Plan Review Details - Permit 16070695
Plan Review Stops For Permit 16070695
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-08-04 Cont ID  
Sent By mvaldes Date 2016-08-04 Time 13:06 Rev Time 0.00
Received By mvaldes Date 2016-08-04 Time 13:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-03 Cont ID  
Sent By mvaldes Date 2016-08-03 Time 14:50 Rev Time 0.00
Received By mvaldes Date 2016-08-03 Time 14:10 Sent To M
Notes
2016-08-03 14:35:26REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO ( RED LINED ON PLANS
 )
  
 1) NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125
 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL
 BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-01 Cont ID  
Sent By mvaldes Date 2016-08-01 Time 17:28 Rev Time 0.00
Received By mvaldes Date 2016-08-01 Time 17:28 Sent To  
Notes
2016-08-01 17:28:53REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - REFER TO INITIAL COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By mvaldes Date 2016-07-25 Time 14:54 Rev Time 0.00
Received By mvaldes Date 2016-07-25 Time 14:42 Sent To  
Notes
2016-07-25 15:04:48REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - WEST PALM BEACH CITY AMENDMENTS REQUIRE PLANS TO BE
 SIGNED AND DATED BY DESIGN PROFFESIONAL RESPONSIBLE FOR
 THE DRAWINGS.
  
 - PLEASE IDENTIFY CIRCUITS FEEDING NEW EQUIPMENT ON THE
 FLOOR PLANS AND PROVIDE A PANEL SCHEDULE MATCHING IN
 ORDER TO VERIFY OCPD,CONDUCTOR, AND CONDUIT SIZES TO BE
 IN ACCORDANCE WITH NAME PLATE RATING. FBC 107 MINIMUM
 PLAN REVIEW.
  
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
 THE OUTDOOR RECEPTACLE OUTLET BY THE CONDENSING UNITS
 SHALL BE GFCI PROTECTED PER NEC 210.8(B)(4).
  
 - ELECTRICAL SUB PERMIT REQUIRED !

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-04 Cont ID  
Sent By cpuell Date 2016-08-04 Time 09:04 Rev Time 0.00
Received By mvaldes Date 2016-08-02 Time 09:42 Sent To  
Notes
2016-08-03 09:42:40RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-01 Cont ID  
Sent By mvaldes Date 2016-08-01 Time 17:29 Rev Time 0.00
Received By mvaldes Date 2016-07-27 Time 09:11 Sent To  
Notes
2016-07-28 09:11:29RESUB ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-25 Cont ID  
Sent By mvaldes Date 2016-07-25 Time 15:05 Rev Time 0.00
Received By mvaldes Date 2016-07-19 Time 14:09 Sent To  
Notes
2016-07-25 13:55:59ROUTED TO MARIO V. 7/25/2016
2016-07-19 14:09:42ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-08-03 Cont ID  
Sent By jvalido Date 2016-08-03 Time 16:44 Rev Time 0.00
Received By jvalido Date 2016-08-03 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-07-28 Cont ID  
Sent By jvalido Date 2016-07-28 Time 16:42 Rev Time 0.00
Received By jvalido Date 2016-07-28 Time 16:30 Sent To E
Notes
2016-07-28 16:33:41CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 PROVIDE ENGINEER SEAL AND SIGNATURE ON EVAPORATOR
 HANGING DETAIL AND CONDENSER TIE DOWN DETAIL.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By jvalido Date 2016-07-25 Time 13:54 Rev Time 0.00
Received By jvalido Date 2016-07-25 Time 13:40 Sent To  
Notes
2016-07-25 13:50:43CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE NAME OF PERSON WHO DREW THE PLANS. IF THE
 PERSON IS AN ARCHITECT OR ENGINEER, AN AFFIXED STAMP
 AND SIGNATURE IS REQUIRED. IF IT IS THE INSTALLING
 COMPANY THE NAME OF THE COMPANY, QUALIFIER NAME AND
 LICENSE # WILL BE ON THE PLANS.
 (2) PROVIDE ON THE PLANS THE ADDRESS OF THE LOCATION
 WHERE THE INSTALLATION IS.
 (3) PROVIDE ON THE PLANS HANGING DETAIL FOR
 EVAPORATORS.
 (4) PROVIDE ON THE PLANS CONDENSER TIE DOWN DETAIL AS
 PER FBC 2014 WINDLOAD REQUIREMENTS.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  