Plan Review Details - Permit 16070634
Plan Review Stops For Permit 16070634
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-12-05 Cont ID  
Sent By jwitmer Date 2016-12-05 Time 17:16 Rev Time 0.00
Received By jwitmer Date 2016-12-05 Time 16:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-11-10 Cont ID  
Sent By jwitmer Date 2016-11-10 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2016-11-10 Time 10:37 Sent To  
Notes
2016-11-10 17:12:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070634
 ADD: 505 S. FLAGLER 15TH FLOOR COMMON AREAS
 CONT: ANDERSON ?MOORE CONSTRUCTION
 TEL: 561-662-1819
 E-MAIL: RKENNEY@ AMCBUILD.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. NOV. 10/ 2016
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) THE 20 % DISPROPORTIONATE COST LETTER DOES NOT LIST
 ANY WORK ON THE FRONT ENTRY DOORS (1508 & 1509) TO THE
 RESTROOMS. THE PERMIT IS FOR WORK IN THE COMMON AREAS,
 MOSTLY THE RESTROOMS. THIS WOULD MAKE THE RESTROOMS THE
 PRIMARY FUNCTION AREA FOR THIS PERMIT. IN FIGURING
 DISPROPORTIONALITY WE HAVE TO LOOK AT
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE:202.4.1 (I) COSTS ASSOCIATED WITH
 PROVIDING AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA.
 THIS WOULD MAKE THE RESTROOM DOORS THE ENTRANCE TO THE
 RESTROOMS AND WOULD BE REQUIRED TO BE MADE ACCESSIBLE
 UP TO THE DOLLAR AMOUNT WHERE DISPROPORTIONALITY
 OCCURS. IF THE REQUIRED FUNDS HAVE NOT BEEN USED UP
 THEN THE NEXT REQUIREMENT WOULD NEED TO BE MET, (II)
 COSTS ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH
 AS INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS.
 THE 2 RESTROOM DOORS COULD MEET CODE COMPLIANCE USING A
 PUSH BOTTOM AND 404.3 AUTOMATIC AND POWER-ASSISTED
 DOORS AND GATES. PLEASE ALSO REVIEW 404.3.2 MANEUVERING
 CLEARANCE.
 EXCEPTION: WHERE AUTOMATIC DOORS AND GATES REMAIN OPEN
 IN THE POWER-OFF CONDITION, COMPLIANCE WITH 404.2.4
 SHALL NOT BE REQUIRED.
  
 1ST REVIEW COMMENTS. THIS PROJECT HAS A PERMIT VALUE OF
 $118,875.00 DOLLARS IN VALUE. THE CONTRACTOR WILL NEED
 TO SUPPLY AN ITEMIZED LIST FOR ACCESSIBLE UPGRADES
 WHERE UP TO 20% OF THE VALUE OF THE PROJECT, $23,775.00
 DOLLARS. PLEASE REVIEW SECTION 202.4.1 DISPROPORTIONATE
 COST OF THE 2014 FBC-ACCESSIBILITY CODE OF THE ORDER
 HOW THE FUNDS ARE TO BE SPENT.
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 3) COMPLIED.
  
 4 IN REVIEWING THE SCOPE OF WORK, NO WORK IS OCCURRING
 AT THE DOOR 1501A, SO THIS DOOR DOES NOT NEED TO COMPLY
 AT THIS TIME WITH ACCESSIBILITY.
 1ST REVIEW COMMENTS. SHEET LS1 & 15-A1.0. PLEASE
 PROVIDE HOW ACCESSIBLE UPGRADES WILL BE ACCOMPLISHED
 FOR DOORS 1501A, 1508 & 1509, PLEASE PROVIDE WHERE THE
 REMAINING FUNDS WILL BE SPENT FOR THE ACCESSIBLE
 UPGRADES UNTIL THE 20% OF THE CONTRACT PRICE HAS BEEN
 MET.
  
 5) DIGITAL REVIEW. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-02 Cont ID  
Sent By jwitmer Date 2016-11-02 Time 08:05 Rev Time 0.00
Received By jwitmer Date 2016-11-02 Time 07:54 Sent To  
Notes
2016-11-02 08:14:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070634
 ADD: 505 S. FLAGLER 15TH FLOOR COMMON AREAS
 CONT: ANDERSON ?MOORE CONSTRUCTION
 TEL: 561-662-1819
 E-MAIL: RKENNEY@ AMCBUILD.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 10/ 2016
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST. THE RESPONSE LETTER STATES SEE ATTACHED
 DOSPROPORTIONATE COST LETTER SHOWING THAT THE
 ACCESSIBLE UPGRADES MEET THE 20% MINIMUM REQUIREMENTS.
 NO SUCH DOCUMENT IS IN THE FILE FOLDER. ONLY THE
 APPLICATION AND 3 PAGES OF COMMENT
 RESPONSES!!!!!!!!!!!!!
  
