Plan Review Details - Permit 16070084
Plan Review Stops For Permit 16070084
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-22 Cont ID  
Sent By jwitmer Date 2016-09-22 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2016-09-21 Time 07:30 Sent To  
Notes
2016-09-22 13:32:01BUILDING PLAN REVIEW
 W. P. B. FOUNDATION PERMIT: 16070084
 W. P. B. PERMIT: 16071078 BUILDING
 ADD: 1718 PARKER AVENUE/ FIRE STATION # 4
 CONT: HEDRICK BROTHERS
 TEL: 561-662-8049
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. SEPT. 22/ 2016
  
 ACTION: BUILDING PROVISO/ REVIEWED ONLY FOR
 FOUNDATION!!!!!!!
  
 1) BUILDING PROVISO: 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.3 PHASED
 APPROVAL. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED.
  
  
 2) TO BE SUBMITTED UNDER THE MAIN PERMIT: CORRECT!!!!
 STRUCTURAL CALCULATIONS BY DAVID CHARLAND HAS NOT
 SIGNED AND SEALED THE INDEX PAGE. 61G15-23.002(2) FL.
 ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION
 & PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-21 Cont ID  
Sent By jwitmer Date 2016-07-21 Time 15:15 Rev Time  
Received By jwitmer Date 2016-07-21 Time 14:34 Sent To  
Notes
2016-07-21 15:15:11BUILDING PLAN REVIEW
 W. P. B. FOUNDATION PERMIT: 16070084
 W. P. B. PERMIT: 16071078 BUILDING
 ADD: 1718 PARKER AVENUE/ FIRE STATION # 4
 CONT: HEDRICK BROTHERS
 TEL: 561-662-8049
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. SEEPT. 21/ 2016
 ACTION: ON HOLD WAITING FOR SIGNED & SEALED SOILS
 REPORT.
  
 REVIEWED ONLY FOR FOUNDATION!!!!!!!
  
 1A) MISSING SOILS REPORT: 2014 FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 1B) TO BE SUBMITTED UNDER THE MAIN PERMIT: CORRECT!!!!
 STRUCTURAL CALCULATIONS BY DAVID CHARLAND HAS NOT
 SIGNED AND SEALED THE INDEX PAGE. 61G15-23.002(2) FL.
 ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION
 & PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-09-13 Cont ID  
Sent By albarran Date 2016-09-13 Time 14:31 Rev Time 0.00
Received By albarran Date 2016-09-13 Time 14:17 Sent To  
Notes
2016-09-13 14:31:31THIS HAD BEEN MISTAKENLY PASSED IN THE SYSTEM BUT THE
 NOTES WERE OBVIOUS AS TO THE FAIL. IT WAS BROUGHT TO MY
 ATTENTION AND CORRECTED TODAY. ITEMS PREVIOUSLY
 REQUESTED FOR THE FOUNDATION REMAIN TO BE PRODUCED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-09-13 Cont ID  
Sent By albarran Date 2016-07-20 Time 11:54 Rev Time 0.00
Received By albarran Date 2016-07-20 Time 10:49 Sent To  
Notes
2016-07-20 11:58:44ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 JOB NAME: WEST PALM BEACH FIRE STATION #4
 JOB ADDRESS: 1718 PARKER AVE.
 DESCRIPTION: FOUNDATION ONLY
 MAST. PERMIT: 16070084
 REVISION: N/A
  
 THE SCOPE OF THIS REVISION IS LIMITED TO THAT INDICATED
 ABOVE AND ON THE PERMIT APPLICATION, (FOUNDATION ONLY).
 THE SUBMITTED PLAN SET DOES NOT INCLUDE THE SITE AND OR
 RISER DIAGRAM. YOU SHALL SUBMIT A SITE PLAN INDICATING
 THE LOCATION OF THE UTILITY TRANSFORMER SERVICE THE
 PREMISES AND THE LOCATION OF THE METER AND MAIN
 DISCONNECTS. FURTHERMORE YOU SHALL INCLUDE AN
 ELECTRICAL RISER DIAGRAM WITH LOAD CALCS FOR THE
 PROPOSED STRUCTURE TO DETERMINE PROPER GROUNDING
 ELECTRODE CONDUCTOR SIZING.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-11-08 Cont ID  
Sent By MJG/NICK Date 2016-11-08 Time   Rev Time 1.00
Received By mgonzale Date 2016-11-08 Time   Sent To I
Notes
2016-11-08 14:05:00RESPOND TO COMMENTS IN WRITING AND IN SEPARATE
 SUBMITTAL (PROVISOS)
  
 #1 ADDRESS STRIPING ALONG PARKER. PAVEMENT WILL HAVE TO
 BE RESTRIPED / TURNING LANE WITH THERMO PLASTIC.
  
