Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By tklarge Date 2016-07-22 Time 05:47 Rev Time 0.00
Received By tklarge Date 2016-07-22 Time 05:30 Sent To  
Notes
2016-07-22 05:47:471) INDICATE ON THE PLANS WHICH SIZING TABLE FROM THE
 2014 FUEL GAS CODE IS BEING USED FOR THE SIZING OF THIS
 SYSTEM.
 2) IF TABLE 402.4 (21) IS BEING USED, SECTIONS OF THIS
 SYSTEM ARE UNDERSIZED.
 3) SHOW THE PIPE SIZE FOR THE LINE SUPPLYING THE BBQ &
 THE POOL HEATER.
 NOTE: COULD NOT DO A COMPLETE REVIEW DUE TO LACK OF
 INFO ON PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-22 Cont ID  
Sent By tklarge Date 2016-07-22 Time 05:48 Rev Time 0.00
Received By tklarge Date 2016-07-19 Time 10:54 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By tklarge Date 2016-07-22 Time 05:48 Rev Time 0.00
Received By njwira Date 2016-07-20 Time 13:28 Sent To G
Notes
2016-07-21 10:13:447/21/16- FAILED
  
 1. PLEASE PROVIDE 2 COPIES OF A SURVEY SHOWING THE
 GENERATOR IS NOT 4FT. WITHIN A REQUIRED SETBACK.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  