Plan Review Stops For Permit 16070628 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2017-02-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-02-14 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-02-14 |
Time |
11:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2017-01-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-01-04 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-01-04 |
Time |
15:20 |
Sent To |
|
|
Notes |
2017-01-04 15:22:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC 109, VALUE IS TOO LOW. PROVIDE AN ACCURATE | | VALUE. THIS MAY BE PROVIDED VIA EMAIL. | | | | 2. APPLICANT WAS INSTRUCTED TO INCLUDE THE CHANGE OF | | OCCUPANCY PERMIT NUMBER FOR THIS SPACE. WITHOUT THIS | | INFORMATION, IT IS NOT POSSIBLE TO DETERMINE WHAT | | REQUIREMENTS APPLY, AND IT IS NOT POSSIBLE TO CONTACT | | IMPACT FEE DEPARTMENT TO DETERMINE WHETHER OR NOT | | IMPACT FEE ASSESSMENT IS REQUIRED. | | | | AFTER SEARCHING FOR SOME TIME THROUGH MULTIPLE PERMITS, | | I HAD LOCATED THE PERMIT NUMBER (SCOPE PER APPLICANT) | | AND PROVIDED THIS OVER THE TELEPHONE. APPLICANT WAS TO | | INCLUDE THIS ON THE PLAN. I WAS UNABLE TO LOCATE THIS | | INFORMATION; IF IT IS ON THE PLAN, PLEASE PROVIDE | | LOCATION. | | | | DUE TO THE LARGE NUMBER OF PERMITS FOR THIS PARCEL, MY | | UNFAMILIARITY WITH THE SITE AND THE UNITS, AND MORE | | THAN ONE CHANGE OF OCCUPANCY PERMIT FOR THE SPACE, IT | | IS IMPOSSIBLE FOR ME TO OBTAIN THIS INFORMATION AS I'D | | ONLY BE GUESSING WHICH PERMIT PERTAINS TO THIS UNIT. | | THE DESIGNER OF RECORD IS REQUIRED TO DO THIS RESEARCH, | | INCLUDE THE INFORMATION ON THE PLAN (3RD REQUEST), AND | | A REVIEW IS DONE ON THE INFORMATION PROVIDED. | | | | 3. THIS PERMIT WILL BE ISSUED WITH PROVISO: | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | REQUIRED. THIS IS TO SHOW ALL MECHANICAL EQUIPMENT. | | PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE, ALL OUTDOOR | | EQUIPMENT ANCHORING, INCLUDING ROOFTOP EQUIPMENT. | | | | THE PLAN INCLUDES A NOTE REGARDING ACCESSIBILITY FOR | | EACH TYPE OF EQUIPMENT, BUT THE PLAN IS NOT COMPLIANT. | | EITHER REVISE THE PLAN TO SHOW COMPLIANCE, OR THIS | | PERMIT WILL BE ISSUED WITH PROVISO THAT A REVISION IS | | REQUIRED PRIOR TO C.O. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-11-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-11-18 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-11-17 |
Time |
18:02 |
Sent To |
|
|
Notes |
2016-11-18 11:27:19 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 16070628 | | ADD: 2223 PALM BEACH LAKES BLVD. | | CONT: BRETT DROUIN | | TEL: 561-745-6785 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | ACTION: DENIED | | | | NOTE THAT A RESPONSE LETTER WAS NOT SUBMITTED AS | | REQUESTED. A LIST OF SHEETS REVISED WAS PROVIDED, BUT | | NO EXPLANATION AS TO HOW THESE ITEMS WERE ADDRESSED. IT | | IS RECOMMENDED THAT APPLICANT CONFIRM THAT ALL COMMENTS | | HAVE BEEN ADDRESSED PRIOR TO SUBMITTAL. | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1) SHEET A-1 CODE SUMMARY, OCCUPANCY GROUP LISTS THIS | | OCCUPANCY TYPE AS A BUSINESS OCCUPANCY. PLEASE SEE THE | | 2014 FBC-B 303.4 ASSEMBLY GROUP A-3 GYMNASIUMS (WITHOUT | | SPECTATOR SEATING). | | | | 2ND REVIEW, A1 STATES THIS IS BUSINESS (SAME BOX AS | | WIND DESIGN CRITERIA). | | | | 2) THE DESIGNER OF RECORD INDICATES THIS IS A LEVEL II | | ALTERATION. PLEASE PROVIDE WHERE THESE LAST KNOWN USES | | OCCUPIED WHICH PORTION OF THE BUILDING TO DETERMINE IF | | THERE IS A CHANGE OF OCCUPANCY FOR THE LOCATION OF THE | | GYMNASIUM. | | 2A) ALAN WELLS COMMERCIAL REAL ESTATE/ BUSINESS TAX | | LICENSE ACTIVE UNTIL 9/30/2016 | | 2B) WEST PALM BEACH EVENT HALL # 1/ / BUSINESS TAX | | LICENSE ACTIVE UNTIL 9/30/2016 | | | | DEPENDING ON THE LOCATION THERE MAY BE A CHANGE OF | | OCCUPANCY. AT LEAST THERE IS A CHANGE OF USE WITHIN THE | | SAME OCCUPANCY TYPE. | | 2014 FBC-B 1012.1. THE PROVISIONS OF THIS SECTION SHALL | | APPLY TO BUILDINGS OR PORTIONS THEREOF UNDERGOING A | | CHANGE OF OCCUPANCY CLASSIFICATION. THIS INCLUDES A | | CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS | | WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE | | GROUP TO A DIFFERENT GROUP. SUCH BUILDINGS SHALL ALSO | | COMPLY WITH SECTIONS 1002 THROUGH 1011. THE APPLICATION | | OF REQUIREMENTS FOR THE CHANGE OF OCCUPANCY SHALL BE AS | | SET FORTH IN SECTIONS 1012.1.1 THROUGH 1012.1.4. | | | | 2ND REVIEW, NOT ADDRESSED. THE REQUESTED INFORMATION | | WAS NOT PROVIDED. THE OUTLINE OF THE BUILDING WITH AN | | AREA HIGHLIGHTED WAS PROVIDED. IT DOES NOT PROVIDE THE | | INFORMATION REQUESTED: ALAN WELLS, EVENT HALL | | LOCATIONS, WHAT WAS IN THIS SPACE BEFORE IF IT WAS | | NEITHER OF THESE? IT IS LIKELY THAT THIS IS A CHANGE OF | | OCCUPANCY, SO THE PREVIOUS LEGAL USE SHOULD BE | | DETERMINED, PLANS REVISED TO INCLUDE THIS INFORMATION, | | AS WELL AS SHOW COMPLIANCE WITH CHANGE OF OCCUPANCY, IF | | APPLICABLE. | | | | 3, 4, 5) OK | | | | 6) IN THE CARDIO AREA THERE SEEMS TO BE NO AREA FOR AN | | ACCESS AISLE. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B | | 1028.9.2 AISLE WIDTH. THE AISLE WIDTH SHALL PROVIDE | | SUFFICIENT EGRESS CAPACITY FOR THE NUMBER OF PERSONS | | ACCOMMODATED BY THE CATCHMENT AREA SERVED BY THE AISLE. | | THE CATCHMENT AREA SERVED BY AN AISLE IS THAT PORTION | | OF THE TOTAL SPACE THAT IS SERVED BY THAT SECTION OF | | THE AISLE. IN ESTABLISHING CATCHMENT AREAS, THE | | ASSUMPTION SHALL BE MADE THAT THERE IS A BALANCED USE | | OF ALL MEANS OF EGRESS, WITH THE NUMBER OF PERSONS IN | | PROPORTION TO EGRESS CAPACITY. | | | | 2ND REVIEW, IT IS NOT CLEAR HOW THIS HAS BEEN | | ADDRESSED. THE EQUIPMENT PLAN SHOWS EQUIPMENT DENSELY | | LOCATED, WITH LITTLE ROOM PROVIDED FOR OCCUPANT EGRESS. | | REVISE PLAN TO SHOW THE CLEAR WIDTH OF AREAS FOR | | EGRESS. ALSO, THE LACK OF SPACE BETWEEN EQUIPMENT | | APPEARS TO SHOW LACK OF COMPLIANCE WITH FBC | | ACCESSIBILITY 236, 1004. | | | | 7) OK | | | | 8) OK | | | | 9) OK WITH PROVISO; IF MECHANICAL REVIEW DETERMINES | | THAT NEW EQUIPMENT IS REQUIRED, PROVIDE ANCHORING, | | STAND OR CURB DETAILS. | | | | 10) THE PLANS NEED TO GO TO PALM BEACH COUNTY IMPACT | | FEE OFFICE FOR REVIEW. BEFORE A PERMIT TO CONSTRUCT, | | MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 | | FOR MORE INFORMATION. | | | | THIS MAY BE DONE AFTER ALL PLAN REVIEWS HAVE PASSED, | | BUT BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | NEW COMMENTS: | | | | 12. SEE NFIP REVIEW. AS DESIGN TO RESIST FLOOD LOADS IS | | A REQUIREMENT OF THE BUILDING CODE (FBC B 1612), REVISE | | THE PLAN TO SHOW COMPLIANCE. OPTIONS WERE SENT VIA | | EMAIL TO OWNER'S REP ON 10/13/16. APPLICANT MAY SEND | | INFORMATION FOR PRELIMINARY REVIEW (SUCH AS ELEVATION | | CERTIFICATE, APPRAISAL) VIA EMAIL PRIOR TO | | RESUBMITTING. | | | | 13. EXERCISE MACHINES AND EQUIPMENT ARE TO COMPLY WITH | | FBC ACCESSIBILITY 236, 1004. REVISE PLAN TO SHOW | | COMPLIANCE. NOTE THAT THIS WOULD HAVE BEEN A PROVISO | | ITEM HAD ALL OTHER BUILDING COMMENTS BEEN ADDRESSED. | | HOWEVER, SINCE THE PLANS NEED TO BE REVISED TO ADDRESS | | OTHER COMMENTS FOR BOTH BUILDING AND OTHER TRADES, | | REVISE TO SHOW COMPLIANCE AT THIS TIME. | | | | 14. IF IT IS DETERMINED THAT THIS PROJECT INCLUDES A | | CHANGE OF OCCUPANCY, PLAN SHOULD BE REVISED TO SHOW | | COMPLIANCE WITH FBC EXISTING BUILDING CHAPTER 10. A | | COMPLETE LIST CANNOT BE PROVIDED DUE TO LACK OF | | INFORMATION. FOR INSTANCE, SEE FBC EXISTING BUILDING | | TABLE 1012.4. IF THIS WAS BUSINESS, AND ASSEMBLY IS | | PROPOSED, THE MEANS OF EGRESS SHALL COMPLY WITH FBC | | CHAPTER 10 AS ASSEMBLY IS A HIGHER CATEGORY. IN THAT | | CASE, PANIC OR FIRE EXIT HARDWARE IS REQUIRED FOR ALL | | DOORS IN THE MEANS OF EGRESS. EXTERIOR DOORS, IF THEY | | DO NOT INCLUDE PANIC DEVICES, WOULD BE REQUIRED TO BE | | REPLACED. | | | | THIS LIST CANNOT BE COMPLETE AS IT IS NOT POSSIBLE TO | | DO A COMPLETE REVIEW WITHOUT FIRST DETERMINING THE | | PREVIOUS LEGAL OCCUPANCY. | | | | 15. SEE FLORIDA STATUTE 553.80 (2) (B), AND NOTE IN | | PARTICULAR THE LANGUAGE "SHALL" (RATHER THAN "MAY"): | | | | (B) WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS' | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | SAMANTHA HILL (FOR JIM WITMER) | | CONSTRUCTION SERVICES DIVISION | | DEVELOPMENT SERVICES DEPARTMENT | | TEL: 561-805-6724, FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-07-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-07-28 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-07-28 |
Time |
06:48 |
Sent To |
|
|
Notes |
