Plan Review Details - Permit 16070261
Plan Review Stops For Permit 16070261
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By vperez Date 2016-07-27 Time 07:59 Rev Time 0.00
Received By vperez Date 2016-07-27 Time 07:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By vperez Date 2016-07-11 Time 12:28 Rev Time 0.00
Received By vperez Date 2016-07-11 Time 12:28 Sent To  
Notes
2016-07-11 12:30:38INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLANS PROVIDED ARE INSUFFICIENT. PLANS ARE TO
 REFLECT PER SCOPE LISTED ON APPLICATION ALL
 REQUIREMENTS PER FBC 107.3.5- MINIMUM PLAN REVIEW.
 2. PLANS ARE TO BE SIGNED AND SEALED BY AOR OR EOR, IF
 QUALIFIER IS DESIGNING DRAWINGS MUST SIGN AND NOTARIZED
 ELECTRICAL SHEETS. FBC 107.3.5- MINIMUM PLAN REVIEW
 3. PROVIDE A GENERAL NOTE TO INDICATE LOW VOLTAGE TO BE
 UNDER SEPARATE PERMIT.
 4. PROVIDE FIXTURE SPECS AND DETAILS OF INSTALLATIONS.
 5. PROVIDE CUT SHEET FOR ALL LIGHTING CONTROLS PANEL
 AND ACCESSORIES AND SHOW SEQUENCE OF OPERATION AS PER
 FBC ENERGY CONSERVATION C405.7
 6. LABEL ON DRAWING WHAT IS EXISTING TO REMAIN, NEW,
 RELOCATED ETC.
 7. LABEL CIRCUIT ID FOR ALL NEW POWER AND LIGHTING
 OUTLETS.
 8. PROVIDE A FIXTURE LEGEND.
 9. PROVIDE A REVISED PANEL SCHEDULE REFLECTING ALL
 CIRCUITS AND NEW LOADS BEING ADDED INCLUDING
 MECHANICAL.
 10. SHOW PANEL LOCATIONS FOR ALL SCOPE REFLECTING
 PROPER CLEARANCE PER NEC 110.26
 11. A COMPLETE REVIEW IN ACCORDANCE WITH FBC CANNOT BE
 COMPLETE DUE TO PENDING INFORMATION.
 12. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-27 Cont ID  
Sent By vperez Date 2016-07-27 Time 07:59 Rev Time 0.00
Received By vperez Date 2016-07-27 Time 07:59 Sent To  
Notes
2016-07-26 10:50:53VPEREZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-11 Cont ID  
Sent By vperez Date 2016-07-11 Time 12:30 Rev Time 0.00
Received By vperez Date 2016-07-11 Time 12:30 Sent To  
Notes
2016-07-11 11:46:38VPEREZ'S DESK