Plan Review Details - Permit 16070628
Plan Review Stops For Permit 16070628
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-02-14 Cont ID  
Sent By jwitmer Date 2017-02-14 Time 11:49 Rev Time 0.00
Received By jwitmer Date 2017-02-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-01-04 Cont ID  
Sent By shill Date 2017-01-04 Time 15:20 Rev Time 0.00
Received By shill Date 2017-01-04 Time 15:20 Sent To  
Notes
2017-01-04 15:22:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 109, VALUE IS TOO LOW. PROVIDE AN ACCURATE
 VALUE. THIS MAY BE PROVIDED VIA EMAIL.
  
 2. APPLICANT WAS INSTRUCTED TO INCLUDE THE CHANGE OF
 OCCUPANCY PERMIT NUMBER FOR THIS SPACE. WITHOUT THIS
 INFORMATION, IT IS NOT POSSIBLE TO DETERMINE WHAT
 REQUIREMENTS APPLY, AND IT IS NOT POSSIBLE TO CONTACT
 IMPACT FEE DEPARTMENT TO DETERMINE WHETHER OR NOT
 IMPACT FEE ASSESSMENT IS REQUIRED.
  
 AFTER SEARCHING FOR SOME TIME THROUGH MULTIPLE PERMITS,
 I HAD LOCATED THE PERMIT NUMBER (SCOPE PER APPLICANT)
 AND PROVIDED THIS OVER THE TELEPHONE. APPLICANT WAS TO
 INCLUDE THIS ON THE PLAN. I WAS UNABLE TO LOCATE THIS
 INFORMATION; IF IT IS ON THE PLAN, PLEASE PROVIDE
 LOCATION.
  
 DUE TO THE LARGE NUMBER OF PERMITS FOR THIS PARCEL, MY
 UNFAMILIARITY WITH THE SITE AND THE UNITS, AND MORE
 THAN ONE CHANGE OF OCCUPANCY PERMIT FOR THE SPACE, IT
 IS IMPOSSIBLE FOR ME TO OBTAIN THIS INFORMATION AS I'D
 ONLY BE GUESSING WHICH PERMIT PERTAINS TO THIS UNIT.
 THE DESIGNER OF RECORD IS REQUIRED TO DO THIS RESEARCH,
 INCLUDE THE INFORMATION ON THE PLAN (3RD REQUEST), AND
 A REVIEW IS DONE ON THE INFORMATION PROVIDED.
  
 3. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED. THIS IS TO SHOW ALL MECHANICAL EQUIPMENT.
 PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE, ALL OUTDOOR
 EQUIPMENT ANCHORING, INCLUDING ROOFTOP EQUIPMENT.
  
 THE PLAN INCLUDES A NOTE REGARDING ACCESSIBILITY FOR
 EACH TYPE OF EQUIPMENT, BUT THE PLAN IS NOT COMPLIANT.
 EITHER REVISE THE PLAN TO SHOW COMPLIANCE, OR THIS
 PERMIT WILL BE ISSUED WITH PROVISO THAT A REVISION IS
 REQUIRED PRIOR TO C.O.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-11-18 Cont ID  
Sent By shill Date 2016-11-18 Time 11:27 Rev Time 0.00
Received By shill Date 2016-11-17 Time 18:02 Sent To  
Notes
2016-11-18 11:27:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070628
 ADD: 2223 PALM BEACH LAKES BLVD.
 CONT: BRETT DROUIN
 TEL: 561-745-6785
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTE THAT A RESPONSE LETTER WAS NOT SUBMITTED AS
 REQUESTED. A LIST OF SHEETS REVISED WAS PROVIDED, BUT
 NO EXPLANATION AS TO HOW THESE ITEMS WERE ADDRESSED. IT
 IS RECOMMENDED THAT APPLICANT CONFIRM THAT ALL COMMENTS
 HAVE BEEN ADDRESSED PRIOR TO SUBMITTAL.
  
 COMMENTS FROM PREVIOUS LIST:
  
 1) SHEET A-1 CODE SUMMARY, OCCUPANCY GROUP LISTS THIS
 OCCUPANCY TYPE AS A BUSINESS OCCUPANCY. PLEASE SEE THE
 2014 FBC-B 303.4 ASSEMBLY GROUP A-3 GYMNASIUMS (WITHOUT
 SPECTATOR SEATING).
  
 2ND REVIEW, A1 STATES THIS IS BUSINESS (SAME BOX AS
 WIND DESIGN CRITERIA).
  
 2) THE DESIGNER OF RECORD INDICATES THIS IS A LEVEL II
 ALTERATION. PLEASE PROVIDE WHERE THESE LAST KNOWN USES
 OCCUPIED WHICH PORTION OF THE BUILDING TO DETERMINE IF
 THERE IS A CHANGE OF OCCUPANCY FOR THE LOCATION OF THE
 GYMNASIUM.
 2A) ALAN WELLS COMMERCIAL REAL ESTATE/ BUSINESS TAX
 LICENSE ACTIVE UNTIL 9/30/2016
 2B) WEST PALM BEACH EVENT HALL # 1/ / BUSINESS TAX
 LICENSE ACTIVE UNTIL 9/30/2016
  
 DEPENDING ON THE LOCATION THERE MAY BE A CHANGE OF
 OCCUPANCY. AT LEAST THERE IS A CHANGE OF USE WITHIN THE
 SAME OCCUPANCY TYPE.
 2014 FBC-B 1012.1. THE PROVISIONS OF THIS SECTION SHALL
 APPLY TO BUILDINGS OR PORTIONS THEREOF UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP. SUCH BUILDINGS SHALL ALSO
 COMPLY WITH SECTIONS 1002 THROUGH 1011. THE APPLICATION
 OF REQUIREMENTS FOR THE CHANGE OF OCCUPANCY SHALL BE AS
 SET FORTH IN SECTIONS 1012.1.1 THROUGH 1012.1.4.
  