2016-07-28 09:56:19 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 16070628 | | ADD: 2223 PALM BEACH LAKES BLVD. | | CONT: BRETT DROUIN | | TEL: 561-745-6785 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: THURS. JULY 28/2016 | | ACTION: DENIED | | | | 1) SHEET A-1 CODE SUMMARY, OCCUPANCY GROUP LISTS THIS | | OCCUPANCY TYPE AS A BUSINESS OCCUPANCY. PLEASE SEE THE | | 2014 FBC-B 303.4 ASSEMBLY GROUP A-3 GYMNASIUMS (WITHOUT | | SPECTATOR SEATING). | | | | 2) THE DESIGNER OF RECORD INDICATES THIS IS A LEVEL II | | ALTERATION. PLEASE PROVIDE WHERE THESE LAST KNOWN USES | | OCCUPIED WHICH PORTION OF THE BUILDING TO DETERMINE IF | | THERE IS A CHANGE OF OCCUPANCY FOR THE LOCATION OF THE | | GYMNASIUM. | | 2A) ALAN WELLS COMMERCIAL REAL ESTATE/ BUSINESS TAX | | LICENSE ACTIVE UNTIL 9/30/2016 | | 2B) WEST PALM BEACH EVENT HALL # 1/ / BUSINESS TAX | | LICENSE ACTIVE UNTIL 9/30/2016 | | | | DEPENDING ON THE LOCATION THERE MAY BE A CHANGE OF | | OCCUPANCY. AT LEAST THERE IS A CHANGE OF USE WITHIN THE | | SAME OCCUPANCY TYPE. | | 2014 FBC-B 1012.1. THE PROVISIONS OF THIS SECTION SHALL | | APPLY TO BUILDINGS OR PORTIONS THEREOF UNDERGOING A | | CHANGE OF OCCUPANCY CLASSIFICATION. THIS INCLUDES A | | CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS | | WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE | | GROUP TO A DIFFERENT GROUP. SUCH BUILDINGS SHALL ALSO | | COMPLY WITH SECTIONS 1002 THROUGH 1011. THE APPLICATION | | OF REQUIREMENTS FOR THE CHANGE OF OCCUPANCY SHALL BE AS | | SET FORTH IN SECTIONS 1012.1.1 THROUGH 1012.1.4. | | 3) SHEET A-3 SHOWS AN ADJACENT TENANT SPACE AND A ROOM | | THAT ENCROACHES PAST THE TENANT SEPARATION WALL THAT | | ALSO INDICATES THIS ROOM IS EXISTING ADJACENT SPACE. | | PLEASE PROVIDE WHICH SECTION OF THE CODE THE DESIGNER | | IS GOING TO COMPLY WITH 2014 FBC-EXISTING BUILDING: | | 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT | | SEPARATION. | | 1012.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH | | SEPARATION. | | | | 4) SHEET A-5 INDICATES THE OCCUPANT LOADS, NO EQUIPMENT | | IS LISTED AS 2,295.9 SQ. FT. AN OCCUPANT LOAD OF 154 | | OCCUPANTS. NOTE THERE ARE NO DECIMAL POINTS FOR | | OCCUPANTS YOU ALWAYS ROUND UP TO THE NEXT FULL NUMBER, | | WE DON?T HAVE PARTS OF OCCUPANTS THEY ARE ALWAYS TAKEN | | AS A WHOLE NUMBER. THE ISSUE IS THE AREA WITH EQUIPMENT | | IS SHOWN AS 1,0722.3 SQ. FT. AND AN OCCUPANT LOAD OF | | 215 OCCUPANTS. HOW CAN THE AREA WITH EQUIPMENT HAVE A | | LESS OCCUPANT LOAD. DISCREPANCY IN PLANS, IT APPEARS | | THERE IS A TYPO, PLEASE CORRECT THE SQUARE FOOTAGE TO, | | 10,722.3 SQ. FT. 107.2.1.3 ADDITIONAL INFORMATION | | REQUIRED. | | | | 5) SHEET A-5 AT THE FRONT ENTRY THERE IS A BUSINESS | | COUNTER, PLEASE NOTE THIS DOOR SWINGS AGAINST THE | | EGRESS FLOW. 2014 FBC-B 1008.1.2 DOORS SHALL SWING IN | | THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR | | AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS. | | | | 6) IN THE CARDIO AREA THERE SEEMS TO BE NO AREA FOR A | | ACCESS AISLE. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B | | 1028.9.2 AISLE WIDTH. THE AISLE WIDTH SHALL PROVIDE | | SUFFICIENT EGRESS CAPACITY FOR THE NUMBER OF PERSONS | | ACCOMMODATED BY THE CATCHMENT AREA SERVED BY THE AISLE. | | THE CATCHMENT AREA SERVED BY AN AISLE IS THAT PORTION | | OF THE TOTAL SPACE THAT IS SERVED BY THAT SECTION OF | | THE AISLE. IN ESTABLISHING CATCHMENT AREAS, THE | | ASSUMPTION SHALL BE MADE THAT THERE IS A BALANCED USE | | OF ALL MEANS OF EGRESS, WITH THE NUMBER OF PERSONS IN | | PROPORTION TO EGRESS CAPACITY. | | | | 7) THE PLANS SHEET A-5 SHOW EXITS LIGHTS HUNG FROM THE | | CEILING BUT NO MENTION OF COMPLIANCE WITH THE 2014 | | FBC-B 1011.4 RAISED CHARACTER AND BRAILLE EXIT SIGNS. A | | SIGN STATING EXIT IN RAISED CHARACTERS AND BRAILLE AND | | COMPLYING WITH ICC A117.1 SHALL BE PROVIDED ADJACENT TO | | EACH DOOR TO AN AREA OF REFUGE, AN EXTERIOR AREA FOR | | ASSISTED RESCUE, AN EXIT STAIRWAY, AN EXIT RAMP, AN | | EXIT PASSAGEWAY AND THE EXIT DISCHARGE. ALSO SEE | | SIGNAGE REQUIREMENTS UNDER THE FBC-ACCESS. CODE SECTION | | 703. | | | | 8) THE PLANS DO NOT INCLUDE ANY HEIGHTS OR ELEVATIONS | | FOR SERVICE COUNTERS SHOW COMPLIANCE WITH THE 2014 | | FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK | | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 | | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | GROUND. | | 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK | | WRITING SURFACES SHALL COMPLY WITH 902.3. | | | | 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND | | SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. | | THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND | | THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. | | | | 9) ADDITIONAL COMMENTS MAY OCCUR DUE TO THE MECHANICAL | | REVIEW AND ANY ADDITIONAL MECHANICAL ROOFTOP EQUIPMENT | | THAT MAYBE REQUIRED. 2014 FBC-M- 301.15 WIND | | RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND | | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND | | INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. | | | | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | LOADS? | | | | 10) THE PLANS MAY NEED TO GO TO PALM BEACH COUNTY | | IMPACT FEE OFFICE FOR REVIEW. BEFORE A PERMIT TO | | CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST | | BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID | | RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | (561)233-5025 FOR MORE INFORMATION. | | | | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | DEVELOPMENT SERVICES DEPARTMENT | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2017-01-25 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2017-01-25 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2017-01-25 |
Time |
09:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-11-17 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-11-17 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-11-17 |
Time |
16:11 |
Sent To |
|
|
Notes |
2016-11-17 16:19:17 | PROVISO= DRINKING FOUNTAIN AND BATH/LOCKERS RECEPTACLES | | TO BE GFCI PROTECTED. | | PROVIDE EM PHOTOMETRICS PER FIRE COMMENTS | | | | VAL PEREZ | | *6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-07-21 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-07-21 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-07-21 |
Time |
12:44 |
Sent To |
|
|
Notes |
2016-07-21 13:03:01 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE | | PERMITS FOR ALL LOW VOLTAGE SYSTEMS AND SIGNAGE SHOWN | | ON PLANS. FBC 107.3 | | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, | | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING AUTOMATIC | | MEANS OF LIGHTING CONTROLS, BRANCH VOLTAGE DROP AND | | COMPLETIONS DOCUMENTS. | | 3. LABEL ALL RECEPTACLES IN LOCKERS AREAS TO BE GFCI | | PROTECTED NEC 210.8B | | 4. PROVIDE A SYMBOLS LEGEND FOR ALL DEVICES SHOWN. FBC | | 107.3.5 | | 5. PROVIDE EQUIPMENT SCHEDULE FOR DRYERS, WATER HEATERS | | TO VERIFY 3 PHASE VOLTAGE LOADS | | 6. CLARIFY IF ABOVE MOUNTED W/H ARE IN A DROP CEILING, | | JUST NEED CLARIFICATION. | | 7. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2017-02-21 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2017-02-21 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2017-02-21 |
Time |
10:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2017-01-19 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-01-19 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-01-19 |
Time |
12:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2016-11-10 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2016-11-10 |
Time |
10:32 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2016-11-10 |
Time |
10:17 |
Sent To |
|
|
Notes |
2016-11-10 10:32:28 | 2223 PALM BEACH LAKES BOULEVARD | | PERMIT #16070628 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | REPEAT COMMENT: THE NORTH GATE OF THE FRONT | | ENTRANCE/FRONT DESK AREA SWINGS AGAINST THE FLOW OF | | EGRESS. GATES SHALL BE EQUIPPED WITH PANIC HARDWARE. | | | | REPEAT COMMENT: OVER THE YEARS, EMERGENCY LIGHTING HAS | | BEEN INSTALLED AND REMOVED FROM THIS SUITE. PROVIDE AN | | ELECTRICAL PHOTOMETRICS PLAN SHOWING AT LEAST 1-FT | | CANDLE IS BEING PROVIDED ALONG ALL EGRESS PATHS. | | | | REPEAT COMMENT: THE ONLY FLOORING MATERIAL INDICATED IN | | THIS SPACE IS THE "TURF" AREA. PROVIDE PRODUCT DATA FOR | | THIS MATERIAL. FLOORING SHALL BE AT LEAST CLASS I. PER | | NFPA 10.2.7.4 CLASS I INTERIOR FLOOR FINISH SHALL BE | | CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN | | 0.45 W/CM2. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2016-07-22 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2016-07-22 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2016-07-22 |
