Plan Review Details - Permit 16070494
Plan Review Stops For Permit 16070494
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-08 Cont ID  
Sent By mvaldes Date 2016-09-08 Time 11:13 Rev Time 0.00
Received By mvaldes Date 2016-09-08 Time 10:38 Sent To  
Notes
2016-09-08 12:08:45REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PASSED WITH THE FOLLOWING PROVISO
  
 1] INSTALL GUARD POLES AT THE SERVICE EQUIPMENT
 LOCATION IN A MANNER TO PREVENT PHYSICAL DAMAGE.
 OUTDOOR ELECTRICAL EQUIPMENT SHALL BE PROTECTED FROM
 ACCIDENTAL CONTACT BY UNAUTHORTIZED PERSONNEL,
 VEHICULAR TRAFFIC, AND OTHER SYSTEM PIPING SPILLAGE OR
 LEAKAGE. NEC 110.27(B)
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By mvaldes Date 2016-07-18 Time 10:20 Rev Time 0.00
Received By mvaldes Date 2016-07-18 Time 09:26 Sent To  
Notes
2016-07-18 10:21:55JOB PERMIT NUMBER: 16070494
 JOB ADDRESS: 471 SPENCER DRIVE
 WEST PALM BEACH FLORIDA
 DATE: JULY 18 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - IN ADDITION TO THE INFORMATION PROVIDED ADD CONDUIT
 SIZES, NEMA RATING, THE GROUNDING DETAIL TO INCLUDE GEC
 SIZE, LASTLY PROVIDE A SERVICE CALCULATION TO VERIFY IF
 SUFFICIENT TO HANDLE CURRENT LOADS. FBC 107 MINIMUM
 PLAN REVIEW, NEC 250.66, NEC 110.28, NEC 220 & 215.5
 - PROVIDE "AIC" RATING OF OVERCURRENT PROTECTION
 DEVICES AND "SCR" OF ELECTRICAL EQUIPMENT. FPL FAULT
 CURRENT LETTER SHALL BE ATTACHED TO THE SUBMITTAL TO
 VERIFY THE INSTALLATION WITHSTANDS LINE TO LINE FAULTS
 IF IMPOSED ON ELECTRICAL APPARATUS. NEC 110.9 & 110.10,
 NEC 110.24
 - INSTALL ALL REQUIRED PERMANENT PLAQUES SUCH AS
 IDENTIFICATION LABEL OF EACH DISCONNECT SHOWING TENANT
 ADDRESS AND ANY ADDITIONAL DETAIL. FURTHERMORE INSTALL
 ARC FLASH WARNING LABELS AT EACH DISCONNECT AND THE
 MARKING SHALL BE SUITABLE TO THE ENVIRONMENT. NEC
 225.37, NEC 110.16
 - A SITE SPECIFIC PLAN IS REQUIRED THAT SHOWS THE
 SERVICE LOCATION PERTAINING TO THE OVERHEAD CONDUCTORS
 CLEARANCES IF RUNNING THROUGH A COMMERCIAL AREA SUBJECT
 OR NOT SUBJECT TO TRUCK TRAFFIC. NEC 230.24(B)(2) OR
 (4).
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-08 Cont ID  
Sent By mvaldes Date 2016-09-08 Time 12:31 Rev Time 0.00
Received By mvaldes Date 2016-09-01 Time 10:45 Sent To  
Notes
2016-09-02 10:45:29RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-18 Cont ID  
Sent By mvaldes Date 2016-07-18 Time 10:22 Rev Time 0.00
Received By mvaldes Date 2016-07-14 Time 13:10 Sent To  
Notes
2016-07-14 13:10:50ELECTRICAL INBOX