 2ND REVIEW, NOT ADDRESSED. THE REQUESTED INFORMATION
 WAS NOT PROVIDED. THE OUTLINE OF THE BUILDING WITH AN
 AREA HIGHLIGHTED WAS PROVIDED. IT DOES NOT PROVIDE THE
 INFORMATION REQUESTED: ALAN WELLS, EVENT HALL
 LOCATIONS, WHAT WAS IN THIS SPACE BEFORE IF IT WAS
 NEITHER OF THESE? IT IS LIKELY THAT THIS IS A CHANGE OF
 OCCUPANCY, SO THE PREVIOUS LEGAL USE SHOULD BE
 DETERMINED, PLANS REVISED TO INCLUDE THIS INFORMATION,
 AS WELL AS SHOW COMPLIANCE WITH CHANGE OF OCCUPANCY, IF
 APPLICABLE.
  
 3, 4, 5) OK
  
 6) IN THE CARDIO AREA THERE SEEMS TO BE NO AREA FOR AN
 ACCESS AISLE. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B
 1028.9.2 AISLE WIDTH. THE AISLE WIDTH SHALL PROVIDE
 SUFFICIENT EGRESS CAPACITY FOR THE NUMBER OF PERSONS
 ACCOMMODATED BY THE CATCHMENT AREA SERVED BY THE AISLE.
 THE CATCHMENT AREA SERVED BY AN AISLE IS THAT PORTION
 OF THE TOTAL SPACE THAT IS SERVED BY THAT SECTION OF
 THE AISLE. IN ESTABLISHING CATCHMENT AREAS, THE
 ASSUMPTION SHALL BE MADE THAT THERE IS A BALANCED USE
 OF ALL MEANS OF EGRESS, WITH THE NUMBER OF PERSONS IN
 PROPORTION TO EGRESS CAPACITY.
  
 2ND REVIEW, IT IS NOT CLEAR HOW THIS HAS BEEN
 ADDRESSED. THE EQUIPMENT PLAN SHOWS EQUIPMENT DENSELY
 LOCATED, WITH LITTLE ROOM PROVIDED FOR OCCUPANT EGRESS.
 REVISE PLAN TO SHOW THE CLEAR WIDTH OF AREAS FOR
 EGRESS. ALSO, THE LACK OF SPACE BETWEEN EQUIPMENT
 APPEARS TO SHOW LACK OF COMPLIANCE WITH FBC
 ACCESSIBILITY 236, 1004.
  
 7) OK
  
 8) OK
  
 9) OK WITH PROVISO; IF MECHANICAL REVIEW DETERMINES
 THAT NEW EQUIPMENT IS REQUIRED, PROVIDE ANCHORING,
 STAND OR CURB DETAILS.
  
 10) THE PLANS NEED TO GO TO PALM BEACH COUNTY IMPACT
 FEE OFFICE FOR REVIEW. BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 THIS MAY BE DONE AFTER ALL PLAN REVIEWS HAVE PASSED,
 BUT BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 NEW COMMENTS:
  
 12. SEE NFIP REVIEW. AS DESIGN TO RESIST FLOOD LOADS IS
 A REQUIREMENT OF THE BUILDING CODE (FBC B 1612), REVISE
 THE PLAN TO SHOW COMPLIANCE. OPTIONS WERE SENT VIA
 EMAIL TO OWNER'S REP ON 10/13/16. APPLICANT MAY SEND
 INFORMATION FOR PRELIMINARY REVIEW (SUCH AS ELEVATION
 CERTIFICATE, APPRAISAL) VIA EMAIL PRIOR TO
 RESUBMITTING.
  
 13. EXERCISE MACHINES AND EQUIPMENT ARE TO COMPLY WITH
 FBC ACCESSIBILITY 236, 1004. REVISE PLAN TO SHOW
 COMPLIANCE. NOTE THAT THIS WOULD HAVE BEEN A PROVISO
 ITEM HAD ALL OTHER BUILDING COMMENTS BEEN ADDRESSED.
 HOWEVER, SINCE THE PLANS NEED TO BE REVISED TO ADDRESS
 OTHER COMMENTS FOR BOTH BUILDING AND OTHER TRADES,
 REVISE TO SHOW COMPLIANCE AT THIS TIME.
  
