Plan Review Details - Permit 16070314
Plan Review Stops For Permit 16070314
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-15 Cont ID  
Sent By jwitmer Date 2016-09-15 Time 16:21 Rev Time 0.00
Received By jwitmer Date 2016-09-15 Time 14:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-03 Cont ID  
Sent By jwitmer Date 2016-08-03 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2016-08-03 Time 14:39 Sent To  
Notes
2016-08-03 16:26:20 
 W. P. B. PERMIT: 16070314
 ADD: 415 S. OLIVE AVE.
 CONT: MDI GENERAL CONTRACTOR
 TEL: 561-346-6916
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 03/2016
 ACTION: DENIED
  
 1) THE CONTRACT VALUE OF THE PROJECT IS $160,000.00. UP
 TO 20% OF THE CONTRACT VALUE COULD BE USED IN UPGRADES
 FOR ACCESSIBLITIY TO EXISTING CONDITIONS. $160,000.00 X
 0.20% = $32,000.00 DOLLORS IN VALUE. PLEASE SEE
 DISPROPORTIONATE COST OF IN WHAT ORDER THESE FUNDS ARE
 TO BE SPENT. PLEASE ALSO PROVIDE A LIST OF ELEMENTS
 BEING UPGRADES AND THE DOLLOR AMOUNT SPENT ON EACH
 ELEMENT.
  
 2014 FBC-ACCESS. CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 2) A-1.01 THE EXISTING DOOR 05 DOES NOT HAVE
 MANEUVERING CLEARANCES PER ACCESS. CODE 404.2.4. AND
 FIGURE 404.2.4.1 (A).
  
 3) DISCREPANCY IN PLANS BETWEEN THE LIFE SAFETY PLANS
 AND SHEET A-1.01 SEE THE CHAIR LAY OUT AND THE REQUIRED
 MANEUVERING CLEARANCES FOR DOORS 18A & 18B. MANEUVERING
 CLEARANCES PER ACCESS. CODE 404.2.4.
  
 4) SHEET A-1.01 TOLIET ROOM DOOR 14 ALSO MISSING THE
 REQUIRED 18 INCHES MANEUVERING CLEARANCES. MANEUVERING
 CLEARANCES PER ACCESS. CODE 404.2.4.
  
 5) SHEET A-1.01 INDICATES THE FRONT GLAZING IS BEING
 REPLACED WITH CURTAIN WALL SYSTEM AND NEW STOREFRONT
 DOOR SYSTEM. THIS REVIEW CYCLE NO PRODUCT APPROVALS
 HAVE BEEN SUBMITTED. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET A-5.00 DETAIL 1A THE BREAK ROOM SINK IAND
 COUNTERTOP IS INDICATED AT THE HEIGHT OF 36 INCHES.
 PLEASE COMPLY WITH
 2014 ACESS. CODE 606.3 HEIGHT. LAVATORIES AND SINKS
 SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE
 RIM OR COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 8) SHEET S-1.0 HAS THE PRESSUES FOR THE ROOF WHICH ARE
 RIGHT ON THE TARGET. THE NEGATIVE PRESSURES FOR WALL
 ZONES 4 & 5 ARE LOW BY 4 LBS. FBC-B 1609.1.5/
 1609.1.2.3.1.
  
 9) SHEET S-3.0 DETAIL # 2 SHOWS A NEW PARAPET BEING
 INSTALLED ONTOP OF THE EXISITNG BEAM. WILL BE STRIPPING
 THE ROOF BACK TO MAKE A TIE IN, WILL NEED PRODUCT
 APPROVALS FOR THIS TIE- IN. COMPONENTS & CLADDING
 1609.4.4.1.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By albarran Date 2016-09-13 Time 19:53 Rev Time 0.00
Received By albarran Date 2016-09-13 Time 18:49 Sent To  
Notes
2016-09-13 19:54:34MOST OF THE PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED. PROVISO STICKER PLACED ON
 PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-13 Cont ID  
Sent By albarran Date 2016-07-13 Time 16:57 Rev Time 0.00
Received By albarran Date 2016-07-13 Time 15:47 Sent To  
Notes
2016-07-13 17:18:071ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 ELECTRICAL REVIEW APPROVED WITH THE FOLLOWING
 EXCEPTIONS:.
 1. NEC 110.16 ARC-FLASH HAZARD WARNING LABELS REQUIRED.
 NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS.
 2. PER FBC-B 714.3.2 EXCEPTIONS: 1.1 UNLESS YOU HAVE
 SOLID NONCOMMUNICATING PARTITIONS, ALL ELECTRICAL BOXES
 IN 2 HR. RATED WALLS SHALL BE PROTECTED WITH LISTED
 FIRE STOPPING MATERIAL.
 3. PER FBC-EC405.7, A MINIMUM OF 50% OF ALL 125V, 15 &
 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED
 WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER
 CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-21 Cont ID  
Sent By pleduc Date 2016-07-21 Time   Rev Time 0.00
Received By pleduc Date 2016-07-21 Time 08:08 Sent To  
Notes
2016-07-21 08:15:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THE ROOF DESIGN IS SUCH THAT A LIGHTWIEIGHT ROOF
 TRUSS IS REQUIRED PER FLORIDA 69A-60.0081; NOTICE
 SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-16 Cont ID  
Sent By skennedy Date 2016-09-16 Time 12:23 Rev Time 0.00
Received By skennedy Date 2016-08-22 Time 13:00 Sent To  
Notes
2016-08-23 13:00:24C04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By jwitmer Date 2016-08-03 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2016-07-11 Time 13:05 Sent To  
Notes
2016-07-11 13:05:33C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-08-03 Cont ID  
Sent By jwitmer Date 2016-08-03 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2016-08-03 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-09-16 Cont ID  
Sent By skennedy Date 2016-09-16 Time 12:23 Rev Time 0.00
Received By skennedy Date 2016-09-16 Time 12:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-09-08 Cont ID  
Sent By ccole Date 2016-09-08 Time 17:10 Rev Time 0.00
Received By ccole Date 2016-09-08 Time 17:10 Sent To  
Notes
2016-09-08 17:42:322ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070314
 9/8/16
  
 1) SHEET M1.1: GENERAL NOTE #1, AND KEY NOTE #1 DO NOT
 APPEAR TO BE APPLICABLE TO THE REVISED PLANS- PLEASE
 REMOVE OR CLARIFY THE NOTES.
  
 2) KEY NOTE #5 IS INCORRECTLY LOCATED AT A RETURN GRILL
 IN THE CONFERENCE ROOM WALL.
  
 3) THE AC CLOSET DOOR #E-13 MUST BE NON-COMBUSTIBLE-
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-07-18 Cont ID  
Sent By ccole Date 2016-07-18 Time 12:34 Rev Time 0.00
Received By ccole Date 2016-07-18 Time 12:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-09-14 Cont ID  
Sent By tklarge Date 2016-09-14 Time 06:17 Rev Time 0.00
Received By tklarge Date 2016-09-14 Time 05:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By tklarge Date 2016-08-01 Time 12:55 Rev Time 0.00
Received By tklarge Date 2016-08-01 Time 12:12 Sent To  
Notes
2016-08-01 12:55:081) A DRINKING FOUNTAIN IS REQD. PER TABLE 403.1 OF 2014
 FPC & 2014 FBC-ACCESS. SECS.202.4.2, 211.2.
 2) A SERVICE SINK IS REQD. PER 2014 FPC TABLE 403.1.
 3) THE BREAKROOM SINK SHALL COMPLY WITH THE FL.
 ACCESSIBILITY CODE SECS. 212.1, 606.
 4) SHOW THE WIDTH OF TOILET ROOM #17. THE WIDTH SHALL
 BE A MINIMUM OF 85 INCHES WIDE IF BUILT PERFECT. 86
 INCHES ALLOWS FOR TOLERANCE.
 5) TOILET ROOM #14 SHALL BE HANDICAPPED ACCESSIBLE.FAC
 SEC. 213.2.
 6) SHT. A-5.01 - SHOW ALL MOUNTING HEIGHTS FOR GRAB
 BARS, MIRROR, SOAP & TOILET PAPER DISPENSER, ETC.ALL
 MOUNTING HEIGHTS SHALL COMPLY WITH 2014 FAC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By   Date 2016-08-24 Time   Rev Time 0.00
Received By kmartin Date 2016-08-24 Time 09:30 Sent To  
Notes
2016-08-24 09:31:53PROVISO:
  
 APPLICANT MUST SUBMIT AND COMPLETE PARKING IMPROVEMENTS
 BEFORE CO IS ISSUED.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT (561) 822-1426 OR [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2016-08-01 Cont ID  
Sent By aaponte Date 2016-08-01 Time 11:30 Rev Time 0.00
Received By kmartin Date 2016-08-01 Time 11:29 Sent To  
Notes
2016-08-01 11:30:221. PROVIDE PROPERTY SURVEY.
 2. PROVIDE SITE PLAN INDICATING COMPLIANCE WITH PARKING
 AND LANDSCAPING REQUIREMENTS.
  
 FOR MORE INFORMATION PLEASE CONTACT KEVIN MARTIN, URBAN
 DESIGN PLANNER AT (561) 822-1426 OR [email protected].