Plan Review Details - Permit 16070609
Plan Review Stops For Permit 16070609
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-11-04 Cont ID  
Sent By jgomez Date 2016-11-04 Time 14:29 Rev Time 0.00
Received By jgomez Date 2016-11-04 Time 12:29 Sent To  
Notes
2016-11-04 12:29:57 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-09-29 Cont ID  
Sent By jgomez Date 2016-09-29 Time 08:44 Rev Time 0.00
Received By jgomez Date 2016-09-28 Time 18:55 Sent To  
Notes
2016-09-29 08:47:5610/31/16
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO AFTER
 CONTRACTOR'S INFORMATION IS UPDATED. PRODUCT APPROVALS
 MAY BE SUBMITTED LATER. CONTRACTOR TO ADVICE IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- CONTRACTOR LICENSE NUMBER SHOWN ON THE PERMIT
 APPLICATION (CPC057027) IS FOR A POOL CONTRACTOR. NEED
 TO PROVIDE LICENSE OF GENERAL, BUILDING OR RESIDENTIAL
 CONTRACTOR. SEC. 489.113 FLORIDA STATUTES.
  
 RESPONSE:
 NOT ADDRESSED. NEED TO REVISE INFORMATION ON THE PERMIT
 APPLICATION TO UPDATE INFORMATION THE CITY SYSTEM.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR;
 A) ROOF TILE AS SPECIFIED ON PLANS. NOA 07-0919.05
 SUBMITTED EXPIRED ON 12/16/12. NEED CURRENT NOA.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 DETAILS AND PLANS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ARCHITECT TO LIST THE CURRENT FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
 NOTE: NOA 03-0123.05 SUBMITTED EXPIRED ON FEBRUARY 16,
 2008. NEED CURRENT NOA OR FLORIDA PRODUCT APPROVAL.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
 NOTE: NEED TO APPROVE ALL THE PRODUCT APPROVALS,
 INCLUDING THE ONES THAT WERE SUBMITTED EARLIER.
  
 4- CLARIFY WHY SUBMITTING NOA 13-1217.01 FOR FLAT ROOF
 DECKS. PLANS DON'T PROVIDE ANY SPECIFICATION FOR THIS
 TYPE OF ROOFING. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA SUBMITTED.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. PLEASE DON"T STAPLE OLD DRAWING. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By jgomez Date 2016-08-25 Time 10:04 Rev Time 0.00
Received By jgomez Date 2016-08-25 Time 09:40 Sent To  
Notes
2016-08-25 10:09:15RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- CONTRACTOR LICENSE NUMBER SHOWN ON THE PERMIT
 APPLICATION (CPC057027) IS FOR A POOL CONTRACTOR. NEED
 TO PROVIDE LICENSE OF GENERAL, BUILDING OR RESIDENTIAL
 CONTRACTOR. SEC. 489.113 FLORIDA STATUTES.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE. NOTE: THIS MAY BE
 DONE LATER WHEN THE PERMIT IS READY TO BE ISSUED
  
 3- SHEET A3:
 A) FOUNDATION PLAN IS NOT CLEAR. FOUNDATION PLAN AND
 FOOTING SCHEDULE DON'T MATCH. THE THICKENED EDGE IS NOT
 SHOWN ON THE FOUNDATION PLAN. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) FOOTING SCHEDULE IS NOT CLEAR. THE DEPTH DIMENSION
 SHOWN FOR FOOTING F1 DOESN'T MATCH THE FOOTING DEPTH
 SPECIFIED UNDER DESCRIPTION. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) SPECIFY THE SIZE OF THE TREADS ON THE TYP. STONE
 STAIR DETAIL. SEC. R311.7.5.2 FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- PROVIDE COMPLETE FRAMING DETAILS FOR THE NEW FRENCH
 DOORS WITH SIDELITES AS SHOWN ON PLANS. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- SHEET A5:
 A) SPECIFY Y CONNECTORS AT TOP AND BOTTOM OF CORNER AND
 MIDDLE COLUMNS TO SHOW THE COMPLETE LOAD PATH AS
 REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: SPECIFYING SIMPSON POST CAP AND BASE IS NOT
 ENOUGH INFORMATION. THERE ARE MANY TYPES OF CONNECTORS.
 CORNER CONNECTORS ARE DIFFERENT. ALSO, TAKE INTO
 CONSIDERATION HOW THE POST BASE IS ATTACHED TO THE
 SPECIFIED CONCRETE BLOCK COLUMN.
  
 B) CONNECTOR DETAIL "B". SPECIFY WHAT IS THIS CONNECTOR
 ATTACHED TO IN ORDER TO GET 4" MIN. EMBEDMENT. ALSO,
 SPECIFIED BOLT SEEMS TO BE FOR MASONRY APPLICATION.
 REVISE AS REQUIRED. NOTE: CONNECTION AT THE SOUTH END
 MAY NEED SPECIAL ATTENTION. THERE IS NO PARAPET WALL
 BEHIND. SEE RIGHT ELEVATION ON SHEET A4. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) THE LATERAL LOADS F1 AND F2 SHOWN ON THE SIMPSON
 CONNECTION SCHEDULE ARE INCORRECT. FROM WHERE ARE THESE
 VALUES TAKEN FROM?. REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
  
 D) INFORMATION SHOWN ON PORCH SECTION IS NOT CLEAR. (1)
 THE 2 X 12 LEDGER SPECIFIED ON THE ROOF FRAMING PLAN IS
 NOT SHOWN. (2) IT DOESN'T MATCH INFORMATION SHOWN ON
 PORCH SECTION ON SHEET A4. THE ROOF PITCH IS DIFFERENT.
 THE PARAPET AND 2X12 LEDGER INFORMATION IS DIFFERENT.
 (3) THE CONCRETE SLAB DOESN'T SHOW THE THICKENED EDGE
 OF FOOTING F2 SHOWN ON THE FOUNDATION PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 E) ATTACHMENT OF THE 2 X 12 LEDGER SHOWN ON THE ROOF
 FRAMING PLAN IS NOT CLEAR. WHAT IS THE FASTENER
 ATTACHED TO IN ORDER TO BE 16" ON CENTER AND HAVE 4"
 EMBEDMENT. SEC. R301.1 FBC-RESIDENTIAL.
  
 F) BEAM TO COLUMN DETAIL IS NOT CLEAR. (1) WOOD BEAM
 DOESN'T MATCH SIZE SPECIFIED ON ROOF FRAMING PLAN.
 (2)WHAT IS CONNECTOR "F". (3) COORDINATE WITH SPECIFIED
 POST CAP. (4) THIS IS A CORNER DETAIL. HOW ARE THE TWO
 BEAMS SEATED ON THE 6" POST. SEC. R301.1
 FBC-RESIDENTIAL.
  
 G) ROOF DESIGN CRITERIA DOESN'T MATCH DESIGN CRITERIA
 SHOWN ON PAGE A. REVISE AS REQUIRED TO MATCH. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 6- SHEET A:
 A) THE TOTAL MIN. ROOF LOAD SHOWN ON THE DESIGN
 CRITERIA IS INCORRECT. REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B) THIS IS ALTERATION LEVEL 3 NOT 2. REVISE AS
 REQUIRED. SEC. 505 FBC-EXISTING BUILDING, 5TH EDITION
 (2014).
  
 C) UPDATE WOOD NOTES #2 AND #3. THE CURRENT CODE IS THE
 FBC 5TH EDITION (2014) NOT 2010 OR 2004. SEC. 553
 FLORIDA STATUTES.
  
 7- SHEET SP1:
 A) SITE PLAN SHOWS AN EXISTING GUEST HOUSE IN THE BACK
 OF THE LOT. THIS STRUCTURE IS SUPPOSED TO BE A GARAGE.
 ACCORDING TO CITY RECORDS AND PBC PROPERTY APPRAISER
 THIS STRUCTURE IS A GARAGE NOT GUEST HOUSE. REVISE AS
 REQUIRED, INCLUDING THE AREA CALCULATIONS. IF PROPOSING
 GUEST HOUSE, THEN REVISE PLANS AS REQUIRED. PLANS WILL
 NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR IMPACT
 FEES ASSESSMENT. CONTACT ZONING TO VERIFY IF GUEST
 HOUSE IS ALLOWED. INSPECTION WILL BE REQUIRED TO VERIFY
 USE OF EXISTING STRUCTURE. SEC. 102.2 CITY AMENDMENTS.
  
 B) FOR YOUR INFORMATION: DRIVEWAYS AND FENCES REQUIRE
 SEPARATE PERMITS. PROVIDE COMPLETE INFORMATION
 SEPARATELY TO AVOID CONFLICTS/DELAYS.
  