 14. IF IT IS DETERMINED THAT THIS PROJECT INCLUDES A
 CHANGE OF OCCUPANCY, PLAN SHOULD BE REVISED TO SHOW
 COMPLIANCE WITH FBC EXISTING BUILDING CHAPTER 10. A
 COMPLETE LIST CANNOT BE PROVIDED DUE TO LACK OF
 INFORMATION. FOR INSTANCE, SEE FBC EXISTING BUILDING
 TABLE 1012.4. IF THIS WAS BUSINESS, AND ASSEMBLY IS
 PROPOSED, THE MEANS OF EGRESS SHALL COMPLY WITH FBC
 CHAPTER 10 AS ASSEMBLY IS A HIGHER CATEGORY. IN THAT
 CASE, PANIC OR FIRE EXIT HARDWARE IS REQUIRED FOR ALL
 DOORS IN THE MEANS OF EGRESS. EXTERIOR DOORS, IF THEY
 DO NOT INCLUDE PANIC DEVICES, WOULD BE REQUIRED TO BE
 REPLACED.
  
 THIS LIST CANNOT BE COMPLETE AS IT IS NOT POSSIBLE TO
 DO A COMPLETE REVIEW WITHOUT FIRST DETERMINING THE
 PREVIOUS LEGAL OCCUPANCY.
  
 15. SEE FLORIDA STATUTE 553.80 (2) (B), AND NOTE IN
 PARTICULAR THE LANGUAGE "SHALL" (RATHER THAN "MAY"):
  
 (B) WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 SAMANTHA HILL (FOR JIM WITMER)
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6724, FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By jwitmer Date 2016-07-28 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2016-07-28 Time 06:48 Sent To  
Notes
2016-07-28 09:56:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070628
 ADD: 2223 PALM BEACH LAKES BLVD.
 CONT: BRETT DROUIN
 TEL: 561-745-6785
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 28/2016
 ACTION: DENIED
  
 1) SHEET A-1 CODE SUMMARY, OCCUPANCY GROUP LISTS THIS
 OCCUPANCY TYPE AS A BUSINESS OCCUPANCY. PLEASE SEE THE
 2014 FBC-B 303.4 ASSEMBLY GROUP A-3 GYMNASIUMS (WITHOUT
 SPECTATOR SEATING).
  
 2) THE DESIGNER OF RECORD INDICATES THIS IS A LEVEL II
 ALTERATION. PLEASE PROVIDE WHERE THESE LAST KNOWN USES
 OCCUPIED WHICH PORTION OF THE BUILDING TO DETERMINE IF
 THERE IS A CHANGE OF OCCUPANCY FOR THE LOCATION OF THE
 GYMNASIUM.
 2A) ALAN WELLS COMMERCIAL REAL ESTATE/ BUSINESS TAX
 LICENSE ACTIVE UNTIL 9/30/2016
 2B) WEST PALM BEACH EVENT HALL # 1/ / BUSINESS TAX
 LICENSE ACTIVE UNTIL 9/30/2016
  
 DEPENDING ON THE LOCATION THERE MAY BE A CHANGE OF
 OCCUPANCY. AT LEAST THERE IS A CHANGE OF USE WITHIN THE
 SAME OCCUPANCY TYPE.
 2014 FBC-B 1012.1. THE PROVISIONS OF THIS SECTION SHALL
 APPLY TO BUILDINGS OR PORTIONS THEREOF UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION. THIS INCLUDES A
 CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS
 WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE
 GROUP TO A DIFFERENT GROUP. SUCH BUILDINGS SHALL ALSO
 COMPLY WITH SECTIONS 1002 THROUGH 1011. THE APPLICATION
 OF REQUIREMENTS FOR THE CHANGE OF OCCUPANCY SHALL BE AS
 SET FORTH IN SECTIONS 1012.1.1 THROUGH 1012.1.4.
 3) SHEET A-3 SHOWS AN ADJACENT TENANT SPACE AND A ROOM
 THAT ENCROACHES PAST THE TENANT SEPARATION WALL THAT
 ALSO INDICATES THIS ROOM IS EXISTING ADJACENT SPACE.
 PLEASE PROVIDE WHICH SECTION OF THE CODE THE DESIGNER
 IS GOING TO COMPLY WITH 2014 FBC-EXISTING BUILDING:
 1012.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT
 SEPARATION.
 1012.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION.
  
 4) SHEET A-5 INDICATES THE OCCUPANT LOADS, NO EQUIPMENT
 IS LISTED AS 2,295.9 SQ. FT. AN OCCUPANT LOAD OF 154
 OCCUPANTS. NOTE THERE ARE NO DECIMAL POINTS FOR
 OCCUPANTS YOU ALWAYS ROUND UP TO THE NEXT FULL NUMBER,
 WE DON?T HAVE PARTS OF OCCUPANTS THEY ARE ALWAYS TAKEN
 AS A WHOLE NUMBER. THE ISSUE IS THE AREA WITH EQUIPMENT
 IS SHOWN AS 1,0722.3 SQ. FT. AND AN OCCUPANT LOAD OF
 215 OCCUPANTS. HOW CAN THE AREA WITH EQUIPMENT HAVE A
 LESS OCCUPANT LOAD. DISCREPANCY IN PLANS, IT APPEARS
 THERE IS A TYPO, PLEASE CORRECT THE SQUARE FOOTAGE TO,
 10,722.3 SQ. FT. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 5) SHEET A-5 AT THE FRONT ENTRY THERE IS A BUSINESS
 COUNTER, PLEASE NOTE THIS DOOR SWINGS AGAINST THE
 EGRESS FLOW. 2014 FBC-B 1008.1.2 DOORS SHALL SWING IN
 THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR
 AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 6) IN THE CARDIO AREA THERE SEEMS TO BE NO AREA FOR A
 ACCESS AISLE. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B
 1028.9.2 AISLE WIDTH. THE AISLE WIDTH SHALL PROVIDE
 SUFFICIENT EGRESS CAPACITY FOR THE NUMBER OF PERSONS
 ACCOMMODATED BY THE CATCHMENT AREA SERVED BY THE AISLE.
 THE CATCHMENT AREA SERVED BY AN AISLE IS THAT PORTION
 OF THE TOTAL SPACE THAT IS SERVED BY THAT SECTION OF
 THE AISLE. IN ESTABLISHING CATCHMENT AREAS, THE
 ASSUMPTION SHALL BE MADE THAT THERE IS A BALANCED USE
 OF ALL MEANS OF EGRESS, WITH THE NUMBER OF PERSONS IN
 PROPORTION TO EGRESS CAPACITY.
  
