Plan Review Details - Permit 16070712
Plan Review Stops For Permit 16070712
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 02:36 Rev Time 0.00
Received By tklarge Date 2016-08-11 Time 02:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By tklarge Date 2016-07-27 Time 05:15 Rev Time 0.00
Received By tklarge Date 2016-07-27 Time 05:06 Sent To  
Notes
2016-07-27 05:15:231) SUBMIT TWO COPIES OF THE GAS PLAN. WPB AMEND. TO FBC
 SEC. 107.1.
 2) INDDICATE ON BOTH PLANS IF THE GAS STOVE AND OUTLET
 ARE EXISTING AND BEING REPLACED WITH NEW PIPING OR IS
 THIS BEING ADDED TO TO AN EXISTING GAS SYSTEM.
 3) IF THIS IS A NEW GAS OUTLET BEING ADDED TO AN
 EXISTING SYSTEM, SUBMIT A COMPLETE GAS RISER SHOWING
 ALL EXISTING GAS APPLIANCES WITH THE BTU LOAD OF EACH
 AAPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM, TYPE OF
 PIPE, LONGEEST DEVELOPED LENGTH TO MOST REMOTE GAS
 OUTLET.FGC SEC. 402.
 4) SUBMIT MANUF. SPECIFICATIONS SHOWING THAT THE RANGE
 IS LISTED AND LABELED PER FGC SEC. 301.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 02:36 Rev Time 0.00
Received By tklarge Date 2016-08-09 Time 15:06 Sent To  
Notes
2016-08-09 15:06:28RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-27 Cont ID  
Sent By tklarge Date 2016-07-27 Time 05:15 Rev Time 0.00
Received By tklarge Date 2016-07-19 Time 10:37 Sent To  
Notes
2016-07-20 10:37:17ROUTED TO PLUMB <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved