Plan Review Details - Permit 16070228
Plan Review Stops For Permit 16070228
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-05 Cont ID  
Sent By wjolin Date 2016-08-05 Time 13:10 Rev Time 0.00
Received By wjolin Date 2016-08-05 Time 09:30 Sent To M
Notes
2016-08-05 10:01:244850 LORING DRIVE
 PERMIT #16070228
 MASTER #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 REPEAT COMMENT: INDICATE THE FLOORS TO BE TESTED IN
 EXCESS OF THE 200 PSI HYDROSTATIC TEST PRESSURE.
 INDICATE THE TEST PRESSURE (ABOVE 200 PSI) NEEDED AT
 THESE FLOORS.
  
 SHEET 2 OF 11:
 1) PLAN INDICATES A HYDROSTATIC TEST PRESSURE OF 200
 PSI. SYSTEMS SHALL BE TESTED AT 50 PSI ABOVE WORKING
 PRESSURE; THEREFORE, THE 1ST FLOOR SHOULD BE TESTED AT
 254 PSI (PUMP CHURN 148 PSI, PLUS CITY SUPPLY 56 PSI,
 PLUS 50 PSI ABOVE WORKING). THE 254 PSI HYDRO TEST
 PRESSURE WILL APPLY TO THE SYSTEM FEED MAINS AND
 STANDPIPES. THE SPRINKLER SYSTEMS WILL BE PROTECTED BY
 A PRESSURE REDUCING VALVE SET TO A MAXIMUM PRESSURE OF
 165 PSI; THEREFORE, THE CROSS MAINS, BRANCHLINES AND
 SPRINKLERS SHALL BE PRESSURE TESTED TO AT LEAST 215
 PSI.
  
 2) ORDINARY HAZARD ROOM MECHANICAL CHILLER #182 HAS
 SEVERAL SPRINKLERS WITH COVERAGES EXCEEDING 130 SQUARE
 FEET.
  
 3) THE CENTER NORTH SPRINKLER IN MULTIPURPOSE #125 IS
 LOCATED IN THE 10'-8" CEILING. THE ADJACENT 9'-8"
 SOFFIT TO THE NORTH OBSTRUCTS THE SPRAY OF THIS
 SPRINKLER PER NFPA 13 TABLE 8.6.5.1.2.
  
 4) TREATMENT #140 HAS A SPRINKLER LOCATED IN THE UPPER
 9'-0" CEILING; HOWEVER, THE ADJACENT 8'-0" SOFFITS
 OBSTRUCT THE SPRAY OF THE SPRINKLER ON THREE SIDES PER
 NFPA 13 TABLE 8.6.5.1.2.
  
 GENERAL OBSERVATION:
 1) RESIDENTIAL SIDEWALL SPRINKLERS ARE TYPICALLY
 INSTALLED 1"- 6" BELOW THE CEILING. THE RESIDENTIAL
 SIDEWALL SPRINKLERS THAT WERE SUBMITTED ALLOW THE
 SIDEWALL SPRINKLERS TO BE INSTALLED UP TO 12" BELOW THE
 CEILING. THIS SHOULD BE NOTED ON ALL PLANS FOR THE
 INSTALLER, OTHERWISE SPRINKLERS INSTALLED 1" - 6" BELOW
 THE CEILING WILL BE OBSTRUCTED BY SOFFITS IN SEVERAL
 DWELLING UNITS SUCH AS UNIT #107 (UNIT TYPE B1A), UNIT
 #106 (UNIT TYPE C3), UNIT #220 (UNIT TYPE C3).
  
 SHEET 5 OF 11:
 1) ARCHITECTURAL AND SPRINKLER PLANS DO NOT INDICATE A
 CEILING HEIGHT IN UNIT #216 (UNIT TYPE E2) AND UNIT
 #218 (UNIT TYPE D2). THESE UNITS FEATURE BEDROOM
 SOFFITS THAT MAY OBSTRUCT THE SIDEWALL SPRINKLER SPRAY
 NFPA 13 TABLE 8.10.7.1.3. THIS SEEMS TO BE NEAR TYPICAL
 CONDITIONS ON EACH FLOOR ABOVE.
  
 SHEET 8 OF 11:
 1) UNIT 1018 (UNIT TYPE D) THE MASTER BEDROOM HAS A
 CEILING HEIGHT OF 10'-0" AND A SOFFIT HEIGHT OF 8'-0".
 THE SOFFIT CREATES A SIDEWALL SPRAY OBSTRUCTION PER
 NFPA 13 TABLE 8.10.7.1.3.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-13 Cont ID  
Sent By wjolin Date 2016-07-13 Time 14:34 Rev Time 0.00
Received By wjolin Date 2016-07-08 Time 14:22 Sent To M
Notes
2016-07-08 14:24:294850 LORING DRIVE
 PERMIT #16070228
 MASTER #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RELIABLE SPRINKLER MODEL G5 WAS SUBMITTED BUT CANNOT BE
 LOCATED ON ANY OF THE PLANS.
  
 SITE PLAN INDICATES THE FIRE PUMP IS "NOT IN CONTRACT"
 HOWEVER, FIRE PUMP ISOMETRIC AND PUMP BILL OF MATERIALS
 HAVE BEEN PROVIDED.
  
 SUBMIT PRODUCT DATA FOR FIRE PUMP, JOCKEY PUMP,
 CONTROLLERS, PRESSURE REDUCING VALVES, PIPE, FITTINGS,
 ETC.
  
 1ST FLOOR PLANS ARE NOT SCALABLE; HOWEVER, PLANS
 INDICATE A SCALE OF 3/32"=1'-0". PLANS ARE REQUIRED TO
 A MINIMUM OF 1/8"=1'-0".
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING)
 INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM
 SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF
 DECK (IF OBSTRUCTED CONSTRUCTION).
  
 PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM
 NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS
 PERMITTED IN THE LISTING DATA.
  
 INDICATE THE FLOORS TO BE TESTED IN EXCESS OF THE 200
 PSI HYDROSTATIC TEST PRESSURE. INDICATE THE TEST
 PRESSURE (ABOVE 200 PSI) NEEDED AT THESE FLOORS.
  
 RELIABLE MODEL RESIDENTIAL SPRINKLERS ARE LOCATED IN
 SEVERAL ROOMS THAT ARE NOT DWELLING UNITS. PER NFPA 13
 SECTION 8.4.5.1 RESIDENTIAL SPRINKLERS SHALL BE
 PERMITTED IN DWELLING UNITS AND THEIR ADJOINING
 CORRIDORS.
  
 SPRINKLER FLOOR CONTROL VALVES (SEVERAL SHEETS): PER
 NFPA 13 SECTION 8.16.1.2.2 PRESSURE GAUGES SHALL BE
 INSTALLED ON THE INLET AND OUTLET SIDES OF EACH
 PRESSURE-REDUCING VALVE. A RELIEF VALVE OF NOT LESS
 THAN 1/2-INCH IN SIZE SHALL BE PROVIDED ON THE
 DISCHARGE SIDE OF THE PRESSURE-REDUCING VALVE SET TO
 OPERATE AT A PRESSURE NOT EXCEEDING 175 PSI.
  
 2ND FLOOR: SPRINKLERS LOCATED IN THE HIGH CEILING OF
 LIVING/LIBRARY ROOM #121 NEED TO BE SUPPLIED FROM THE
 1ST FLOOR SPRINKLER SYSTEM SEEING THAT THE SPRINKLERS
 ARE PROTECTING THE FLOOR AREA OF THE 1ST FLOOR,
 OTHERWISE FIREFIGHTERS MAY INCORRECTLY ASSUME THE FIRE
 IS LOCATED ON THE 2ND FLOOR WHEN THE FLOW SWITCH
 OPERATES.
  
 10TH FLOOR: THE HYDRAULIC CALCULATION NODES DO NOT
 MATCH THE HYDRAULIC NODES ON THE PLANS. FOR EXAMPLE,
 HYDRAULIC CALCULATIONS INDICATE FLOWING NODES #1001 -
 #1005; HOWEVER, THE PLANS SHOW NODES IN THE 300'S AND
 3000'S.
  
 10TH FLOOR: NO HYDRAULIC CALCULATIONS SUBMITTED FOR
 AREAS OUTSIDE THE DWELLING UNITS SUCH AS TRASH ROOMS,
 STORAGE ROOMS, COMMUNITY ROOMS ETC.
  
 10TH FLOOR: PROVIDE HYDRAULIC CALCULATION FOR 4
 SIDEWALL SPRINKLERS IN UNIT #1019.
  
 10TH FLOOR: RESIDENTIAL TYPE SPRINKLERS SHOWN IN
 ACTIVITY ROOM #1017 AND COMMUNITY ROOM #937 (TYPICAL
 SEVERAL FLOORS). PER NFPA 13 SECTION 8.4.5.1
 RESIDENTIAL SPRINKLERS SHALL BE PERMITTED IN DWELLING
 UNITS AND THEIR ADJOINING CORRIDORS.
  
 STANDPIPE RISERS: PROVIDE PRESSURE GAUGES AT THE TOP OF
 THE STANDPIPES PER NFPA 14 SECTION 5.5.
  
 FIRE PUMP ISOMETRIC: PER NFPA 20 (2010 EDITION) SECTION
 4.14.6.3.2, THE DISTANCE OF THE FIRE PUMP SUCTION
 FLANGE AND ANY ADJACENT SUCTION PIPE ELBOW/TEE FLANGE
 SHALL BE SEPARATED BY AT LEAST 10 PIPE DIAMETERS WHEN
 THE ELBOW/TEE HAS A CENTERLINE PLANE PARALLEL TO A
 HORIZONTAL SPLIT-CASE PUMP SHAFT. NOTE: THE CODE
 REQUIREMENTS HAVE NOT CHANGED IN THE LATEST EDITION OF
 THE STANDARD; HOWEVER, DIAGRAMS OF CORRECT/INCORRECT
 SUCTION PIPE INSTALLATIONS HAVE BEEN UPDATED IN FIGURE
 A4.14.6 OF NFPA 20 - 2013 EDITION.
  
 A COMPLETE PLAN REVIEW CANNOT BE COMPLETED AT THIS TIME
 DUE TO SCALING AND TECHNICAL ERRORS SUBMITTED ON THE
 PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-09 Cont ID  
Sent By hmoser Date 2016-08-09 Time 11:02 Rev Time 0.00
Received By hmoser Date 2016-08-03 Time 09:31 Sent To  
Notes
2016-08-04 09:31:24RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-20 Cont ID  
Sent By hmoser Date 2016-07-20 Time 14:55 Rev Time 0.00
Received By hmoser Date 2016-07-07 Time 09:51 Sent To  
Notes
2016-07-08 09:51:51ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-09 Cont ID  
Sent By hmoser Date 2016-08-09 Time 11:02 Rev Time 0.00
Received By hmoser Date 2016-08-09 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-20 Cont ID  
Sent By hmoser Date 2016-07-20 Time 14:45 Rev Time 0.00
Received By hmoser Date 2016-07-20 Time 14:45 Sent To  
Notes
2016-07-20 14:55:09PLAN DENIED
 REFER TO FIRE COMMENTS. HM.