Time |
10:57 |
Sent To |
|
|
Notes |
2016-07-22 11:42:07 | 2223 PALM BEACH LAKES BOULEVARD | | PERMIT #16070628 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE PLANS INDICATE THIS IS A BUSINESS OCCUPANCY; | | HOWEVER, THE LIFE SAFETY CODE WILL CLASSIFY THIS | | OCCUPANCY AS AN ASSEMBLY. | | | | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS | | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A | | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. | | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF | | OCCUPANTS PERMITTED FOR EACH ROOM. | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | EXIT SIGNS. | | | | THE NORTH GATE OF THE FRONT ENTRANCE/FRONT DESK AREA | | SWINGS AGAINST THE FLOW OF EGRESS. GATES SHALL BE | | EQUIPPED WITH PANIC HARDWARE. | | | | THE EXISTING DOUBLE DOORS EQUIPPED WITH MAG-LOCKS | | INDICATE "EXIST LOCK." THESE DOORS SHALL FEATURE | | OBVIOUS SIGNAGE INDICATING "NOT AN EXIT." | | | | OVER THE YEARS, EMERGENCY LIGHTING HAS BEEN INSTALLED | | AND REMOVED FROM THIS SUITE. PROVIDE AN ELECTRICAL | | PHOTOMETRICS PLAN SHOWINGAT LEAST 1-FT CANDLE IS BEING | | PROVIDED ALONG ALL EGRESS PATHS. | | | | WHAT TYPE OF WALL FINISHES ARE INTENDED TO BE | | INSTALLED? | | | | THE ONLY FLOORING MATERIAL INDICATED IN THIS SPACE IS | | THE "TURF" AREA. PROVIDE PRODUCT DATA FOR THIS | | MATERIAL. FLOORING SHALL BE AT LEAST CLASS I. PER NFPA | | 10.2.7.4 CLASS I INTERIOR FLOOR FINISH SHALL BE | | CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN | | 0.45 W/CM2. | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | ALARM SYSTEM. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2017-02-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-02-28 |
Time |
07:48 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-02-24 |
Time |
14:48 |
Sent To |
|
|
Notes |
2017-02-27 14:48:45 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2017-02-23 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2017-02-23 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2017-02-07 |
Time |
14:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2017-01-25 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2017-01-25 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2017-01-25 |
Time |
09:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-11-28 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-11-28 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-11-04 |
Time |
09:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-08-06 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-08-06 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-07-18 |
Time |
13:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
N |
Date |
2017-02-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-02-14 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-02-14 |
Time |
11:27 |
Sent To |
|
|
Notes |
2017-02-14 11:29:41 | PALM BEACH COUNTY IMPACT FEE OFFICE: | | MU-2017-000648-0000 | | NO FEES DUE | | JAN. 10/ 2017 | | J. W. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2016-07-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-07-28 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-07-28 |
Time |
09:56 |
Sent To |
|
|
Notes |
2016-07-28 09:57:00 | IMPACT FEES | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2017-02-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-02-28 |
Time |
07:48 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-02-28 |
Time |
07:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2017-02-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-02-22 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-02-22 |
Time |
14:41 |
Sent To |
|
|
Notes |
2017-02-22 14:54:55 | 5TH REVIEW FBC-2014 MECHANICAL | | PERMIT #16070628 | | 2/22/17 | | | | 1) THE REAR EGRESS CORRIDOR SHALL NOT BE USED AS A | | RETURN AIR DUCT PER SECTION 601.2. PLEASE REMOVE THE | | TRANSFER GRILLS AND PROVIDE DUCTED RETURNS FROM THE | | AEROBICS, SPINNING, AND BREAK ROOMS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2017-02-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-02-10 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-02-09 |