 8- OUTLOOKERS ON RIGHT ELEVATION ON SHEET A4 ARE NOT
 CLEAR: SPACING OF THE OUTLOOKERS SHOWN DON'T MATCH
 SPACING SHOWN ON THE ROOF FRAMING PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING
 SCREWS, THEN SPECIFY NUMBER AND SIZE OF SCREWS. IF
 USING ADHESIVE, THEN PRODUCT APPROVAL IS REQUIRED.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR;
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON DETAILS AND PLANS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ARCHITECT TO LIST THE CURRENT FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. PLEASE DON"T STAPLE OLD DRAWING. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-10-31 Cont ID  
Sent By vperez Date 2016-10-31 Time 17:04 Rev Time 0.00
Received By vperez Date 2016-10-31 Time 17:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By albarran Date 2016-07-22 Time 12:13 Rev Time 0.00
Received By albarran Date 2016-07-22 Time 10:59 Sent To  
Notes
2016-07-22 12:13:30ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB NAME: ADDITION &N ALTERATION
 JOB ADDRESS: 437 29TH STREET
 DESCRIPTION: ADDITION & INTERIOR REMODEL
 MAST. PERMIT: 16070609
 REVISION:
  
 1. YOU WILL NEED TO ADD A BLOCK NOTE ADDRESSING THE
 FOLLOWING:
 A) THE ARC-FAULT REQUIREMENT OF NEC 210.12
 B) THE PADDLE FAN OUTLET BOX REQUIREMENT OF NEC 314.27
 C) THE GROUNDED CONDUCTOR REQUIREMENT FOR SWITCHES OF
 NEC 404.2
 D) THE HIGH-EFFICIENCY LAMP REQUIREMENT OF FBC-ER404.1
 2. IN THE INTEREST OF LIFE SAFETY, ENERGY CONSERVATION
 & OCCUPANT CONVENIENCE, MAY I SUGGEST THAT YOU ALSO
 INSTALL A 3W SWITCH (LIGHTING CONTROL) FROM THE DINING
 ROOM AS YOU EXIT TO THE BEDROOM CORRIDOR.
 3. THE ELECTRICAL RISER DIAGRAM SHOWS AN ?ATS? WITH NO
 INDICATION OF EXISTING OR NEW. PLEASE INDICATE IF THIS
 IS NEW OR EXISTING AND IF ITS EXISTING SHOW ON RISER
 DIAGRAM THE GENERATOR AND/OR EMERGENCY PANEL IF NOT
 SIZED FOR THE WHOLE HOUSE.
 4. YOU SHALL INCLUDE IN THE ELECTRICAL PLAN THE
 LOCATION OF ALL HVAC EQUIPMENT, ELECTRICAL PANELS AND
 METER. MECHANICAL PLANS SHOW THE AHU INSIDE THE ATTIC.
 IF THIS IS TO BE THE CASE, ALL THE REQUIRED ELECTRICAL
 SHALL ALSO BE ADDRESSED, I.E.: PROPER ILLUMINATION, THE
 REQUIRED WALL SWITCH AND GFI RECEPTACLE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2016-11-08 Cont ID  
Sent By skennedy Date 2016-11-08 Time 13:28 Rev Time 0.00
Received By skennedy Date 2016-11-08 Time 13:27 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By Mgonzale Date 2016-08-26 Time   Rev Time 1.00
Received By mgonzale Date 2016-08-26 Time   Sent To I
Notes
2016-08-26 16:55:07SEPARATE DRIVEWAY PERMIT IS REQUIRED.
  
 10' WIDE AT EACH ENTRANCE.
  