 #2 STOP SIGN AT THE INTERSECTION WILL HAVE TO BE
 DESIGNED AT THE CROSSING. ADA RAMP AT THE LOCATION
 SPECIFIED
 GUIDES PEDESTRIANS OUT TO PARKER AND PARK PLACE WHERE
 THERE IS NO RECEIVING ADA RAMPS OR CROSSWALK STRIPING.
  
 #3 DUMPSTER WILL REQUIRE MORE ANGLE TO PROVIDE CITY
 SANITATION TRUCK WITH A DIRECT FRONT LOAD ENTRY. IT'S
 IMPORTANT TO PROVIDE
 A 10' CONCRETE PAD IN FRONT OF THE DUMPSTER WHERE TRUCK
 WEIGHT DOES NOT HINDER ASPHALT.
  
 #4 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 SUBMIT THE SPECIFICATION SHEETS FOR DOMESTIC WATER
 BACKFLOWS RPPA AND FIRE DCDA BACKFLOWS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-09-07 Cont ID  
Sent By cranford Date 2016-09-07 Time 11:01 Rev Time 0.00
Received By cranford Date 2016-09-07 Time 11:01 Sent To  
Notes
2016-09-07 11:01:37NOT REVIEWED. FAILED FOR THIS REVIEW PERIOD. WILL
 REVIEW REVISED SUBMITTAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-09-27 Cont ID  
Sent By pleduc Date 2016-09-27 Time   Rev Time 0.00
Received By pleduc Date 2016-09-27 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-19 Cont ID  
Sent By pleduc Date 2016-07-19 Time   Rev Time 0.00
Received By pleduc Date 2016-07-18 Time 16:21 Sent To  
Notes
2016-07-18 16:43:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THIS APPROVAL IS ONLY FOR THE FOUNDATION.
  
  
  
 1) SHEET COV - THERE IS NO REFERNECE TO ANY FIRE CODE
 COMPLIANCE.
  
 AT MINIMUM PLEASE ENSURE COMPLIANCE WITH THE BELOW
 NOTED CODES:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 UNDERGROUND FIRE LINE WORK SHALL COMPLY WITH NFPA 24,
 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE
 MAINS AND THEIR APPURTENANCES, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
  
  
 2) SHEET COV - THERE IS NO INDICATION OF A FIRE
 SPRINKLER SYSTEM. PER NFPA 1, CHAPTER 13, FIRE
 PROTECTION SYSTEMS.
 13.3.2.3 NEW BUILDINGS HOUSING EMERGENCY FIRE, RESCUE,
 OR AMBULANCE SERVICES SHALL BE PROTECTED THROUGHOUT BY
 APPROVED AUTOMATIC SPRINKLER SYSTEMS.
  
 SHOULD ANY WORK RELATED TO THE FIRE SPRINKLER SYSTEM
 INVOLVE UNDERGROUND WORK PLEASE PROVIDED THE
 APPROPRIATE REVISION OR AS-BUILT.
  
  
 3) SHEET COV - WHERE A FIRE PROTECTION ENGINEERED
 SYSTEM IS PROPOSED, PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 PLEASE PROVIDE AT MINIMUM A SEALED LETTER FROM A
 QUAILIFED ENGINEER OF RECORD INDICATING THE NOTED
 INFORMATION ABOVE FOR THE PROJECT.
  
  
 4) ALL UNDERGROUND FIRE LINES SHALL BE SUBMITTED,
 CONSTURCTED AND INSPECTED PER NFPA 24.
  
 PLEASE ENSURE ALL UNDERGROUND FIRE LINES COMPLY WITH
 THE ABOVE AND INSPECTED BY FIRE AND MECHANICAL PER THE
 CODE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
 ALL OTHER COMMENTS ARE NOTED AS INFORMATIONAL FOR THE
 BUILDING PLAN SUBMITTAL:
  
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
  
  
 1) SHEET 101 A - A NOTE IS INDICATED " RANGE HOOD SEE
 MECHANICAL DRAWINGS FOR DETAIL" NO MECHANICAL SHEET IS
 INCLUDED IN PLAN SUBMITTAL.
  
 PROVIDE APPLICABLE MECHANICAL SHEET.
  
 2) NO SHEETS - NO MECHANCIAL SHEETS ARE INCLUDED IN
 PLAN SUBMITTAL
  
 PROVIDE ALL MECHANICAL SHEETS.
  