Time |
14:53 |
Sent To |
|
|
Notes |
2017-02-10 08:08:29 | 4TH REVIEW FBC-2014 MECHANICAL | | PERMIT #16070628 | | 2/9/17 | | | | 1) THE NEW 48X16 RETURN TRANSFER FROM THE AEROBICS ROOM | | TO THE EGRESS CORRIDOR IS PROHIBITED PER SECTION 601.2. | | | | 2) AS PREVIOUSLY REQUESTED PROVIDE AN AIR DEVICE | | SCHEDULE LISTING THE MAKES AND MODELS OF ALL NEW AND | | EXISTING AIR DEVICES. | | | | 3) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER | | SMACNA HVAC DUCT CONSTRUCTION STANDARDS 2005. | | | | 4) PLACE A NOTE ON THE PLANS IN ACCORDANCE WITH SECTION | | C408.2.2 TO INDICATE THE SYSTEMS WILL BE TESTED AND | | BALANCED BY EITHER A LICENSED ENGINEER OR AN INDIVIDUAL | | HOLDING A CURRENT CERTIFICATION FROM A RECOGNIZED | | TESTING AND BALANCING AGENCY ORGANIZATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2016-12-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-12-29 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-12-29 |
Time |
11:35 |
Sent To |
|
|
Notes |
2016-12-29 11:43:30 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16070628 | | 12/18/16 | | | | 1) THE OUTDOOR AIR CALCULATIONS ARE INCORRECT PER TABLE | | 403.3 AND ASHRAE 62.1-2010. THE HEALTH GYM, AEROBICS | | ROOM, AND SPIN ROOM SHALLL BE CALCULATED AT 40 PERSONS | | PER 1000 SF. | | | | 2) BASED ON THE O/A CALCULATIONS ENERGY RECOVERY | | SYSTEMS MUST BE INSTALLED FOR RTU'S 2 & 3- REFER TO | | TABLE C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE | | REVISE THE PLANS ACCORDINGLY. | | | | 3) PLEASE CORRELATE THE IDENTIFICATION NUMBERS OF THE | | RTU'S IN THE SXCHEDULE TO MATCH THE PLANS. | | | | 4) PROVIDE AN AIR DEVICE SCHEDULE FOR BOTH THE NEW AND | | EXISTING DIFFUSERS AND GRILLS. IT APPEARS THAT THE | | EXISTING SUPPLY DIFFUSERS FOR THE RTU'S SERVING THE GYM | | ARE UNDERSIZED FOR THE SPECIFIED CFMS. PLEASE PROVIDE | | MANUFACTURER'S ENGINEERING DATA FOR THE EXISTING | | DIFFUSERS THAT INDICATES THE CFM CAPACITIES BASED ON | | THE PRESSURE LOSS OF THE SYSTEMS AND FACE VELOCITIES. | | | | 5) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS NOT | | PROVIDED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-11-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-11-10 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-11-10 |
Time |
16:17 |
Sent To |
|
|
Notes |
2016-11-10 16:44:41 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16070628 | | 11/10/16 | | | | 1) REVISE THE EXISTING EQUIPMENT SCHEDULE TO INCLUDE | | THE TOTAL SUPPLY CFMS FOR EACH RTU. | | | | 2) SHOW THE RETURN DUCT SIZES FROM THE AEROBICS ROOM, | | SPINNING ROOM, AND BREAKROOM, AND THE POINTS OF | | CONNECTION TO THE MAIN RETURN TRUNK AND TRUNK SIZE. | | | | 3) THERE ARE LARGE OPEN AREAS IN THE HEALTH GYM | | INCLUDING THE FRONT DESK WHERE NO AC AIR DISTRIBUTION | | IS SHOWN ON THE PLANS. HOW ARE THESE AREAS BEING | | CONDITIONED AND SUPPLIED WITH O/A IN ACCORDANCE WITH | | THE CALCULATIONS? A) SHOW THE ENTIRE DUCT LAYOUTS FOR | | RTU-2 & 3 WITH DUCT, DIFFUSER AND RETURN GRILL SIZES | | SHOWN, AND THE SUPPLY CFMS AT EACH DIFFUSER INDICATED. | | | | 4) THERE ARE 3 EXISTING FANS IN THE HEALTH GYM SHOWN ON | | THE PLAN. CLARIFY THE PURPOSE OF THE FANS AND PROVIDE | | INFORMATION INCLUDING THE MAKES AND MODELS, CFM | | CAPACITIES AND THEIR INDIVIDUAL CONTROL OPERATIONS. | | | | 5) THE PROJECT IS NOW BEING CLASSIFIED AS A "CHANGE OF | | OCCUPANCY" PER THE NEW NOTE ON SHEET A-1. REFER TO | | SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND PROVIDE | | ENERGY CALCULATIONS- SEE SECTION C401.2 FOR COMPLIANCE | | PATH OPTIONS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-07-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-07-21 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-07-21 |
Time |
14:18 |
Sent To |
|
|
Notes |