 1ST REVIEW COMMENTS. THIS PROJECT HAS A PERMIT VALUE OF
 $118,875.00 DOLLARS IN VALUE. THE CONTRACTOR WILL NEED
 TO SUPPLY AN ITEMIZED LIST FOR ACCESSIBLE UPGRADES
 WHERE UP TO 20% OF THE VALUE OF THE PROJECT, $23,775.00
 DOLLARS. PLEASE REVIEW SECTION 202.4.1 DISPROPORTIONATE
 COST OF THE 2014 FBC-ACCESSIBILITY CODE OF THE ORDER
 HOW THE FUNDS ARE TO BE SPENT.
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 3) COMPLIED.
  
 4) 2ND REQUEST. THE RESPONSE LETTER STATES SEE ATTACHED
 DOSPROPORTIONATE COST LETTER SHOWING THAT THE
 ACCESSIBLE UPGRADES MEET THE 20% MINIMUM REQUIREMENTS.
 NO SUCH DOCUMENT IS IN THE FILE FOLDER. ONLY THE
 APPLICATION AND 3 PAGES OF COMMENT
 RESPONSES!!!!!!!!!!!!!
  
 1ST REVIEW COMMENTS. SHEET LS1 & 15-A1.0. PLEASE
 PROVIDE HOW ACCESSIBLE UPGRADES WILL BE ACCOMPLISHED
 FOR DOORS 1501A, 1508 & 1509, PLEASE PROVIDE WHERE THE
 REMAINING FUNDS WILL BE SPENT FOR THE ACCESSIBLE
 UPGRADES UNTIL THE 20% OF THE CONTRACT PRICE HAS BEEN
 MET.
  
 5) DIGITAL REVIEW. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By jwitmer Date 2016-08-10 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2016-08-10 Time 07:30 Sent To  
Notes
2016-08-10 10:23:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070634
 ADD: 505 S. FLAGLER 15TH FLOOR COMMON AREAS
 CONT: ANDERSON ?MOORE CONSTRUCTION
 TEL: 561-662-1819
 E-MAIL: RKENNEY@ AMCBUILD.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 10/ 2016
 ACTION: DENIED
  
 1) THE DEMO SHEET 022_D1.0 SHOWS THE REMOVAL OF THE
 ELEVATOR LOBBY DOORS AND THE LIFE SAFETY PLANLS1.0 THEY
 ARE NOT RE-INSTALLED. THIS IS A HIGH RISE BUILDING,
 PLEASE SHOW HOW COMPLIANCE WITH
 FBC-B 713.14.1 ELEVATOR LOBBY IS COMPLIED WITH AND OR
 ONE OF THE 7 EXCEPTIONS.
  
 2) THIS PROJECT HAS A PERMIT VALUE OF $118,875.00
 DOLLARS IN VALUE. THE CONTRACTOR WILL NEED TO SUPPLY AN
 ITEMIZED LIST FOR ACCESSIBLE UPGRADES WHERE UP TO 20%
 OF THE VALUE OF THE PROJECT, $23,775.00 DOLLARS. PLEASE
 REVIEW SECTION 202.4.1 DISPROPORTIONATE COST OF THE
 2014 FBC-ACCESSIBILITY CODE OF THE ORDER HOW THE FUNDS
 ARE TO BE SPENT.
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 3) IN BOTH THE WOMENS AND MENS RESTROOMS PLEASE PROVIDE
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4)SHEET LS1. PLEASE PROVIDE HOW ACCESSIBLE UPGRADES
 WILL BE ACCOMPLISHED FOR DOORS 1501A, 1508 & 1509,
 PLEASE PROVIDE WHERE THE REMAINING FUNDS WILL BE SPENT
 FOR THE ACCESSIBLE UPGRADES UNTIL THE 20% OF THE
 CONTRACT PRICE HAS BEEN MET.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-12-08 Cont ID  
Sent By vperez Date 2016-12-08 Time 13:21 Rev Time 0.00
Received By vperez Date 2016-12-08 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-21 Cont ID  
Sent By vperez Date 2016-07-21 Time 17:17 Rev Time 0.00
Received By vperez Date 2016-07-21 Time 17:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-10-17 Cont ID  
Sent By pleduc Date 2016-10-17 Time   Rev Time 0.00
Received By pleduc Date 2016-10-17 Time 13:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By pleduc Date 2016-07-26 Time   Rev Time 0.00
Received By pleduc Date 2016-07-25 Time 10:54 Sent To  
Notes
2016-07-26 13:31:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET D 1.0 - THE PLAN INDICATES THE REMOVAL 9AND
 NON-REPLACEMENT) OF THE ELEVATOR LOBBY DOORS. ELEVATOR
 DOORS CAN BE REMOVED UNDER CERTAIN EXEMPTIONS. SOME
 ELEVATORS DOORS ARE REQUIRED TO ASSIST IN FIRE
 PROTECTION, PRESSURIZATION, SMOKE CONTROL , ETC.
  