 7) THE PLANS SHEET A-5 SHOW EXITS LIGHTS HUNG FROM THE
 CEILING BUT NO MENTION OF COMPLIANCE WITH THE 2014
 FBC-B 1011.4 RAISED CHARACTER AND BRAILLE EXIT SIGNS. A
 SIGN STATING EXIT IN RAISED CHARACTERS AND BRAILLE AND
 COMPLYING WITH ICC A117.1 SHALL BE PROVIDED ADJACENT TO
 EACH DOOR TO AN AREA OF REFUGE, AN EXTERIOR AREA FOR
 ASSISTED RESCUE, AN EXIT STAIRWAY, AN EXIT RAMP, AN
 EXIT PASSAGEWAY AND THE EXIT DISCHARGE. ALSO SEE
 SIGNAGE REQUIREMENTS UNDER THE FBC-ACCESS. CODE SECTION
 703.
  
 8) THE PLANS DO NOT INCLUDE ANY HEIGHTS OR ELEVATIONS
 FOR SERVICE COUNTERS SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 9) ADDITIONAL COMMENTS MAY OCCUR DUE TO THE MECHANICAL
 REVIEW AND ANY ADDITIONAL MECHANICAL ROOFTOP EQUIPMENT
 THAT MAYBE REQUIRED. 2014 FBC-M- 301.15 WIND
 RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
  
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 10) THE PLANS MAY NEED TO GO TO PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR REVIEW. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-25 Cont ID  
Sent By vperez Date 2017-01-25 Time 09:19 Rev Time 0.00
Received By vperez Date 2017-01-25 Time 09:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-11-17 Cont ID  
Sent By vperez Date 2016-11-17 Time 16:18 Rev Time 0.00
Received By vperez Date 2016-11-17 Time 16:11 Sent To  
Notes
2016-11-17 16:19:17PROVISO= DRINKING FOUNTAIN AND BATH/LOCKERS RECEPTACLES
 TO BE GFCI PROTECTED.
 PROVIDE EM PHOTOMETRICS PER FIRE COMMENTS
  
 VAL PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By vperez Date 2016-07-21 Time 12:45 Rev Time 0.00
Received By vperez Date 2016-07-21 Time 12:44 Sent To  
Notes
2016-07-21 13:03:01INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE
 PERMITS FOR ALL LOW VOLTAGE SYSTEMS AND SIGNAGE SHOWN
 ON PLANS. FBC 107.3
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING AUTOMATIC
 MEANS OF LIGHTING CONTROLS, BRANCH VOLTAGE DROP AND
 COMPLETIONS DOCUMENTS.
 3. LABEL ALL RECEPTACLES IN LOCKERS AREAS TO BE GFCI
 PROTECTED NEC 210.8B
 4. PROVIDE A SYMBOLS LEGEND FOR ALL DEVICES SHOWN. FBC
 107.3.5
 5. PROVIDE EQUIPMENT SCHEDULE FOR DRYERS, WATER HEATERS
 TO VERIFY 3 PHASE VOLTAGE LOADS
 6. CLARIFY IF ABOVE MOUNTED W/H ARE IN A DROP CEILING,
 JUST NEED CLARIFICATION.
 7. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-02-21 Cont ID  
Sent By wjolin Date 2017-02-21 Time 10:00 Rev Time 0.00
Received By wjolin Date 2017-02-21 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-01-19 Cont ID  
Sent By pleduc Date 2017-01-19 Time   Rev Time 0.00
Received By pleduc Date 2017-01-19 Time 12:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-11-10 Cont ID  
Sent By wjolin Date 2016-11-10 Time 10:32 Rev Time 0.00
Received By wjolin Date 2016-11-10 Time 10:17 Sent To  
Notes
2016-11-10 10:32:282223 PALM BEACH LAKES BOULEVARD
 PERMIT #16070628
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: THE NORTH GATE OF THE FRONT
 ENTRANCE/FRONT DESK AREA SWINGS AGAINST THE FLOW OF
 EGRESS. GATES SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 REPEAT COMMENT: OVER THE YEARS, EMERGENCY LIGHTING HAS
 BEEN INSTALLED AND REMOVED FROM THIS SUITE. PROVIDE AN
 ELECTRICAL PHOTOMETRICS PLAN SHOWING AT LEAST 1-FT
 CANDLE IS BEING PROVIDED ALONG ALL EGRESS PATHS.
  