2016-07-21 14:58:17 | 1ST REVIEW MECHANICAL, EXISTING BUILDING CODES. | | PERMIT #16070628 | | 7/21/16 | | | | 1) SHEET ME-1: REFER TO SECTION 809.2 FBC-14 EXISTING | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | FBC-14 MECHANICAL. IDENTIFY ALL ROOMS AND SPACES ON THE | | PLANS AND PROVIDE A SCHEDULE THAT INDICATES THE | | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE | | THAT THIS IS NOT A BUSINESS OCCUPANCY AS INDICATED ON | | NTHE FLOOR PLAN NOTE- THIS IS AN A3 ASSEMBLY OCCUPANCY | | PER SECTION 303.4 FBC-14 BUILDING. | | | | 2) ME-1: REFER TO TABLE 403.3 AND PROVIDE EXHAUST | | VENTILATION CALCULATIONS FOR THE ALTERED AND MEN'S AND | | WOMEN'S TOILET AND LOCKER ROOMS. | | | | 3) ME-1: THE AC DRAWINGS ARE INCOMPLETE. A) SHOW THE AC | | SUPPLY AND EXHAUST DUCT RUNS, DIFFUSERS AND GRILLS IN | | THE TOILET POOMS, THE LOCKER ROOMS, B) SHOW POINTS OF | | CONNECTIONS FOR NEW BRANCH DUCTS TO EXISTING TRUNKS. C) | | PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING AC SYSTEMS | | AND SHOW THEIR LOCATIONS ON THE PLANS. | | | | 4) ME-1: THE RETURN DUCT SIZES FROM THE AEROBICS AND | | BREAKROOM ARE NOT SHOWN. | | | | 5) ME-1: INDICATE THE SUPPLY CFMS AT THE BREAKROOM | | DIFFUSER. | | | | 6) ME-1: THE 12" DUCT SUPPLYING 1250 CFMS OF AIR TO THE | | AEROBICS ROOM IS UNDERSIZED PER ASHRAE/ACCA APPROVED | | DUCTULATOR- MINI,UM 16" REQUIRED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
3 |
Status |
P |
Date |
2017-01-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-01-04 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-01-04 |
Time |
15:33 |
Sent To |
|
|
Notes |
2017-01-04 15:33:49 | ****PROVISO**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | REQUIRED. THIS IS TO SHOW ALL MECHANICAL EQUIPMENT. | | PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE, ALL OUTDOOR | | EQUIPMENT ANCHORING, INCLUDING ROOFTOP EQUIPMENT, | | REQUIRED. | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
2 |
Status |
F |
Date |
2016-11-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-11-17 |
Time |
18:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-11-17 |
Time |
18:02 |
Sent To |
|
|
Notes |
2016-11-17 18:04:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | THIS PROJECT CONSTITUTES A SUBSTANTIAL IMPROVEMENT. | | CUMULATIVE LIFETIME IMPROVEMENTS = $477,909; PROPERTY | | APPRAISER VALUE FOR THE STRUCTURE IS $373,621. | | CUMULATIVE LIFETIME IMPROVEMENTS EXCEED 50% OF THE | | STRUCTURE'S VALUE. REFER TO EMAIL SENT ON 10/13 FOR | | FURTHER EXPLANATION AND OPTIONS. | | | | FBC 1612 | | | | FOR YOUR CONVENIENCE, THE EMAIL PROVIDED THE FOLLOWING | | OPTIONS: | | | | FOR SUBSTANTIAL IMPROVEMENT DETERMINATION OUR (PRE- | | SEPTEMBER 12, 2016) ORDINANCE COUNTS CUMULATIVE | | LIFETIME IMPROVEMENTS WITH A 6" FREEBOARD. OUR | | ORDINANCE CHANGED ON SEPTEMBER 12 TO FIVE YEARS WITH A | | 1' FREEBOARD. | | | | PROPERTY APPRAISER HAS A STRUCTURE VALUE OF $ 373,621 | | IN 2016. THE STRUCTURE HAS $477,909 CUMULATIVE LIFETIME | | IMPROVEMENTS, WHICH EXCEEDS 50% OF THE STRUCTURE'S | | VALUE, SO THIS IS CONSIDERED A "SUBSTANTIAL | | IMPROVEMENT". | | | | THE PRELIMINARY FLOOD ZONE MAP (NOT YET ADOPTED) WILL | | LIKELY REMOVE THIS PROPERTY FROM THE SFHA, SO THAT | | LEADS ME TO BELIEVE THAT THE STRUCTURE IS PROBABLY HIGH | | ENOUGH. WE ARE NOT ALLOWED TO USE THE PRELIMINARY MAP | | FOR REGULATORY PURPOSES; THIS CAN BE USED ONLY AFTER | | ADOPTION (MOST LIKELY WITHIN THE YEAR). | | | | THERE ARE TWO OPTIONS: | | | | A. OBTAIN AN APPRAISAL WHICH WOULD NEED TO SHOW A | | SIGNIFICANTLY HIGHER VALUE FOR THE STRUCTURE. THE VALUE | | WOULD NEED TO BE OVER $955,818 TO BRING THE CUMULATIVE | | LIFETIME IMPROVEMENTS BELOW 50%. I (OR THE BUILDING | | REVIEWER) WOULD ALSO BE REQUIRED TO EVALUATION THE | | VALUE OF THE IMPROVEMENTS MORE CAREFULLY. | | | | B. A SUBSTANTIAL IMPROVEMENT REQUIRES THAT THE BUILDING | | BE BROUGHT INTO COMPLIANCE. THE DFE AT THIS LOCATION IS | | 16.5' NGVD29 (16' PER FIRM PLUS 6" FREEBOARD). AN | | ELEVATION CERTIFICATE WOULD PROVIDE THE INFORMATION TO | | DETERMINE WHETHER OR NOT THE BUILDING IS ALREADY | | COMPLIANT. MY GUESS (THE "GOOD NEWS") IS THAT THE | | BUILDING MAY ALREADY BE HIGH ENOUGH. IF THE MECHANICAL | | EQUIPMENT IS NOT LOWER THAN THE FINISHED FLOOR, OR IF | | IT IS ON THE ROOF, THE BUILDING MAY BE COMPLIANT. | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
F |
Date |
2016-07-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-07-28 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-07-28 |
Time |
14:32 |
Sent To |
|
|
Notes |
