Plan Review Details - Permit 16070476
Plan Review Stops For Permit 16070476
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-11-08 Cont ID  
Sent By cthroop Date 2017-11-08 Time 17:13 Rev Time 0.00
Received By cthroop Date 2017-11-08 Time 17:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-10-24 Cont ID  
Sent By cthroop Date 2017-10-24 Time 12:49 Rev Time 0.00
Received By cthroop Date 2017-10-24 Time 07:04 Sent To M
Notes
2017-10-24 12:55:41BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THERE ARE THREE PLAN SHEETS LABELED A-1. PLEASE
 RE-LABEL AND RE-SUBMIT.
 2. PLANS SHOW FIXED WINDOWS. PROVIDE PRODUCT APPROVALS
 FOR THIS TYPE OF WINDOW.
 3. THE PRODUCT APPROVALS FOR THE SINGLE HUNG WINDOWS DO
 NOT HAVE A MODEL THAT COMPLIES WITH THE SIZE OF SOME
 WINDOWS ON PLAN.
 4. IDENTIFY MODEL OF WINDOWS AND DOORS TO BE USED ON
 PRODUCT APPROVALS.
 5. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH
 OPENINGS, DESIGN WIND LOADS. IDENTIFY LOCATION OF EACH
 WINDOW AND DOOR ON PLAN.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-23 Cont ID  
Sent By cthroop Date 2017-02-23 Time 09:18 Rev Time 0.00
Received By cthroop Date 2017-02-23 Time 09:18 Sent To  
Notes
2017-02-23 09:21:32BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE REINFORCING DETAIL FOR NEW BOND BEAMS.
 3. SELECT NEW IMPACT RATED WINDOWS TO BE INSTALLED FROM
 PRODUCT APPROVAL SUBMITTAL,

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 14:28 Rev Time 0.00
Received By cthroop Date 2016-08-09 Time 14:28 Sent To E
Notes
2016-08-09 14:35:54BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/9/16
  
 1. PROVIDE SITE PLAN.
 2. SCOPE OF WORK EXCEEDS DESCRIPTION ON APPLICATION.
 STRUCTURAL CONCRETE, WALLS AND ROOFING SHOWN ON PLANS.
 3. STATED VALUE MAY BE LOW.
 4. ROOFING PERMIT REQUIRED.
 5. PROVIDE RE-INFORCING DTAIL FOR NEW BOND BEAMS.
 6. DETAIL 1, PG A-4 INDICATES NEW ROOF RAFTERS. DEMO
 PLANS SHOWS NO WORK IN THIS AREA.. PLEASE CLARIFY. TO
 WHAT EXTENT IS ROOFING BEING REMOVED?
 7. PROVIDE LANDINGS AT EXTERIOR DOORS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 [A] 109.3 BUILDING PERMIT VALUATIONS.
 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED
 PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS
 SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS
 AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH
 AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND
 PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING
 PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-11-08 Cont ID  
Sent By jpearson Date 2017-11-08 Time 10:43 Rev Time 0.00
Received By jpearson Date 2017-11-08 Time 10:43 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-10-05 Cont ID  
Sent By jpearson Date 2017-10-05 Time 08:38 Rev Time 0.00
Received By jpearson Date 2017-10-05 Time 08:38 Sent To  
Notes
2017-10-05 08:38:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. KITCHEN SMALL APPLIANCE CIRCUITS PROVIDED ARE SHOWN
 AS #14 WIRE ON A 20 AMP BREAKER. THERE ARE SEVERAL
 OTHER CIRCUITS IN PANEL SCHEDULE IDENTIFIED LIKE THIS.
 PROVIDE CORRECTION. NEC 310.15(B)(16), 334.80; FBC RE
 TABLE E3702.13, TABLE E3705.5.3
 2. DISHWASHER AND DISPOSAL ARE SHOWN IN PANEL SCHEDULE
 AS #12 WIRE ON A 30 AMP BREAKER. PROVIDE CORRECTION.
 NEC 310.15(B)(16), 334.80; FBC RE TABLE E3702.13, TABLE
 E3705.5.3
 3. BREAKER FOR WATER HEATER IS STATED AS 30 AMP IN
 PANEL SCHEDULE, WHICH IS TOO LARGE FOR THIS LOAD.
 BREAKER SHOULD BE SIZED AT 125% OF THE LOAD. BASED ON
 THE 4500 WATT STATED, THIS WOULD BE A MAXIMUM BREAKER
 SIZE OF 25 AMPS. PROVIDE CORRECTION. NEC 422.13; FBC
 RE3702.10
 4. THE LOAD CALCULATION PROVIDED FOR PANEL IS
 INCORRECT. THE DEMAND FACTORS ARE NOT APPLIED TO EVERY
 LOAD IN PANEL. PROVIDE CORRECTED LOAD CALCULATION AS
 PER THE FBC RESIDENTIAL CODE, SECTION E3602.2. INCLUDE
 ALL LOADS IN THIS CALCULATION. THE CURRENT PANEL
 SCHEDULE SHOWS ONLY 1 AHU/AC SYSTEM. NEC 220, FBC RE
 3602.2
 5. THE RISER DIAGRAM PROVIDED HAS CONFLICTING
 INFORMATION. IT SHOWS A FEED TO A DISCONNECT AND THEN
 TO PANEL A WITH 2/0 WIRE. IT ALSO SHOWS A FEED DIRECTLY
 FROM METER TO PANEL A WITH #1 WIRE. CLARIFY AND/OR
 CORRECT. ADDITIONALLY, IF USING A MAIN DISCONNECT AS
 DRAWN, THE WIRING FROM THE DISCONNECT TO PANEL A
 REQUIRES AN EQUIPMENT GROUNDING CONDUCTOR. REFLECT ALL
 CORRECTED INFORMATION ON POWER PLAN AS WELL, IT
 CURRENTLY ONLY SHOWS A PANEL, NO DISCONNECT OR METER
 CAN. PROVIDE CORRECTION. NEC 250.122; FBC 107.2.1; FBC
 RE 3704.6
 6. PROVIDE CORRECTED NOTES AS FOLLOWS: "ALL RECEPTS. TO
 BE TAMPER PROOF AS PER NEC 2010 SEC 406.11". THE 2010
 NEC DOES NOT EXIST AND SECTION 406.11 IN THE CURRENT
 CODE, THE 2011 NEC, DOES NOT APPLY TO TR RECEPTACLES.
 ALSO; "ELECTRICAL CONTRACTOR TO CONFORM TO 2008 NEC
 BUILDING CODES". THIS IS NOT THE CURRENT CODE. PROVIDE
 CORRECTIONS. FBC PREFACE, 107.2.1; NEC 406.12; FBC RE
 4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-02-21 Cont ID  
Sent By rlecky Date 2017-02-21 Time 11:24 Rev Time 0.00
Received By rlecky Date 2017-02-21 Time 10:33 Sent To  
Notes
2017-02-21 11:30:38 
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE ELECTRIC PLAN SHOWS TWO KITCHENS. PLEASE CLARIFY.
  