 REPEAT COMMENT: THE ONLY FLOORING MATERIAL INDICATED IN
 THIS SPACE IS THE "TURF" AREA. PROVIDE PRODUCT DATA FOR
 THIS MATERIAL. FLOORING SHALL BE AT LEAST CLASS I. PER
 NFPA 10.2.7.4 CLASS I INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.45 W/CM2.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By wjolin Date 2016-07-22 Time 11:42 Rev Time 0.00
Received By wjolin Date 2016-07-22 Time 10:57 Sent To  
Notes
2016-07-22 11:42:072223 PALM BEACH LAKES BOULEVARD
 PERMIT #16070628
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THIS IS A BUSINESS OCCUPANCY;
 HOWEVER, THE LIFE SAFETY CODE WILL CLASSIFY THIS
 OCCUPANCY AS AN ASSEMBLY.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE NORTH GATE OF THE FRONT ENTRANCE/FRONT DESK AREA
 SWINGS AGAINST THE FLOW OF EGRESS. GATES SHALL BE
 EQUIPPED WITH PANIC HARDWARE.
  
 THE EXISTING DOUBLE DOORS EQUIPPED WITH MAG-LOCKS
 INDICATE "EXIST LOCK." THESE DOORS SHALL FEATURE
 OBVIOUS SIGNAGE INDICATING "NOT AN EXIT."
  
 OVER THE YEARS, EMERGENCY LIGHTING HAS BEEN INSTALLED
 AND REMOVED FROM THIS SUITE. PROVIDE AN ELECTRICAL
 PHOTOMETRICS PLAN SHOWINGAT LEAST 1-FT CANDLE IS BEING
 PROVIDED ALONG ALL EGRESS PATHS.
  
 WHAT TYPE OF WALL FINISHES ARE INTENDED TO BE
 INSTALLED?
  
 THE ONLY FLOORING MATERIAL INDICATED IN THIS SPACE IS
 THE "TURF" AREA. PROVIDE PRODUCT DATA FOR THIS
 MATERIAL. FLOORING SHALL BE AT LEAST CLASS I. PER NFPA
 10.2.7.4 CLASS I INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.45 W/CM2.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-02-28 Cont ID  
Sent By ccole Date 2017-02-28 Time 07:48 Rev Time 0.00
Received By ccole Date 2017-02-24 Time 14:48 Sent To  
Notes
2017-02-27 14:48:45RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-23 Cont ID  
Sent By cpuell Date 2017-02-23 Time 14:44 Rev Time 0.00
Received By cpuell Date 2017-02-07 Time 14:43 Sent To  
Notes
2017-02-08 14:44:17B36

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-25 Cont ID  
Sent By vperez Date 2017-01-25 Time 09:19 Rev Time 0.00
Received By vperez Date 2017-01-25 Time 09:19 Sent To  
Notes
2016-12-22 16:24:06B39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-28 Cont ID  
Sent By gjohnson Date 2016-11-28 Time 09:57 Rev Time 0.00
Received By gjohnson Date 2016-11-04 Time 09:26 Sent To  
Notes
2016-11-07 09:26:41B38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-06 Cont ID  
Sent By tklarge Date 2016-08-06 Time 08:13 Rev Time 0.00
Received By tklarge Date 2016-07-18 Time 13:27 Sent To  
Notes
2016-07-18 13:27:54B38

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-02-14 Cont ID  
Sent By jwitmer Date 2017-02-14 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2017-02-14 Time 11:27 Sent To  
Notes
2017-02-14 11:29:41PALM BEACH COUNTY IMPACT FEE OFFICE:
 MU-2017-000648-0000
 NO FEES DUE
 JAN. 10/ 2017
 J. W.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By jwitmer Date 2016-07-28 Time 09:56 Rev Time 0.00
Received By jwitmer Date 2016-07-28 Time 09:56 Sent To  
Notes
2016-07-28 09:57:00IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2017-02-28 Cont ID  
Sent By ccole Date 2017-02-28 Time 07:48 Rev Time 0.00
Received By ccole Date 2017-02-28 Time 07:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2017-02-22 Cont ID  
Sent By ccole Date 2017-02-22 Time 14:41 Rev Time 0.00
Received By ccole Date 2017-02-22 Time 14:41 Sent To  
Notes
2017-02-22 14:54:555TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16070628
 2/22/17
  
 1) THE REAR EGRESS CORRIDOR SHALL NOT BE USED AS A
 RETURN AIR DUCT PER SECTION 601.2. PLEASE REMOVE THE
 TRANSFER GRILLS AND PROVIDE DUCTED RETURNS FROM THE
 AEROBICS, SPINNING, AND BREAK ROOMS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-02-10 Cont ID  
Sent By ccole Date 2017-02-10 Time 08:03 Rev Time 0.00
Received By ccole Date 2017-02-09 Time 14:53 Sent To  
Notes
2017-02-10 08:08:294TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16070628
 2/9/17
  
 1) THE NEW 48X16 RETURN TRANSFER FROM THE AEROBICS ROOM
 TO THE EGRESS CORRIDOR IS PROHIBITED PER SECTION 601.2.
  