 3) NO SHEET - NO REFERENCE IS INDICATED FOR FIRE
 PROTECTION OF THE HOOD SYSTEM. PER NFPA 101, CHAPTER 9
 BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN
 VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE
 IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE
 PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT.
  
 PLEASE PROVIDE AT NOTE AND MINIMUM INDICATING, ALL
 KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH NFPA
 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
  
 4) SHEET A 410 - PER FLORIDA 69A-60.0081; NOTICE
 SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE A NOTE AT MINIMUM INDICATING THE ABOVE.
  
 5) A SHEETS - THERE IS NO DOOR SCHEDULE INCLUDED IN THE
 PLAN SUBMITTAL.
  
 PLEASE PROVIDE THE APPLICABLE DOOR SCHEDULE INCLUDING
 ALL APPLICABLE EXIT HARDWARE AND FIRE RATINGS.
  
  
 6) SHEET A 100 - A GENERATOR AND FUEL TANKS NOTE IS
 INDICATED, WHAT IS THE FUEL SOURCE OF THE GENERATOR?
 THE GENERATOR AND FUEL SOURCE TANKS SHALL BE UNDER
 SEPARATE SHOP DRAWINGS AND PERMITS.
  
 PLEASE PROVIDE A NOTE FOR COMPLIANCE WITH NFPA 110,
 STANDARD FOR EMEGENCY AND STANDBY POWER SYSTEMS AND
 NFPA 54, NATIONAL FUEL GAS CODE.
  
  
  
 7) SHEET A 411 - THERE IS NO HANDRAIL AND/OR GAURDRAIL
 DETAIL FOR THE STAIRS.
  
 PLEASE PROVIDE DETAIL IN COMPLIANCE WITH NFPA 101,
 CHAPTER 7, 7.2.2.4.4 HANDRAIL DETAILS;
 7.2.2.4.4.1 NEW HANDRAILS ON STAIRS SHALL NOT BE LESS
 THAN 34 IN. AND NOT MORE THAN 38 IN. ABOVE THE SURFACE
 OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE
 RAIL FROM THE LEADING EDGE OF THE TREAD.
  
 7.2.2.4.5 GUARD DETAILS. SEE 7.1.8 FOR GUARD
 REQUIREMENTS.
 7.2.2.4.5.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8
 SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD
 FROM THE SURFACE ADJACENT THERETO.
 7.2.2.4.5.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065
 MM) HIGH
  
  
  
 8) SHEET A 411 - THERE IS NO HANDRAIL GAURDRAIL FOR THE
 RAMP.
  
 PLEASE PROVIDE DETAIL IN COMPLIANCE WITH NFPA 101,
 CHAPTER 7, 7.2.5.4 GUARDS AND HANDRAILS. 7.2.5.4.1
 GUARDS COMPLYING WITH 7.2.2.4 SHALL BE PROVIDED FOR
 RAMPS, UNLESS OTHERWISE PROVIDED IN 7.2.5.4.4.
 7.2.5.4.2 HANDRAILS COMPLYING WITH 7.2.2.4 SHALL BE
 PROVIDED ALONG BOTH SIDES OF A RAMP RUN WITH A RISE
 GREATER THAN 6 IN. (150 MM), UNLESS OTHERWISE PROVIDED
 IN 7.2.5.4.4.
 7.2.5.4.3 THE HEIGHT OF HANDRAILS AND GUARDS SHALL BE
 MEASURED VERTICALLY TO THE TOP OF THE GUARD OR RAIL
 FROM THE WALKING SURFACE ADJACENT THERETO.
  
  
  
 9) SHEET E 31 - THERE IS NO INDICATION OF EXIT STAIR
 LIGHTING. 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
  
  
 10) SHEET E 31 - THERE IS NO INDICATIONS OF THE KITCHEN
 EQUIPMENT PLAN.
  
 PLEASE PROVIDE DETAILS.
  
  
 11) FA 2.1 - THERE IS NO 2ND FLOOR FA PALN.
  
 PLEASE PROVIDE.
  
  
 12) SHEET 101 A - A GWH IS INDICATED WITH NO DETAILS.
  
 LP/NG GAS PIPING AND DETAIL SHALL BE SUBMITTED UNDER
 SEPARATE SHOP DRAWINGS.
  
  
 13) IS LP/NG GAS PROPOSED FOR THE STOVE/OVEN? NO DETAIL
 IS PROVIDED.
  
 LP/NG GAS PIPING AND DETAIL SHALL BE SUBMITTED UNDER
 SEPARATE SHOP DRAWINGS.
  