 SETBACK IS 3' FROM SIDE PROPERTY LINES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 818-1322
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-11-08 Cont ID  
Sent By skennedy Date 2016-11-08 Time 14:07 Rev Time 0.00
Received By skennedy Date 2016-11-08 Time 14:07 Sent To  
Notes
2016-09-29 08:50:51GAS DRAWING SUBMITTED. JG.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-08-12 Cont ID  
Sent By gjohnson Date 2016-08-12 Time 13:20 Rev Time 0.00
Received By gjohnson Date 2016-08-12 Time 13:20 Sent To  
Notes
2016-08-12 13:21:53GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-10-04 Cont ID  
Sent By fmittner Date 2016-10-04 Time 11:09 Rev Time 0.00
Received By fmittner Date 2016-10-04 Time 11:09 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By fmittner Date 2016-07-22 Time 09:38 Rev Time 0.00
Received By fmittner Date 2016-07-22 Time 09:38 Sent To  
Notes
2016-07-22 09:39:33REQUIRES SUBMITTAL OF COA AND APPROVAL OF HPB.
 CALLED/E-MAILED OWNER 7/22/16. QUESTIONS CONTACT
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-08 Cont ID  
Sent By skennedy Date 2016-11-08 Time 14:07 Rev Time 0.00
Received By skennedy Date 2016-09-23 Time 11:29 Sent To  
Notes
2016-09-26 11:30:09R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-14 Cont ID  
Sent By lmarchan Date 2016-09-14 Time 09:17 Rev Time 0.00
Received By lmarchan Date 2016-07-18 Time 14:26 Sent To  
Notes
2016-07-25 10:25:22R02
2016-07-18 14:26:21LIBRARY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-09-29 Cont ID  
Sent By jgomez Date 2016-09-29 Time 09:06 Rev Time 0.00
Received By jgomez Date 2016-09-29 Time 09:06 Sent To  
Notes
2016-09-29 09:06:55NO WORK ON DETACHED GARAGE. NO ADDITIONAL LIVABLE AREA
 PROPOSED. NEW COVERED LOGGIA ONLY.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-25 Cont ID  
Sent By jgomez Date 2016-08-25 Time 10:13 Rev Time 0.00
Received By jgomez Date 2016-08-25 Time 10:13 Sent To  
Notes
2016-08-25 10:14:011- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE. NOTE: THIS MAY BE DONE LATER WHEN THE PERMIT IS
 READY TO BE ISSUED
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-11-08 Cont ID  
Sent By skennedy Date 2016-11-08 Time 14:06 Rev Time 0.00
Received By skennedy Date 2016-11-08 Time 14:06 Sent To  
Notes
2016-11-08 14:06:52HISTORIC ENERGY NOT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-09-13 Cont ID  
Sent By jvalido Date 2016-09-13 Time 19:28 Rev Time 0.00
Received By jvalido Date 2016-09-13 Time 19:08 Sent To  
Notes
2016-09-13 19:11:49CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 FLORIDA ENERGY CODE FBC 2014
  
 FLORIDA ENERGY CODE - SECTION R202 RENOVATED BUILDINGS
 - A RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING
 ALTERATION THAT VARIES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
  
 (1) PROVIDE (2) SETS OF FORM R405 - 2014 - BOTH SETS
 MUST BE SIGNED BY PREPARED BY AND OWNER/AGENT.
 (2) PROVIDE (2) SETS OF HEAT LOAD CALCULATIONS.
  
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-08-12 Cont ID  
Sent By gjohnson Date 2016-08-12 Time 13:20 Rev Time 0.00
Received By gjohnson Date 2016-08-11 Time 14:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-11-08 Cont ID  
Sent By skennedy Date 2016-11-08 Time 14:07 Rev Time 0.00
Received By skennedy Date 2016-11-08 Time 14:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-09-29 Cont ID  
Sent By jgomez Date 2016-09-29 Time 13:43 Rev Time 0.00
Received By jgomez Date 2016-09-29 Time 13:43 Sent To  
Notes
2016-09-29 13:58:591- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR;
 A) ROOF TILE AS SPECIFIED ON PLANS. NOA 07-0919.05
 SUBMITTED EXPIRED ON 12/16/12. NEED CURRENT NOA.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 3- CLARIFY WHY SUBMITTING NOA 13-1217.01 FOR FLAT ROOF
 DECKS. PLANS DON'T PROVIDE ANY SPECIFICATION FOR THIS
 TYPE OF ROOFING. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA SUBMITTED.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-26 Cont ID  
Sent By jgomez Date 2016-08-26 Time 18:16 Rev Time 0.00
Received By jgomez Date 2016-08-26 Time 07:27 Sent To  
Notes
2016-08-26 18:17:291- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR;
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-04 Cont ID  
Sent By fmittner Date 2016-10-04 Time 11:09 Rev Time 0.00
Received By fmittner Date 2016-10-04 Time 11:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By fmittner Date 2016-07-22 Time 09:44 Rev Time 0.00
Received By fmittner Date 2016-07-22 Time 09:44 Sent To  
Notes
2016-07-22 09:45:12DRIVEWAY TOO WIDE. 10' MAX PER CURB CUT.