Plan Review Details - Permit 16070269
Plan Review Stops For Permit 16070269
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-08-15 Cont ID  
Sent By jwitmer Date 2016-08-15 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2016-08-15 Time 13:27 Sent To  
Notes
2016-08-15 13:28:27E-MAIL RECEIVED TODAY:
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-08-13 Cont ID  
Sent By jwitmer Date 2016-08-13 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2016-08-13 Time 11:00 Sent To  
Notes
2016-08-13 11:05:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070269
 ADD: 2427 PRESIDENTIAL WAY SUITE # 301
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-427-5664
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SAT. AUGUST 13/2016
 ACTION: DENIED
  
 1) 3RD REQUEST. SEMI-COMPLIED.THE DEMOLITION PLAN
 INDICATES THE REMOVAL OF ALL FLOOR FINISHES THROUGH OUT
 THE UNIT. SHEET A.02 THIS REVIEW MAKES REFERENCE TO
 WHICH ROOMS WILL RECEIVE WOOD FLOOR FINISHES AND WHICH
 WILL RECEIVE MARBLE FINISHES.
 _______________________________________________________
 _______________________________________________________
 ___
 E-MIAL SENT SAT. AUG. 13/16 11:24 AM
  
 GOOD MORNING MR. STEINBORG,
 I'VE BEEN REVIEWING THE PLANS FOR 2427 PRESIDENTIAL WAY
 THE PLANS INDICATE THE USE OF WOOD FLOORING THROUGH THE
 UNIT WITH THE EXCEPTION OF THE RESTROOMS AND LAUNDRY
 ROOM THE INSTALLATION OF MARBLE IN THESE ROOMS. WE ONLY
 HAVE TESTING FOR THE PROFLEX RCU-500 FOR MARBLE/ TILE.
 NO ONE TO DATE HAS BROUGHT IN THE TEST REPORTS TO USE
 THIS PRODUCT ON WOOD. WE WILL NEED THE ACTUAL TEST
 DOCUMENTS FOR THE FLOOR INSULATION TESTED WITH A WOOD
 FINISH FLOOR ABOVE. PLEASE ALSO NOTE THE SUBMITTED
 DOCUMENTS SUBMITTED ONCE OPENED ARE NOLONGER ATTACHED
 TO THIS E-MAIL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
 _______________________________________________________
 _______________________________________________________
 PLAN REVIEW NOTES
  
 THE PLANS REFER BACK TO THE REQUIRED TESTING REPORTS. I
 SPOKE LAST WEEK WITH A DESIGNER ON THIS PROJECT. DO NOT
 SEND IN SPEC SHEETS, WE NEED THE ACTUAL TEST. SUBMITTED
 IS PROFLEX MSC 90, THIS DOES NOT MEET THE REQUIREMENT
 WHEN YOU ACTUALLY SEE THE DOCUMENTED TEST. NEITHER DID
 THE DESIGNER NOR CONTRACTOR SUBMIT THE FLAME SPREAD
 TEST REPORT REQUESTED BELOW.
 CURRENTLY THE ONLY PRODUCT THAT HAS MET ALL OF THE
 REQUIREMENTS FOR TILE ON A 6 INCH SLAB IS THE PRODUCT
 PROFLEX RCU-500 WHICH IS 1/2 INCH THICK. STC 53 & IIC
 50,
 FOR THE USE OF TILE/ MARBLE, 6 INCH CONCRETE SLAB/ NO
 DROPPED CEILING.
  
  
 PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A)2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-04 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2016-08-04 Time 11:58 Sent To  
Notes
2016-08-04 12:21:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070269
 ADD: 2427 PRESIDENTIAL WAY SUITE # 301
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-427-5664
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 18/2016
 ACTION: DENIED
  
 NOTICE TO CONTRACTOR, REMOVE OLD SHEETS AND INSERT NEW
 SHEETS< SEE COMMENT # 3!!!!!!!
  
  
  
 1) 2ND REQUEST. THE DEMOLITION PLAN INDICATES THE
 REMOVAL OF ALL FLOOR FINISHES THROUGH OUT THE UNIT.
 SHEET A.02 MAKES REFERENCE TWICE TO THE REQUIRED FLOOR
 SOUND INSULATION REQUIREMENTS. THE SHEET A.02 INTERIOR
 NOTE # 6 INDICATES THE FLOOR FINISHES ARE TO BE
 SPECIFIED BY THE OWNER. THE PLANS DO NOT STATE WHICH
 ROOMS WILL RECIEVE WHAT FLOOR FINISHES!!!!!! WE NEED TO
 KNOW THAT TO BE ABLE TO MATCH UP THE TYPEOF MATERIAL TO
 BE INSTALLED TO THE SUBMITTED REPORT.
  