 PLEASE PROVIDE A REVIEW FROM THE ENGINEER OF RECORD
 THAT THE PURPOSE AND FUNCTION OF ELEVATOR LOBBY DOORS
 HAS BEEN REVIEWED AND VERIFIED. ADDITIONALLY, THE
 REMOVEAL OF THESE DOORS IS WITHIN CODE REQUIRMENTS,(
 PROVIDE THE CODE) AND WILL NOT AFFECT THE PREVIOUSLY
 ENGINEERED LIFE SAFETY FIRE PROTECTIONS SYSTEMS OF THE
 BUILDING.
  
  
 2) SHEET E 2.1 - NOTE # 2 INDICATES WORK ON FIRE ALARM
 DEVICES.
  
 PLEASE PROVIDE A NOTE INDICATING THAT ALL WORK THE FIRE
 ALARM SYSTEM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
  
 3) SHEET E 2.1 - INFORMATIONAL PURPOSES ONLY :
  
 THERE DOES NOT APPEAR ANY VISUAL FIRE ALARM DEVICES.
 THOUGH THIS IS A CONCEPTUAL DRAWING, ENSURE THAT THE
 FIRE ALARM SHOP DRAWINGS INCLUDE ANY APPLICABLE VISUAL,
 AS WELL AS, AUDIBLE DEVICES.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-12-15 Cont ID  
Sent By gjohnson Date 2016-12-15 Time 09:22 Rev Time 0.00
Received By gjohnson Date 2016-11-29 Time 17:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-10 Cont ID  
Sent By jwitmer Date 2016-11-10 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2016-11-03 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-03 Cont ID  
Sent By cpuell Date 2016-11-03 Time 10:34 Rev Time 0.00
Received By cpuell Date 2016-10-12 Time 08:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-18 Cont ID  
Sent By cpuell Date 2016-08-18 Time 14:26 Rev Time 0.00
Received By cpuell Date 2016-07-20 Time 10:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-10 Cont ID  
Sent By jwitmer Date 2016-08-10 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2016-08-10 Time 07:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-02 Cont ID  
Sent By ccole Date 2016-11-02 Time 09:39 Rev Time 0.00
Received By ccole Date 2016-11-02 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-08-02 Cont ID  
Sent By ccole Date 2016-08-02 Time 07:19 Rev Time 0.00
Received By ccole Date 2016-08-02 Time 06:57 Sent To  
Notes
2016-08-02 07:24:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16070634
 8/2/2016
  
 1) SHEETS M2.1 & M6.1: LABEL THE DIFFUSERS AND GRILLS
 IN THE RESTROOMS. IT APPEARS THAT AIR FROM THE
 RESTROOMS IS BEING RECIRCULATED WHICH IS PROHIBITED PER
 TABLE 403.3 FOOTNOTE G- PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-12-15 Cont ID  
Sent By gjohnson Date 2016-12-15 Time 09:22 Rev Time 0.00
Received By gjohnson Date 2016-12-15 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-03 Cont ID  
Sent By gjohnson Date 2016-11-03 Time 10:05 Rev Time 0.00
Received By gjohnson Date 2016-11-03 Time 10:05 Sent To  
Notes
2016-11-03 10:22:072ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 1. PLEASE PROVIDE A LETTER SHOWING THE 20% OF THE TOTAL
 PROJECT COST SPENT ON ACCESSIBILITY. BUILDING HAS ASK
 FOR THIS AND IT WAS NOT PROVIDED PLUMBING CAN NOT BE
 APPROVED UNTIL THIS IS PROVIDED BECAUSE IT MAY AFFECT
 THE LOCATION OF THE PLUMBING FIXTURES.
 THE LETTER SHALL SHOW COMPLIANCE WITH FBC ACC 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-17 Cont ID  
Sent By tklarge Date 2016-08-05 Time 11:18 Rev Time 0.00
Received By tklarge Date 2016-08-05 Time 05:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-12-16 Cont ID  
Sent By skennedy Date 2016-12-16 Time 13:10 Rev Time 0.00
Received By skennedy Date 2016-12-16 Time 13:10 Sent To  
Notes
2016-12-05 17:00:27ARCHITECTURAL SIGNATURES REVIEWED AND APPROVED.
 12/05/2016 JW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-11-03 Cont ID  
Sent By gjohnson Date 2016-11-03 Time 10:25 Rev Time 0.00
Received By gjohnson Date 2016-11-03 Time 10:25 Sent To  
Notes
2016-11-03 10:26:33SIGNATURES HAVE BEEN CHECK AND APPROVED ON 11/3/16 BY
 GPJ


Account Summary | Usage Policy | Privacy Policy