 PROVIDE A 20 AMPERE KITCHEN COUNTER TOP RECEPTACLES AS
 REQUIRED FOR ALL COUNTER SPACES. FBC E3901.4
  
 PROVIDE A 20 AMPERE RECEPTACLE CIRCUIT FOR THE DINING
 AREA/ KITCHEN WALL SPACE. FBC E3901.3
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA INCLUDING THE SECOND FLOOR.
 IF THE BUILDING HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIREPLACE, A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R314, 315
  
 A DEDICATED LAUNDRY BRANCH CIRCUIT AND RECEPTACLE IS
 REQUIRED. FBC E3703.3
  
 PROVIDE WALL SWITCHED CONTROLLED LIGHTING AT ALL
 ENTRANCES. FBC E3903,
  
 SHOW THE LOCATION OF THE ELECTRICAL PANEL AND MAIN
 DISCONNECTS. FBC E3405, E3603
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By mvaldes Date 2016-08-11 Time 09:42 Rev Time 0.00
Received By mvaldes Date 2016-08-11 Time 09:09 Sent To M
Notes
2016-08-11 10:26:37REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1) SHEET E-1, SHOW PROPER GFCI RECEPTACLE SPACING IN
 THE KITCHEN COUNTERTOP PER NEC 210.52(3)(C)
  
 2) SHEET E-1, THE A/C DISCONNECT IS SHOWN BEHIN THE CU
 PLEASE RELOCATE TO BE IN COMPLIANCE WITH WORKING
 CLEARANCE. NEC 110.26(A)(1)
  
 3) SHEET E-1, THE RECEPTACLE BY THE CU SHALL HAVE DUAL
 RATING "WP/WR" LISTING IN ACCORDANCE WITH NEC 406.9(B).
 PLEASE ADD SYMBOL TO OUTLET.
  
 4) SHEET E-1, SMOKE ALAMS NEED TO BE REFLECTED IN BOTH
 "EXISTING & AREA OF REMODEL" TO COMPLY WITH FBC-R 314 &
 315.
  
