Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-12-05 Cont ID  
Sent By cthroop Date 2016-12-05 Time 11:20 Rev Time 0.00
Received By cthroop Date 2016-12-05 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-11-08 Cont ID  
Sent By cthroop Date 2016-11-08 Time 11:32 Rev Time 0.00
Received By cthroop Date 2016-11-08 Time 11:32 Sent To  
Notes
2016-11-08 11:35:37BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. SEPERATE PERMIT REQUIRED FOR 2ND STRUCTURE. PERMITS
 AND PLANS MAY RUN CONCURRENTLY.
  
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS
 DETACHED AND MARK VOID.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-10-03 Cont ID  
Sent By cthroop Date 2016-10-03 Time 10:47 Rev Time 0.00
Received By cthroop Date 2016-10-03 Time 09:27 Sent To  
Notes
2016-10-03 10:49:22BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
  
 1. SEPERATE PERMIT REQUIRED FOR BUILDING B.
 2. PROVIDE WINDOW MULLION PRODUCT APPRO0VALS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW
 MULLION SUBMITTALS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By cthroop Date 2016-07-22 Time 12:56 Rev Time 0.00
Received By cthroop Date 2016-07-19 Time 05:59 Sent To  
Notes
2016-07-22 13:06:12BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/22/16
  
 1. PLANS TO BE SIGNED AND SEALED BY DESIGNER OF RECORD.
 2. PALM BEACH COUNTY IMPACT FEES MAY APPLY.
 3. ROOFING PERMIT REQUIRED.
 4. PROVIDE ENERGY CALCULATIONS.
 5. SEPERATE PERMIT REQUIRED FOR SECOND DWELLING UNIT.
 PERMITS MAY RUN CONCURRENTLY AND SHARE PLANS.
 6. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS.
 7. PROVIDE DETAIL FOR 1 HR RATED WALL. WALL TO RUN FROM
 FOUNDATION TO UNDERSIDE OF ROOF ASSEMBLY PER FBC
 R302.3.
 8. PROVIDE SITE PLAN SHOWING LOCATION OF BUILDINGS AND
 SETBACKS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW AND DOOR SUBMITTALS.
  
 R302.3 TWO-FAMILY DWELLINGS.
 DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE
 SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR
 ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH
 ASTM E 119 OR UL 263. FIRE-RESISTANCE-RATED
 FLOOR/CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND
 BE TIGHT AGAINST THE EXTERIOR WALL, AND WALL ASSEMBLIES
 SHALL EXTEND FROM THE FOUNDATION TO THE UNDERSIDE OF
 THE ROOF SHEATHING.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-27 Cont ID  
Sent By albarran Date 2016-10-27 Time 14:11 Rev Time 0.00
Received By albarran Date 2016-10-27 Time 11:08 Sent To  
Notes
2016-10-27 14:13:21WITH THE EXCEPTION OF A FEW ITEMS WITH RELATION TO THE
 RISER AND LOAD CALCS, ALL OTHER COMMENTS WERE
 SATISFACTORILY ADDRESSED. I HAVE GREEN CLOUDED THE
 CORRECTIONS ON BOTH DRAWINGS FOR FIELD INSPECTOR
 VERIFICATION.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-10-18 Cont ID  
Sent By albarran Date 2016-10-18 Time 19:22 Rev Time 0.00
Received By albarran Date 2016-10-18 Time 12:40 Sent To I
Notes
2016-10-18 19:25:572ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 335 KENILWORTH BLVD.
 DESCRIPTION: INTERIOR REPAIRS TO INCLUDE NEW ELECTRICAL
 AND HVAC
 MASTER PERMIT: 16070049
  