2016-07-28 14:33:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | IT APPEARS THAT THIS MAY BE A SUBSTANTIAL IMPROVEMENT. | | CUMULATIVE LIFETIME IMPROVEMENTS = $477,909; PROPERTY | | APPRAISER VALUE FOR THE STRUCTURE IS $373,621. | | CUMULATIVE LIFETIME IMPROVEMENTS EXCEED 50% OF THE | | STRUCTURE'S VALUE. REFER TO EMAIL SENT ON 10/13 FOR | | FURTHER EXPLANATION AND OPTIONS. | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2017-02-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-02-10 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-02-10 |
Time |
12:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2017-01-23 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-01-23 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-01-23 |
Time |
09:23 |
Sent To |
|
|
Notes |
2017-01-23 09:30:13 | 3RD REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. PLEASE PROVIDE TWO COMPLETE PLAN SETS. ONE THAT WAS | | PROVIDED IS MISSING SGN-1 ONE IS MISSING P-1. PLEASE | | CLARIFY WPB AMEND TO FBC 107.2.1 | | | | 2. PROVIDE TEMPERED WATER TO ALL LAVATORY'S. PER FBC PL | | 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING | | FACILITIES. | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | 1070 OR CSA B125.3 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2016-11-28 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-11-28 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-11-28 |
Time |
09:52 |
Sent To |
|
|
Notes |
2016-11-28 09:55:40 | 2ND REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: 2ND REQUEST | | | | | | NOT COMPLIED 3) SUBMIT EXPANDED SANITARY AND WATER | | RISERS FOR REVIEW. IT IS DIFFICULT TO REVIEW THE RISERS | | AS DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. | | | | NOT COMPLIED 5) THE SINK LOCATED AT THE FRONT DESK | | SHALL COMPLY WITH THE FBC - ACCESS. SEC. 212 7 606. | | NOT COMPLIED 6) IF THIS IS A CHANGE OF OCCUPANCY THE | | LAVATORIES SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER | | PER 2014 FBC PLUMBING SEC. 607.1. | | NOT COMPLIED 7) SUBMIT ENLARGED FLOOR PLANS FOR THE | | TOILET ROOMS AND SHOWERS.THE SHOWERS, SEATS, CONTROLS, | | GRAB BARS SHALL COMPLY WITH 2014 FBC-ACCESS. SECS.608, | | 610 & 612. | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-08-06 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-08-06 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-08-06 |
Time |
06:49 |
Sent To |
|
|
Notes |
2016-08-06 08:11:31 | 1) THE PLANS LIST THIS AS A "B" OCCUPANCY. THIS IS AN | | A-3 OCCUPANCY PER CHAPTER 3 OF 2014 FBC. | | 2) A SERVICE SINK IS REQD. PER TABLE 403.1 OF 2014 FBC. | | 3) SUBMIT EXPANDED SANITARY AND WATER RISERS FOR | | REVIEW. IT IS DIFFICULT TO REVIEW THE RISERS AS DRAWN. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 4) IDENTIFY ON THE PLANS THE USE OF THE PREP SINK.WPB | | AMEND. TO FBC SEC. 107.2.1. | | 5) THE SINK LOCATED AT THE FRONT DESK SHALL COMPLY WITH | | THE FBC - ACCESS. SEC. 212 7 606. | | 6) IF THIS IS A CHANGE OF OCCUPANCY THE LAVATORIES | | SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014 | | FBC PLUMBING SEC. 607.1. | | 7) SUBMIT ENLARGED FLOOR PLANS FOR THE TOILET ROOMS AND | | SHOWERS.THE SHOWERS, SEATS, CONTROLS, GRAB BARS SHALL | | COMPLY WITH 2014 FBC-ACCESS. SECS.608, 610 & 612. | | 8) THE SAUNA SHALL COMPLY WITH 2014 FBC-ACCESS. | | SEC.612. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2017-02-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2017-02-23 |
Time |
14:22 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2017-02-23 |
Time |
14:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2016-12-28 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-12-28 |
Time |
16:29 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2016-12-28 |
Time |
16:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2016-11-22 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-11-22 |
Time |
17:14 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2016-11-22 |
Time |
17:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2016-07-26 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2016-07-26 |
Time |
11:53 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2016-07-26 |
Time |
11:53 |
Sent To |
|
|
Notes |
2016-07-26 11:54:31 | SIGNS REQUIRE SEPARATE PERMIT WITH PLANS. | | | | PLEASE NOTE THAT IT APPEARS THERE ARE MORE SIGNS THAN | | ARE PERMITTED BY THE CITY'S SIGN REGULATIONS. |
|
|