 2) AS PREVIOUSLY REQUESTED PROVIDE AN AIR DEVICE
 SCHEDULE LISTING THE MAKES AND MODELS OF ALL NEW AND
 EXISTING AIR DEVICES.
  
 3) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SMACNA HVAC DUCT CONSTRUCTION STANDARDS 2005.
  
 4) PLACE A NOTE ON THE PLANS IN ACCORDANCE WITH SECTION
 C408.2.2 TO INDICATE THE SYSTEMS WILL BE TESTED AND
 BALANCED BY EITHER A LICENSED ENGINEER OR AN INDIVIDUAL
 HOLDING A CURRENT CERTIFICATION FROM A RECOGNIZED
 TESTING AND BALANCING AGENCY ORGANIZATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-12-29 Cont ID  
Sent By ccole Date 2016-12-29 Time 11:35 Rev Time 0.00
Received By ccole Date 2016-12-29 Time 11:35 Sent To  
Notes
2016-12-29 11:43:303RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16070628
 12/18/16
  
 1) THE OUTDOOR AIR CALCULATIONS ARE INCORRECT PER TABLE
 403.3 AND ASHRAE 62.1-2010. THE HEALTH GYM, AEROBICS
 ROOM, AND SPIN ROOM SHALLL BE CALCULATED AT 40 PERSONS
 PER 1000 SF.
  
 2) BASED ON THE O/A CALCULATIONS ENERGY RECOVERY
 SYSTEMS MUST BE INSTALLED FOR RTU'S 2 & 3- REFER TO
 TABLE C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE
 REVISE THE PLANS ACCORDINGLY.
  
 3) PLEASE CORRELATE THE IDENTIFICATION NUMBERS OF THE
 RTU'S IN THE SXCHEDULE TO MATCH THE PLANS.
  
 4) PROVIDE AN AIR DEVICE SCHEDULE FOR BOTH THE NEW AND
 EXISTING DIFFUSERS AND GRILLS. IT APPEARS THAT THE
 EXISTING SUPPLY DIFFUSERS FOR THE RTU'S SERVING THE GYM
 ARE UNDERSIZED FOR THE SPECIFIED CFMS. PLEASE PROVIDE
 MANUFACTURER'S ENGINEERING DATA FOR THE EXISTING
 DIFFUSERS THAT INDICATES THE CFM CAPACITIES BASED ON
 THE PRESSURE LOSS OF THE SYSTEMS AND FACE VELOCITIES.
  
 5) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS NOT
 PROVIDED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-11-10 Cont ID  
Sent By ccole Date 2016-11-10 Time 16:17 Rev Time 0.00
Received By ccole Date 2016-11-10 Time 16:17 Sent To  
Notes
2016-11-10 16:44:412ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070628
 11/10/16
  
 1) REVISE THE EXISTING EQUIPMENT SCHEDULE TO INCLUDE
 THE TOTAL SUPPLY CFMS FOR EACH RTU.
  
 2) SHOW THE RETURN DUCT SIZES FROM THE AEROBICS ROOM,
 SPINNING ROOM, AND BREAKROOM, AND THE POINTS OF
 CONNECTION TO THE MAIN RETURN TRUNK AND TRUNK SIZE.
  
 3) THERE ARE LARGE OPEN AREAS IN THE HEALTH GYM
 INCLUDING THE FRONT DESK WHERE NO AC AIR DISTRIBUTION
 IS SHOWN ON THE PLANS. HOW ARE THESE AREAS BEING
 CONDITIONED AND SUPPLIED WITH O/A IN ACCORDANCE WITH
 THE CALCULATIONS? A) SHOW THE ENTIRE DUCT LAYOUTS FOR
 RTU-2 & 3 WITH DUCT, DIFFUSER AND RETURN GRILL SIZES
 SHOWN, AND THE SUPPLY CFMS AT EACH DIFFUSER INDICATED.
  
 4) THERE ARE 3 EXISTING FANS IN THE HEALTH GYM SHOWN ON
 THE PLAN. CLARIFY THE PURPOSE OF THE FANS AND PROVIDE
 INFORMATION INCLUDING THE MAKES AND MODELS, CFM
 CAPACITIES AND THEIR INDIVIDUAL CONTROL OPERATIONS.
  
 5) THE PROJECT IS NOW BEING CLASSIFIED AS A "CHANGE OF
 OCCUPANCY" PER THE NEW NOTE ON SHEET A-1. REFER TO
 SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND PROVIDE
 ENERGY CALCULATIONS- SEE SECTION C401.2 FOR COMPLIANCE
 PATH OPTIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By ccole Date 2016-07-21 Time 14:18 Rev Time 0.00
Received By ccole Date 2016-07-21 Time 14:18 Sent To  
Notes
2016-07-21 14:58:171ST REVIEW MECHANICAL, EXISTING BUILDING CODES.
 PERMIT #16070628
 7/21/16
  
 1) SHEET ME-1: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. IDENTIFY ALL ROOMS AND SPACES ON THE
 PLANS AND PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE
 THAT THIS IS NOT A BUSINESS OCCUPANCY AS INDICATED ON
 NTHE FLOOR PLAN NOTE- THIS IS AN A3 ASSEMBLY OCCUPANCY
 PER SECTION 303.4 FBC-14 BUILDING.
  