 THE PLANS REFER BACK TO THE REQUIRED TESTING REPORTS. I
 SPOKE LAST WEEK WITH A DESIGNER ON THIS PROJECT. DO NOT
 SEND IN SPEC SHEETS, WE NEED THE ACTUAL TEST. SUBMITTED
 IS PROFLEX MSC 90, THIS DOES NOT MEET THE REQUIREMENT
 WHEN YOU ACTUALLY SEE THE DOCUMENTED TEST. NEITHER DID
 THE DESIGNER NOR CONTRACTOR SUBMIT THE FLAME SPREAD
 TEST REPORT REQUESTED BELOW.
 CURRENTLY THE ONLY PRODUCT THAT HAS MET ALL OF THE
 REQUIREMENTS FOR TILE ON A 6 INCH SLAB IS THE PRODUCT
 PROFLEX RCU-500 WHICH IS 1/2 INCH THICK. STC 53 & IIC
 50, 6 INCH CONCRETE SLAB/ NO DROPPED CEILING.
  
  
 PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A)2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) COMPLIED.
  
 3) 2ND REQUEST!!!!! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By jwitmer Date 2016-07-18 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2016-07-18 Time 11:25 Sent To  
Notes
2016-07-18 11:52:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070269
 ADD: 2427 PRESIDENTIAL WAY SUITE # 301
 CONT: FINE LINE CONSTRUCTION
 TEL: 561-427-5664
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 18/2016
 ACTION: DENIED
  
 1) THE DEMOLITION PLAN INDICATES THE REMOVAL OF ALL
 FLOOR FINISHES THROUGH OUT THE UNIT. PLEASE PROVIDE
 COMPLIANCE WITH THE 2014 FBC-B.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2A) SHEET A.02 SHOWS A LIVING ROOM CEILING HEIGHT OF 8
 FT. 1 IN. AND A BREAKFAST AREA WITH THE SAME FINISH
 CEILING AT 8 FT. 1 INCH. PLEASE NOTE THERE IS A NOTE OF
 A NEW 7 INCH DEEP SOFFIT ( DROPPED CEILING OVER THE
 KITCHEN AREA) BUT THERE IS NO INFORMATION AS TO WHERE
 IT ENDS? THIS ALSO HOLDS TRU WITH THE NEW MASTER BATH
 LAYOUT AND MASTER BATH ENTRY HALLWAY. PLEASE NOTE WITH
 ONLY A 7 INCH DROPPED CEILING WHERE WILL THE A/C DUCTS
 BE RUN SINCE THE FRAMING MEMBERS WILL TAKE
 APPROXIMATELY 3 1/2 INCHES OF THIS SPACE? 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 2B) THERE IS ALSO NO FRAMING INFORMATIONFOR THE DROPPED
 SOFFIT/ CEILING, AS TO MATERIAL, SIZE OF, GAUGE,
 SPACING, ANCHORING TO THE CONCRETE DECK ABOVE, TYPE OF
 ANCHOR, FREQUENCY OF ATTACHMENT TO THE CONRETE DECK,IF
 STIFF BACKS ARE REQUIRED NOR THE TYPE OF FINISH
 MATERIAL TO BE USED FOR THE SOFFIT/ KITCHEN CEILING NOR
 THE ALLOWABLE CEILING SPANS AND DEFLECTION LIMITATIONS.
 2014 FBC-B TABLE 2507.2 STEEL STUDS NON-LOAD BEARING
 ASTM C645. ASTM C754. TABLE 1604.3 DEFLECTION.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-11 Cont ID  
Sent By albarran Date 2016-07-11 Time 17:53 Rev Time 0.00
Received By albarran Date 2016-07-11 Time 17:19 Sent To  
Notes
2016-07-11 17:54:20ELECTRICAL REVIEW IS SUBJECT TO FIELD INSPECTOR'S
 APPROVAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-04 Cont ID  
Sent By scaldero Date 2016-08-04 Time 09:38 Rev Time 0.00
Received By scaldero Date 2016-08-04 Time 09:38 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-11 Cont ID  
Sent By scaldero Date 2016-07-11 Time 12:31 Rev Time 0.00
Received By scaldero Date 2016-07-11 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-15 Cont ID  
Sent By jwitmer Date 2016-08-15 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2016-08-15 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-13 Cont ID  
Sent By   Date 2016-08-13 Time   Rev Time 0.00
Received By lmarchan Date 2016-08-11 Time 15:15 Sent To  
Notes
2016-08-11 15:15:13RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-04 Cont ID  
Sent By jwitmer Date 2016-08-04 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2016-07-28 Time 09:30 Sent To  
Notes
2016-07-29 09:30:52RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 12:16 Rev Time 0.00
Received By tklarge Date 2016-07-08 Time 14:08 Sent To  
Notes
2016-07-08 14:09:02B19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-07-18 Cont ID  
Sent By ccole Date 2016-07-18 Time 16:12 Rev Time 0.00
Received By ccole Date 2016-07-18 Time 16:08 Sent To  
Notes
2016-07-18 16:14:117/18/16
  
 SEPARATE PERMIT REQUIRED FOR HVAC ALTERATIONS- SEE
 SHEET A.03.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-12 Cont ID  
Sent By tklarge Date 2016-08-12 Time 08:58 Rev Time 0.00
Received By tklarge Date 2016-08-12 Time 06:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 12:15 Rev Time 0.00
Received By tklarge Date 2016-07-23 Time 12:08 Sent To  
Notes
***NONE***