 5) SHEET E-1, AT LEAST ONE WALL SWITCH SHALL CONTROL A
 LIGHTING OUTLET ON THE EXTERIOR SIDE OF OUTDOOR DOORS.
 NEC 210.70(2)(B)
  
 6) SHEET E-1, PROVIDE A RISER-DIAGRAM TO VERIFY
 ELECTRICAL DISTRUBUTION SYSTEM AND REFLECT PANEL AND
 SERVICE LOCATION ON THE FLOOR PLAN. FBC-107

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-09-29 Cont ID  
Sent By fmittner Date 2017-09-29 Time 09:44 Rev Time 0.00
Received By fmittner Date 2017-09-29 Time 09:44 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2017-02-13 Cont ID  
Sent By fmittner Date 2017-02-13 Time 14:56 Rev Time 0.00
Received By fmittner Date 2017-02-13 Time 14:56 Sent To  
Notes
2017-02-13 14:56:39PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED:
  
 STRUCTURE IS LOCATED IN NORTHWEST HISTORIC DISTRICT.
 PLANS INDICATE CHANGES IN WINDOW OPENINGS. NO WINDOW
 SCHEDULE OR ELEVATIONS WERE PROVIDED TO COMPLETE
 EVALUATION. PLEASE SUBMIT ADDITIONAL INFORMATION.
 CONTACT FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION
 PLANNER AT 822-1457 FOR ADDITIONAL QUESTIONS.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By fmittner Date 2016-07-21 Time 14:16 Rev Time 0.00
Received By fmittner Date 2016-07-21 Time 14:16 Sent To  
Notes
2016-07-21 14:25:45STRUCTURE IS LOCATED IN NORTHWEST HISTORIC DISTRICT.
 PLANS INDICATE CHANGES IN WINDOW OPENINGS. NO WINDOW
 SCHEDULE OR ELEVATIONS WERE PROVIDED TO COMPLETE
 EVALUATION. PLEASE SUBMIT ADDITIONAL INFORMATION.
 CONTACT FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION
 PLANNER AT 822-1457 FOR ADDITIONAL QUESTIONS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-11-08 Cont ID  
Sent By cthroop Date 2017-11-08 Time 17:13 Rev Time 0.00
Received By cthroop Date 2017-11-06 Time 15:32 Sent To I
Notes
2017-11-07 15:32:25RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-25 Cont ID  
Sent By hmoser Date 2017-10-25 Time 15:09 Rev Time 0.00
Received By hmoser Date 2017-09-20 Time 14:49 Sent To  
Notes
2017-09-22 14:49:43R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-17 Cont ID  
Sent By hmoser Date 2017-03-17 Time 14:49 Rev Time 0.00
Received By hmoser Date 2017-01-30 Time 10:53 Sent To  
Notes
2017-01-31 10:54:00R16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-17 Cont ID  
Sent By gjohnson Date 2016-08-17 Time 12:52 Rev Time 0.00
Received By gjohnson Date 2016-07-13 Time 13:27 Sent To  
Notes
2016-07-14 13:27:29LIBRARY

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-11-14 Cont ID  
Sent By skennedy Date 2017-11-14 Time 10:23 Rev Time 0.00
Received By skennedy Date 2017-11-14 Time 10:23 Sent To  
Notes
2017-11-14 10:24:22REVIEW BY HMOSER, SIMPLY VERIFIED SECOND COPY WAS
 IDENTICAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-10-25 Cont ID  
Sent By hmoser Date 2017-10-25 Time 15:09 Rev Time 0.00
Received By hmoser Date 2017-10-25 Time 14:50 Sent To  
Notes
2017-10-25 15:09:33PLAN DENIED
 ONLY ONE MECHANICAL PLAN SUBMITTED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-17 Cont ID  
Sent By cthroop Date 2017-02-23 Time 09:36 Rev Time 0.00
Received By hmoser Date 2017-03-17 Time 14:43 Sent To  
Notes
2017-03-17 14:48:52PLAN DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 2014 FBC (M)
 2) COMPLETE EQUIPMENT SCHEDULE ON PLAN.
 PER SECTION 107 FBC 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-08-11 Cont ID  
Sent By hmoser Date 2016-08-11 Time 13:37 Rev Time 0.00
Received By hmoser Date 2016-08-11 Time 13:00 Sent To  
Notes
2016-08-11 13:37:33PASS PROVISO
 PROVIDE ENGINEER DETAIL ON CONDENSER TIE DOWN TO SLAB.
 PER SECTION 301.15 WIND RESISTANCE 2014 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-04 Cont ID  
Sent By gjohnson Date 2017-10-04 Time 19:08 Rev Time 0.00
Received By gjohnson Date 2017-10-04 Time 19:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-02-22 Cont ID  
Sent By gjohnson Date 2017-02-22 Time 08:42 Rev Time 0.00
Received By gjohnson Date 2017-02-22 Time 08:42 Sent To  
Notes
2017-02-22 08:53:102ND REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS: 2ND REQUEST PREVIOUS COMMENTS NOT
 ADDRESSED.
  