  
  
 14) FIREMAN POLES ARE INDICATED; HOWEVER, THERE IS NO
 DETAIL, I.E. HOLE SIZE, SAFETY EQUIPMENT, POLE TYPE,
 ETC.
  
 PLEASE PROVIDE DETAIL.
  
  
  
 15) A KNOX BOX IS REQUIRED FOR THIS STRUCTURE LOCATED
 IN COORDINATION WITH THE AHJ.
  
 PLEASE PROVIDE A NOTE.
  
  
  
 16) HOW IS CONTROLLED GATE ACCESS PROVIDED? A KNOX KEY
 SWITCH FOR ENTRY IS RECOMMENDED BUT SHALL BE
 COORDINATED WITH THE AHJ?
  
 PLEASE PROVIDE A NOTE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2016-12-06 Cont ID  
Sent By ajones Date 2016-12-06 Time 14:42 Rev Time 0.00
Received By ajones Date 2016-12-06 Time 14:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-28 Cont ID  
Sent By mgonzale Date 2017-03-28 Time 14:59 Rev Time 0.00
Received By lmarchan Date 2016-09-07 Time 08:53 Sent To  
Notes
2016-09-15 08:56:47B35
2016-09-15 08:54:49B35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-09-15 Cont ID  
Sent By cpuell Date 2016-09-15 Time 08:53 Rev Time 0.00
Received By cpuell Date 2016-07-05 Time 10:39 Sent To  
Notes
2016-07-06 10:39:12C02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-07-21 Cont ID  
Sent By jwitmer Date 2016-07-21 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2016-07-21 Time 15:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-09-29 Cont ID  
Sent By gjohnson Date 2016-09-29 Time 08:42 Rev Time 0.00
Received By gjohnson Date 2016-09-29 Time 08:42 Sent To  
Notes
2016-09-29 08:45:06NO PLUMBING UNDER FOUNDATION PERMIT PER SEAN KAUFFMAN
 FROM HEDRICK BROTHERS CONT.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-30 Cont ID  
Sent By tklarge Date 2016-07-30 Time 06:58 Rev Time 0.00
Received By tklarge Date 2016-07-30 Time 04:58 Sent To  
Notes
2016-07-30 06:50:371) SUBMIT THE SPECIFIC SHEETS THAT ARE APPLICABLE ONLY
 FOR THE WORK TO BE DONE FOR THE FOUNDATION ONLY PERMIT.
 THERE ARE IRRIGATION AND LANDSCAPING PLANS, PROPANE GAS
 PLANS, STORM DRAINAGE, ETC. WPB AMEND. TO FBC SEC.
 107.2.1.
 2) IF ANY PIPING FOR THE PLUMBING SYSTEM WILL BE
 INSTALLED UNDER THIS PERMIT, SUBMIT RISER DIAGRAMS FOR
 THE WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 3) IF THE INTERCEPTORS / SEPARATORS ARE BEING INSTALLED
 UNDER THIS PERMIT, SUBMIT SIZING CALCULATIONS FOR EACH
 INTERCEPTOR. THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR AND EACH SEPARATOR SHALL BE APPROVED BY THE
 PLUMBING OFFICIAL PER 2014 FBC-PLUMBING SEC.1003.2.
 4) A SAMPLING PORT IS REQUIRED IN THE DISCHARGE LINE OF
 EACH INTERCEPTOR IN ACCORDANCE WITH CITY ORDINANCE.
 5) THE OIL / SAND SEPARATOR SHALL COMPLY WITH 2014
 FBC-PLUMBING SECS. 1003.4.2.
  
 NOTE: A COMPREHENSIVE PLUMBING PLAN REVIEW COULD NOT BE
 PERFORMED AT THIS TIME AS THE SCOPE OF WORK TO BE DONE
 IS NOT CLEARLY DEFINED ON THE PLANS. ONCE THIS IS
 CLARIFIED, ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 FORTHCCOMING ON THE RE-REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
 .

Review Stop Z ZONING
Rev No 2 Status P Date 2016-10-04 Cont ID  
Sent By   Date 2016-10-04 Time   Rev Time 0.00
Received By kmartin Date 2016-10-04 Time 11:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-07-14 Cont ID  
Sent By kmartin Date 2016-07-14 Time   Rev Time 0.00
Received By kmartin Date 2016-07-14 Time 15:25 Sent To  
Notes
2016-07-14 15:27:08FOUNDATION PERMIT APPROVED 7/14/16.
 FOR ADDITIONAL DETAILS, PLEASE CONTACT KEVIN MARTIN,
 URBAN DESIGN PLANNER (561) 822-1426 [email protected].