2016-08-03 16:26:20 | |
| W. P. B. PERMIT: 16070314 |
| ADD: 415 S. OLIVE AVE. |
| CONT: MDI GENERAL CONTRACTOR |
| TEL: 561-346-6916 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. AUGUST 03/2016 |
| ACTION: DENIED |
| |
| 1) THE CONTRACT VALUE OF THE PROJECT IS $160,000.00. UP |
| TO 20% OF THE CONTRACT VALUE COULD BE USED IN UPGRADES |
| FOR ACCESSIBLITIY TO EXISTING CONDITIONS. $160,000.00 X |
| 0.20% = $32,000.00 DOLLORS IN VALUE. PLEASE SEE |
| DISPROPORTIONATE COST OF IN WHAT ORDER THESE FUNDS ARE |
| TO BE SPENT. PLEASE ALSO PROVIDE A LIST OF ELEMENTS |
| BEING UPGRADES AND THE DOLLOR AMOUNT SPENT ON EACH |
| ELEMENT. |
| |
| 2014 FBC-ACCESS. CODE 202.4.1 DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 2) A-1.01 THE EXISTING DOOR 05 DOES NOT HAVE |
| MANEUVERING CLEARANCES PER ACCESS. CODE 404.2.4. AND |
| FIGURE 404.2.4.1 (A). |
| |
| 3) DISCREPANCY IN PLANS BETWEEN THE LIFE SAFETY PLANS |
| AND SHEET A-1.01 SEE THE CHAIR LAY OUT AND THE REQUIRED |
| MANEUVERING CLEARANCES FOR DOORS 18A & 18B. MANEUVERING |
| CLEARANCES PER ACCESS. CODE 404.2.4. |
| |
| 4) SHEET A-1.01 TOLIET ROOM DOOR 14 ALSO MISSING THE |
| REQUIRED 18 INCHES MANEUVERING CLEARANCES. MANEUVERING |
| CLEARANCES PER ACCESS. CODE 404.2.4. |
| |
| 5) SHEET A-1.01 INDICATES THE FRONT GLAZING IS BEING |
| REPLACED WITH CURTAIN WALL SYSTEM AND NEW STOREFRONT |
| DOOR SYSTEM. THIS REVIEW CYCLE NO PRODUCT APPROVALS |
| HAVE BEEN SUBMITTED. 2014 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 7) SHEET A-5.00 DETAIL 1A THE BREAK ROOM SINK IAND |
| COUNTERTOP IS INDICATED AT THE HEIGHT OF 36 INCHES. |
| PLEASE COMPLY WITH |
| 2014 ACESS. CODE 606.3 HEIGHT. LAVATORIES AND SINKS |
| SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE |
| RIM OR COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. |
| |
| 8) SHEET S-1.0 HAS THE PRESSUES FOR THE ROOF WHICH ARE |
| RIGHT ON THE TARGET. THE NEGATIVE PRESSURES FOR WALL |
| ZONES 4 & 5 ARE LOW BY 4 LBS. FBC-B 1609.1.5/ |
| 1609.1.2.3.1. |
| |
| 9) SHEET S-3.0 DETAIL # 2 SHOWS A NEW PARAPET BEING |
| INSTALLED ONTOP OF THE EXISITNG BEAM. WILL BE STRIPPING |
| THE ROOF BACK TO MAKE A TIE IN, WILL NEED PRODUCT |
| APPROVALS FOR THIS TIE- IN. COMPONENTS & CLADDING |
| 1609.4.4.1. |
| |
| 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |