONTR.TKL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-08 Cont ID  
Sent By tklarge Date 2016-08-08 Time 06:43 Rev Time 0.00
Received By tklarge Date 2016-08-05 Time 14:35 Sent To  
Notes
2016-08-05 14:35:56RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-25 Cont ID  
Sent By tklarge Date 2016-07-25 Time 05:47 Rev Time 0.00
Received By tklarge Date 2016-07-21 Time 10:48 Sent To  
Notes
2016-07-22 10:48:55PLUMB <5K