 1. SHOW LAUNDRY ON RISER DIAGRAM IT SHALL CONNECT TO
 BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP. WPB AMEND
 TO FBC 107.3.5.3(11) / FBC RES P3108.4
 2. SHOW LOCATION OF WATER HEATER. PER WPB AMEND TO FBC
 107.2.1
  
 NEW COMMENTS;
  
 1. REVISE DESCRIPTION OF WORK ON THE PLUMBING SUB
 PERMIT APPLICATION TO REFLECT THE COMPLETE SCOPE OF
 WORK SHOWN ON THE PLAN. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE DIMENSION OF THE NEW SHOWER SHALL COMPLY
 WITH FBC RES P2708.1 GENERAL.
 SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900 SQUARE
 INCHES (0.6 M2) OF INTERIOR CROSS-SECTIONAL AREA.
 SHOWER COMPARTMENTS SHALL BE NOT LESS THAN 30 INCHES
 (762 MM) IN MINIMUM DIMENSION MEASURED FROM THE
 FINISHED INTERIOR DIMENSION OF THE SHOWER COMPARTMENT,
 EXCLUSIVE OF FIXTURE VALVES, SHOWER HEADS, SOAP DISHES,
 AND SAFETY GRAB BARS OR RAILS. THE MINIMUM REQUIRED
 AREA AND DIMENSION SHALL BE MEASURED FROM THE FINISHED
 INTERIOR DIMENSION AT A HEIGHT EQUAL TO THE TOP OF THE
 THRESHOLD AND AT A POINT TANGENT TO ITS CENTERLINE AND
 SHALL BE CONTINUED TO A HEIGHT OF NOT LESS THAN 70
 INCHES (1778 MM) ABOVE THE SHOWER DRAIN OUTLET. HINGED
 SHOWER DOORS SHALL OPEN OUTWARD. THE WALL AREA ABOVE
 BUILT-IN TUBS HAVING INSTALLED SHOWER HEADS AND IN
 SHOWER COMPARTMENTS SHALL BE CONSTRUCTED IN ACCORDANCE
 WITH SECTION R702.4. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB, RECEPTOR OR SHOWER FLOOR.
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-17 Cont ID  
Sent By gjohnson Date 2016-08-17 Time 11:41 Rev Time 0.00
Received By gjohnson Date 2016-08-17 Time 11:41 Sent To  
Notes
2016-08-17 12:52:301ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHOW LAUNDRY ON RISER DIAGRAM IT SHALL CONNECT TO
 BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP. WPB AMEND
 TO FBC 107.3.5.3(11) / FBC RES P3108.4
 2. SHOW LOCATION OF WATER HEATER. PER WPB AMEND TO FBC
 107.2.1
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2017-10-24 Cont ID  
Sent By cthroop Date 2017-10-24 Time 11:03 Rev Time 0.00
Received By cthroop Date 2017-10-24 Time 07:04 Sent To  
Notes
2017-10-24 11:04:21SEE PERMIT # 15110883

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-02-23 Cont ID  
Sent By cthroop Date 2017-02-23 Time 09:16 Rev Time 0.00
Received By cthroop Date 2017-02-23 Time 09:16 Sent To  
Notes
2017-02-23 09:18:07BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. COMMENTS FROM 1ST REVIEW NOT ADDRESSED.
 2. ROOFING PERMIT REQUIRED.
 3. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM
 COMPONENTS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-09 Cont ID  
Sent By cthroop Date 2016-08-09 Time 14:54 Rev Time 0.00
Received By cthroop Date 2016-08-09 Time 14:54 Sent To  
Notes
2016-08-09 14:59:01BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/9/16
  
 1. NEW ROOFING TO BE INSTALLED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-10-02 Cont ID  
Sent By   Date 2017-10-02 Time   Rev Time 0.00
Received By kmartin Date 2017-10-02 Time 11:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-02-10 Cont ID  
Sent By   Date 2017-02-10 Time   Rev Time 0.00
Received By kmartin Date 2017-02-10 Time 09:28 Sent To HIST
Notes
2017-02-10 09:27:50PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT (561) 822-1426 OR [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2016-08-08 Cont ID  
Sent By   Date 2016-08-08 Time   Rev Time 0.00
Received By kmartin Date 2016-08-08 Time 11:22 Sent To  
Notes
2016-08-08 11:23:021. PROPERTY SURVEY NEEDED TO VERIFY DENSITY
 REQUIREMENT.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT (561) 822-1426 OR [email protected].


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved