Plan Review Details - Permit 16070085
Plan Review Stops For Permit 16070085
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-08-30 Time 13:23 Rev Time 0.00
Received By jwitmer Date 2016-08-30 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-08-15 Cont ID  
Sent By jwitmer Date 2016-08-15 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-08-15 Time 07:01 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-07-13 Cont ID  
Sent By jwitmer Date 2016-07-13 Time 05:59 Rev Time 0.00
Received By jwitmer Date 2016-07-13 Time 05:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-29 Cont ID  
Sent By albarran Date 2016-08-29 Time 14:46 Rev Time 0.00
Received By albarran Date 2016-08-29 Time 14:30 Sent To  
Notes
2016-08-29 14:48:27REVIEWED AND STAMPED REVISED ELECTRICAL SHEET E111.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-12 Cont ID  
Sent By albarran Date 2016-07-12 Time 10:43 Rev Time 0.00
Received By albarran Date 2016-07-12 Time 10:27 Sent To  
Notes
2016-07-12 10:44:47APPROVED ELECTRICAL REVIEW AS SUBMITTED. MADE REMINDER
 NOTE TOWARDS THE OBVIOUS REQUIREMENTS: TAMPER-RESISTANT
 RECEPTACLES, ARC-FAULT PROTECTION & SMOKE DETECTORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-11 Cont ID  
Sent By scaldero Date 2016-07-11 Time 12:35 Rev Time 0.00
Received By scaldero Date 2016-07-11 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-30 Cont ID  
Sent By jwitmer Date 2016-08-30 Time 13:23 Rev Time 0.00
Received By jwitmer Date 2016-08-24 Time 11:06 Sent To  
Notes
2016-08-25 11:06:15B01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-20 Cont ID  
Sent By tklarge Date 2016-08-20 Time 04:37 Rev Time 0.00
Received By tklarge Date 2016-08-09 Time 09:58 Sent To  
Notes
2016-08-10 09:58:23B36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 04:30 Rev Time 0.00
Received By tklarge Date 2016-07-05 Time 10:13 Sent To  
Notes
2016-07-06 10:12:44B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-07-13 Cont ID  
Sent By jwitmer Date 2016-07-13 Time   Rev Time  
Received By jwitmer Date 2016-07-13 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-08-30 Cont ID  
Sent By ccole Date 2016-08-30 Time 10:29 Rev Time 0.00
Received By ccole Date 2016-08-30 Time 10:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-08-15 Cont ID  
Sent By ccole Date 2016-08-15 Time 14:27 Rev Time 0.00
Received By ccole Date 2016-08-15 Time 14:27 Sent To  
Notes
2016-08-15 14:29:292ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070085
 8/15/16
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. THE
 DRYER BOOSTER FAN THAT IS PROHIBITED IS SHOWN TO BE
 RELOCATED TO THE NEW DRYER LOCATION ON SHEET E-111.
  
 2) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. THE
 SUBMITTED SPECIFICATIONS FOR THE DRYER DO NOT INDICATE
 THE EXHAUST CFM CAPACITY OF THE APPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-11 Cont ID  
Sent By ccole Date 2016-07-11 Time 14:37 Rev Time 0.00
Received By ccole Date 2016-07-11 Time 14:37 Sent To  
Notes
2016-07-11 16:13:261ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16070085
 7/11/16
  
 1) SHEET M-111: THE EXCEPTION THAT ALLOWED THE USE OF
 BOOSTER FANS UNDER SECTION 504.6.4.1 IN THE FBC-10
 MECHANICAL CODE WAS REMOVED FROM THE FBC-14 MECHANICAL
 CODE. PLEASE REMOVE THE FAN FROM THE PLAN AND PROVIDE
 THE TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN USING
 TABLE 504.5.1.
  
 2) M-111: REFER TO SECTION 504.6.4.2 AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE DRYER.
  
 3) M-111: REFER TO SECTION 5043.5 AND PROVIDE MAKEUP
 AIR FOR THE DRYER IF THE EXHAUST CAPACITY EXCEEDS 200
 CFMS.
  
 4) M-111: PROVIDE KEYED NOTE #3 AT THE 10X6 DUCT
 CONNECTION IN THE KITCHEN.
  
 5) M-111: PROVIDE AN EXHAUST SYSTEM FOR THE NEW
 COOKTOP- REFER TO SECTION 505.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-08-20 Cont ID  
Sent By tklarge Date 2016-08-20 Time 04:37 Rev Time 0.00
Received By tklarge Date 2016-08-20 Time 03:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 04:30 Rev Time 0.00
Received By tklarge Date 2016-07-23 Time 04:23 Sent To  
Notes
2016-07-23 04:30:121) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW
 FOR THE CHANGES BEING MADE TO THE EXISTING PLUMBING
 SYSTEMM.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE WATER SUPPLY VALVES FOR THE WASHER/DRYER UNIT
 SHALL BE ACCESSIBLE.SHOW ON THE PLANS. 2014
 FBC-PLUMBING SEC.606.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  