2016-07-15 15:20:03 | COMPLY WITH THE FOLLOWING REQUIREMENTS.THE |
| DOCUMENTATION THAT WAS SUBMITTED DOES NOT SHOW THE |
| DEVICE IS ON THE USC LIST OF APPROVED DEVICES.YOU |
| SUBMITTED INSTALLATION INSTRUCTIONS, NOT THE |
| MANUFACTURER'S SPECIFICATIONS. |
| DOCUMENTATION REQUIRED FOR BACKFLOW PREVENTION DEVICE |
| PERMITS |
| |
| EFFECTIVE DATE: JANUARY 4TH, 2016 |
| |
| THE PERMIT APPLICATION SHALL BE SUBMITTED WITH THE |
| FOLLOWING DOCUMENTATION: |
| |
| 1) TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR |
| THE BACKFLOW PREVENTER. THE MAKE, MODEL AND SIZE OF THE |
| DEVICE SHALL BE NOTED IN THE DESCRIPTION OF WORK |
| SECTION ON THE PERMIT APPLICATION. |
| |
| 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE. |
| |
| 3) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF |
| SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES. |
| 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO |
| CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE |
| CITY?S REQUIREMENTS. |
| 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED |
| IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND |
| CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH |
| PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO |
| ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE |
| DEVICE. |
| 6) INDICATE THE SIZE AND TYPE OF DEVICE AND SUBMIT THE |
| SPECS FOR THE DEVICE THAT WILL BE USED ON THE BYPASS. |
| NOTE: THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS |
| SHALL BE ON THE JOBSITE FOR INSPECTION |
| THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| MANUAL CAN BE FOUND AT : |
| HTTP://WPB.ORG/UTILITIES/BACKFLOW |
| UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS: |
| WWW.USC.EDU/DEPT/FCCCHR |
| |
| |
| PLUMBING PLAN REVIEW |