 2) ME-1: REFER TO TABLE 403.3 AND PROVIDE EXHAUST
 VENTILATION CALCULATIONS FOR THE ALTERED AND MEN'S AND
 WOMEN'S TOILET AND LOCKER ROOMS.
  
 3) ME-1: THE AC DRAWINGS ARE INCOMPLETE. A) SHOW THE AC
 SUPPLY AND EXHAUST DUCT RUNS, DIFFUSERS AND GRILLS IN
 THE TOILET POOMS, THE LOCKER ROOMS, B) SHOW POINTS OF
 CONNECTIONS FOR NEW BRANCH DUCTS TO EXISTING TRUNKS. C)
 PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING AC SYSTEMS
 AND SHOW THEIR LOCATIONS ON THE PLANS.
  
 4) ME-1: THE RETURN DUCT SIZES FROM THE AEROBICS AND
 BREAKROOM ARE NOT SHOWN.
  
 5) ME-1: INDICATE THE SUPPLY CFMS AT THE BREAKROOM
 DIFFUSER.
  
 6) ME-1: THE 12" DUCT SUPPLYING 1250 CFMS OF AIR TO THE
 AEROBICS ROOM IS UNDERSIZED PER ASHRAE/ACCA APPROVED
 DUCTULATOR- MINI,UM 16" REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2017-01-04 Cont ID  
Sent By shill Date 2017-01-04 Time 15:33 Rev Time 0.00
Received By shill Date 2017-01-04 Time 15:33 Sent To  
Notes
2017-01-04 15:33:49****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED. THIS IS TO SHOW ALL MECHANICAL EQUIPMENT.
 PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE, ALL OUTDOOR
 EQUIPMENT ANCHORING, INCLUDING ROOFTOP EQUIPMENT,
 REQUIRED.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2016-11-17 Cont ID  
Sent By shill Date 2016-11-17 Time 18:03 Rev Time 0.00
Received By shill Date 2016-11-17 Time 18:02 Sent To  
Notes
2016-11-17 18:04:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THIS PROJECT CONSTITUTES A SUBSTANTIAL IMPROVEMENT.
 CUMULATIVE LIFETIME IMPROVEMENTS = $477,909; PROPERTY
 APPRAISER VALUE FOR THE STRUCTURE IS $373,621.
 CUMULATIVE LIFETIME IMPROVEMENTS EXCEED 50% OF THE
 STRUCTURE'S VALUE. REFER TO EMAIL SENT ON 10/13 FOR
 FURTHER EXPLANATION AND OPTIONS.
  
 FBC 1612
  
 FOR YOUR CONVENIENCE, THE EMAIL PROVIDED THE FOLLOWING
 OPTIONS:
  
 FOR SUBSTANTIAL IMPROVEMENT DETERMINATION OUR (PRE-
 SEPTEMBER 12, 2016) ORDINANCE COUNTS CUMULATIVE
 LIFETIME IMPROVEMENTS WITH A 6" FREEBOARD. OUR
 ORDINANCE CHANGED ON SEPTEMBER 12 TO FIVE YEARS WITH A
 1' FREEBOARD.
  
 PROPERTY APPRAISER HAS A STRUCTURE VALUE OF $ 373,621
 IN 2016. THE STRUCTURE HAS $477,909 CUMULATIVE LIFETIME
 IMPROVEMENTS, WHICH EXCEEDS 50% OF THE STRUCTURE'S
 VALUE, SO THIS IS CONSIDERED A "SUBSTANTIAL
 IMPROVEMENT".
  
 THE PRELIMINARY FLOOD ZONE MAP (NOT YET ADOPTED) WILL
 LIKELY REMOVE THIS PROPERTY FROM THE SFHA, SO THAT
 LEADS ME TO BELIEVE THAT THE STRUCTURE IS PROBABLY HIGH
 ENOUGH. WE ARE NOT ALLOWED TO USE THE PRELIMINARY MAP
 FOR REGULATORY PURPOSES; THIS CAN BE USED ONLY AFTER
 ADOPTION (MOST LIKELY WITHIN THE YEAR).
  
 THERE ARE TWO OPTIONS:
  
 A. OBTAIN AN APPRAISAL WHICH WOULD NEED TO SHOW A
 SIGNIFICANTLY HIGHER VALUE FOR THE STRUCTURE. THE VALUE
 WOULD NEED TO BE OVER $955,818 TO BRING THE CUMULATIVE
 LIFETIME IMPROVEMENTS BELOW 50%. I (OR THE BUILDING
 REVIEWER) WOULD ALSO BE REQUIRED TO EVALUATION THE
 VALUE OF THE IMPROVEMENTS MORE CAREFULLY.
  
