Plan Review Stops For Permit 16070695 |
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2016-08-04 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-08-04 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-08-04 |
Time |
13:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2016-08-03 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-08-03 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-08-03 |
Time |
14:10 |
Sent To |
M |
|
Notes |
2016-08-03 14:35:26 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO ( RED LINED ON PLANS | | ) | | | | 1) NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 | | VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE | | OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR | | THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL | | BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2016-08-01 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-08-01 |
Time |
17:28 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-08-01 |
Time |
17:28 |
Sent To |
|
|
Notes |
2016-08-01 17:28:53 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | - REFER TO INITIAL COMMENTS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-07-25 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-07-25 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-07-25 |
Time |
14:42 |
Sent To |
|
|
Notes |
2016-07-25 15:04:48 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | - WEST PALM BEACH CITY AMENDMENTS REQUIRE PLANS TO BE | | SIGNED AND DATED BY DESIGN PROFFESIONAL RESPONSIBLE FOR | | THE DRAWINGS. | | | | - PLEASE IDENTIFY CIRCUITS FEEDING NEW EQUIPMENT ON THE | | FLOOR PLANS AND PROVIDE A PANEL SCHEDULE MATCHING IN | | ORDER TO VERIFY OCPD,CONDUCTOR, AND CONDUIT SIZES TO BE | | IN ACCORDANCE WITH NAME PLATE RATING. FBC 107 MINIMUM | | PLAN REVIEW. | | | | - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, | | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET | | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE | | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE | | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. | | THE OUTDOOR RECEPTACLE OUTLET BY THE CONDENSING UNITS | | SHALL BE GFCI PROTECTED PER NEC 210.8(B)(4). | | | | - ELECTRICAL SUB PERMIT REQUIRED ! |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-08-04 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2016-08-04 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-08-02 |
Time |
09:42 |
Sent To |
|
|
Notes |
2016-08-03 09:42:40 | RESUB ROUTED TO JVALIDO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-08-01 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-08-01 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-07-27 |
Time |
09:11 |
Sent To |
|
|
Notes |
2016-07-28 09:11:29 | RESUB ROUTED TO JVALIDO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-07-25 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-07-25 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-07-19 |
Time |
14:09 |
Sent To |
|
|
Notes |
2016-07-25 13:55:59 | ROUTED TO MARIO V. 7/25/2016 | 2016-07-19 14:09:42 | ROUTED TO MECHANICAL INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2016-08-03 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-08-03 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-08-03 |
Time |
16:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-07-28 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-07-28 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-07-28 |
Time |
16:30 |
Sent To |
E |
|
Notes |
2016-07-28 16:33:41 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | PROVIDE ENGINEER SEAL AND SIGNATURE ON EVAPORATOR | | HANGING DETAIL AND CONDENSER TIE DOWN DETAIL. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-07-25 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2016-07-25 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2016-07-25 |
Time |
13:40 |
Sent To |
|
|
Notes |
2016-07-25 13:50:43 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | (1) PROVIDE NAME OF PERSON WHO DREW THE PLANS. IF THE | | PERSON IS AN ARCHITECT OR ENGINEER, AN AFFIXED STAMP | | AND SIGNATURE IS REQUIRED. IF IT IS THE INSTALLING | | COMPANY THE NAME OF THE COMPANY, QUALIFIER NAME AND | | LICENSE # WILL BE ON THE PLANS. | | (2) PROVIDE ON THE PLANS THE ADDRESS OF THE LOCATION | | WHERE THE INSTALLATION IS. | | (3) PROVIDE ON THE PLANS HANGING DETAIL FOR | | EVAPORATORS. | | (4) PROVIDE ON THE PLANS CONDENSER TIE DOWN DETAIL AS | | PER FBC 2014 WINDLOAD REQUIREMENTS. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|
|