 B. A SUBSTANTIAL IMPROVEMENT REQUIRES THAT THE BUILDING
 BE BROUGHT INTO COMPLIANCE. THE DFE AT THIS LOCATION IS
 16.5' NGVD29 (16' PER FIRM PLUS 6" FREEBOARD). AN
 ELEVATION CERTIFICATE WOULD PROVIDE THE INFORMATION TO
 DETERMINE WHETHER OR NOT THE BUILDING IS ALREADY
 COMPLIANT. MY GUESS (THE "GOOD NEWS") IS THAT THE
 BUILDING MAY ALREADY BE HIGH ENOUGH. IF THE MECHANICAL
 EQUIPMENT IS NOT LOWER THAN THE FINISHED FLOOR, OR IF
 IT IS ON THE ROOF, THE BUILDING MAY BE COMPLIANT.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2016-07-28 Cont ID  
Sent By shill Date 2016-07-28 Time 14:32 Rev Time 0.00
Received By shill Date 2016-07-28 Time 14:32 Sent To  
Notes
2016-07-28 14:33:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IT APPEARS THAT THIS MAY BE A SUBSTANTIAL IMPROVEMENT.
 CUMULATIVE LIFETIME IMPROVEMENTS = $477,909; PROPERTY
 APPRAISER VALUE FOR THE STRUCTURE IS $373,621.
 CUMULATIVE LIFETIME IMPROVEMENTS EXCEED 50% OF THE
 STRUCTURE'S VALUE. REFER TO EMAIL SENT ON 10/13 FOR
 FURTHER EXPLANATION AND OPTIONS.
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-02-10 Cont ID  
Sent By gjohnson Date 2017-02-10 Time 13:54 Rev Time 0.00
Received By gjohnson Date 2017-02-10 Time 12:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-01-23 Cont ID  
Sent By gjohnson Date 2017-01-23 Time 09:23 Rev Time 0.00
Received By gjohnson Date 2017-01-23 Time 09:23 Sent To  
Notes
2017-01-23 09:30:133RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE TWO COMPLETE PLAN SETS. ONE THAT WAS
 PROVIDED IS MISSING SGN-1 ONE IS MISSING P-1. PLEASE
 CLARIFY WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE TEMPERED WATER TO ALL LAVATORY'S. PER FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-28 Cont ID  
Sent By gjohnson Date 2016-11-28 Time 09:52 Rev Time 0.00
Received By gjohnson Date 2016-11-28 Time 09:52 Sent To  
Notes
2016-11-28 09:55:402ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
  
 NOT COMPLIED 3) SUBMIT EXPANDED SANITARY AND WATER
 RISERS FOR REVIEW. IT IS DIFFICULT TO REVIEW THE RISERS
 AS DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOT COMPLIED 5) THE SINK LOCATED AT THE FRONT DESK
 SHALL COMPLY WITH THE FBC - ACCESS. SEC. 212 7 606.
 NOT COMPLIED 6) IF THIS IS A CHANGE OF OCCUPANCY THE
 LAVATORIES SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER
 PER 2014 FBC PLUMBING SEC. 607.1.
 NOT COMPLIED 7) SUBMIT ENLARGED FLOOR PLANS FOR THE
 TOILET ROOMS AND SHOWERS.THE SHOWERS, SEATS, CONTROLS,
 GRAB BARS SHALL COMPLY WITH 2014 FBC-ACCESS. SECS.608,
 610 & 612.
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-06 Cont ID  
Sent By tklarge Date 2016-08-06 Time 08:13 Rev Time 0.00
Received By tklarge Date 2016-08-06 Time 06:49 Sent To  
Notes
2016-08-06 08:11:311) THE PLANS LIST THIS AS A "B" OCCUPANCY. THIS IS AN
 A-3 OCCUPANCY PER CHAPTER 3 OF 2014 FBC.
 2) A SERVICE SINK IS REQD. PER TABLE 403.1 OF 2014 FBC.
 3) SUBMIT EXPANDED SANITARY AND WATER RISERS FOR
 REVIEW. IT IS DIFFICULT TO REVIEW THE RISERS AS DRAWN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 4) IDENTIFY ON THE PLANS THE USE OF THE PREP SINK.WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) THE SINK LOCATED AT THE FRONT DESK SHALL COMPLY WITH
 THE FBC - ACCESS. SEC. 212 7 606.
 6) IF THIS IS A CHANGE OF OCCUPANCY THE LAVATORIES
 SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014
 FBC PLUMBING SEC. 607.1.
 7) SUBMIT ENLARGED FLOOR PLANS FOR THE TOILET ROOMS AND
 SHOWERS.THE SHOWERS, SEATS, CONTROLS, GRAB BARS SHALL
 COMPLY WITH 2014 FBC-ACCESS. SECS.608, 610 & 612.
 8) THE SAUNA SHALL COMPLY WITH 2014 FBC-ACCESS.
 SEC.612.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2017-02-23 Cont ID  
Sent By eschneid Date 2017-02-23 Time 14:22 Rev Time 0.25
Received By eschneid Date 2017-02-23 Time 14:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-12-28 Cont ID  
Sent By eschneid Date 2016-12-28 Time 16:29 Rev Time 0.25
Received By eschneid Date 2016-12-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-22 Cont ID  
Sent By eschneid Date 2016-11-22 Time 17:14 Rev Time 0.25
Received By eschneid Date 2016-11-22 Time 17:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-07-26 Cont ID  
Sent By eschneid Date 2016-07-26 Time 11:53 Rev Time 0.25
Received By eschneid Date 2016-07-26 Time 11:53 Sent To  
Notes
2016-07-26 11:54:31SIGNS REQUIRE SEPARATE PERMIT WITH PLANS.
  
 PLEASE NOTE THAT IT APPEARS THERE ARE MORE SIGNS THAN
 ARE PERMITTED BY THE CITY'S SIGN REGULATIONS.