 THIS WAS REVIEWED ONCE BEFORE. THE BELOW COMMENTS ARE
 NUMBERED IN ACCORDANCE WITH THE PREVIOUS COMMENTS. ANY
 GREATER NUMBER REPRESENTS NEW OBSERVATIONS. ADDITIONAL
 CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF SUBMITTED
 CORRECTIONS.
 1. RESPONSE ACCEPTED
 2. RESPONSE ACCEPTED
 3. YOU SHALL CORRECTLY LABEL ALL PANELS ON THE RISER
 DIAGRAM TO MATCH THE PANEL SCHEDULES AND UNIT NUMBERS.
 YOU SHALL CORRECT THE LOAD CALCS AND OCPD FOR EACH UNIT
 AND MULTI DWELLING SERVICE INCLUDING THE LAUNDRY
 CIRCUIT LOADS. KEEP IN MIND THAT THE WATER HEATERS,
 RANGE, LIGHTING AND HVAC ARE CONTINUOUS LOADS. YOU
 SHALL INCLUDE CONDUCTOR SIZING AND PROPOSED INSULATION
 TYPE. THE GROUNDING SHALL COMPLY WITH NEC 250.53. BLDG.
 A RISER IS MISSING THE INTER-SYSTEM BONDING REQUIRED BY
 NEC 250.94.
 4. ADDITIONAL CO (CARBON MONOXIDE) DETECTORS ARE
 REQUIRED FOR BEDROOMS 1 OF BLDG. A.
 5. FBC-ER3905.8: A BLOCK NOTE STATING COMPLIANCE WITH
 THIS SHALL BE PLACED ON THE DRAWINGS.
 6. RESPONSE ACCEPTED
 7. FBC-ER3903.4: YOU INDICATE THAT THERE IS NO ATTIC,
 YET THE DRAWINGS FOR BLDG. A SUGGEST OTHERWISE. MAY I
 SUGGEST THAT THIS BE SWITCHED OUTSIDE THE ATTIC AND
 CONTROLLED WITH A SWITCH THAT HAS A PILOT SO AS TO
 INDICATE IF THE LIGHT IS ACCIDENTLY LEFT ON.
 7. RESPONSE ACCEPTED
 8. RESPONSE ACCEPTED
 9. RESPONSE ACCEPTED
 10. RESPONSE ACCEPTED
 11. PER FBC BLDG. "A" UNITS 1 & 2 BATHROOMS REQUIRE
 MECHANICAL VENTILATION WHENEVER THE ROOM IS OCCUPIED.
 THEREFORE THE EXHAUST FAN SHALL BE CONNECTED TO THE
 LIGHT TO COME ON SIMULTANEOUSLY.
 12. APT. 2 KITCHEN IS MISSING THE REQUIRED OUTLETS.
 13. RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS
 SHALL IN ADDITION TO HAVING AND IN-USE TYPE COVER, BE
 LISTED WEATHER-RESISTANT. A BLOCK NOTE TO THIS SHALL BE
 INCLUDED ON THE DRAWINGS.
 14. FBC-RE3901.7: BLDG. "B" IS MISSING THE EXTERIOR
 OUTLET REQUIRED BY CODE.
 15. FBC-ER3903.4: A LIGHT CONTROLLED BY A WALL SWITCH
 IS REQUIRED IN THE WATER HEATER CLOSET.
 16. FBC-ER404.1: A MINIMUM OF 75% OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE OF THE
 HIGH-EFFICACY TYPE OR HAVE A MINIMUM OF 75% OF THE
 FIXTURES SHALL CONTAIN HIGH-EFFICACY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-12 Cont ID  
Sent By albarran Date 2016-07-12 Time 16:03 Rev Time 0.00
Received By albarran Date 2016-07-12 Time 14:16 Sent To  
Notes
2016-07-12 16:11:381ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. FBC-107.2.5 A SITE PLAN SHOWING THE LOCATION OF ALL
 STRUCTURES ON THE SITE SHALL BE PROVIDED. THIS PLAN
 SHALL INCLUDE THE LOCATION OF EVERY ELECTRICAL SERVICE,
 ELECTRICAL METER & ELECTRICAL SERVICE DISCONNECT. SHOW
 ON THE PLANS THE LOCATION OF THE FPL POLE SERVING THE
 PROPERTY.
 2. NEC 230.2 AS WELL AS FPL?S SERVICE STANDARDS LIMITS
 A SINGLE DROP PER PROPERTY.
 3. THE SUBMITTED DRAWING HAS CONFLICTING INFORMATION.
 THERE ARE TWO BLDGS. BOTH OF WHICH ARE LABELED BLDG. B
 EACH OF WHICH ACCORDING TO THE RISER DIAGRAMS IS
 SUPPOSED TO HAVE TWO APARTMENTS. THE PLAN ONLY SHOWS
 THREE APARTMENTS AND THREE ELECTRICAL PANELS. CORRECT
 ACCORDINGLY.
 4. FBC-R315 YOU SHALL INSTALL CARBON MONOXIDE DETECTORS
 WITHIN 10? OF THE DOOR TO EACH SLEEPING AREA.
 5. FBC-RE3905.8 BOXES FOR CEILING/PADDLE FANS SHALL BE
 LISTED FOR THE APPLICATION
 6. FBC-RE3901.12 A 125V 1 PHASE 15/20 AMP OUTLET IS
 REQUIRED WITHIN 25? OF CONDENSING UNITS OR HVAC
 EQUIPMENT INSIDE AN ATTIC.
 7. FBC-RE3903.4 AT LEAST ONE LIGHTING OUTLET CONTROLLED
 BY A WALL SWITCH CLOSE TO THE USUAL POINT OF ENTRY
 SHALL BE INSTALLED IN ATTICS WHERE EQUIPMENT REQUIRING
 SERVICE IS INSTALLED.
 8. FBC-RE3703.3/NEC210.11/FBC-RE3901.58 A 20
 AMPERE-RATED OUTLET SHALL BE PROVIDED TO SERVE THE
 LAUNDRY AREA.
 9. FBC-RE4101.5/NEC422.33 YOU SHALL HAVE A DISCONNECT
 FOR THE WATER HEATER.
 10. FBC-ER A LEAST 75% OF PERMANENTLY INSTALLED LAMPS
 SHALL BE OF THE HIGH EFFICIENCY TYPE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2016-07-07 Cont ID  
Sent By pleduc Date 2016-07-07 Time   Rev Time 0.00
Received By pleduc Date 2016-07-07 Time 11:31 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-11-21 Cont ID  
Sent By fmittner Date 2016-11-21 Time 14:30 Rev Time 0.00
Received By fmittner Date 2016-11-21 Time 14:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-08-04 Cont ID  
Sent By fmittner Date 2016-08-04 Time 11:49 Rev Time 0.00
Received By fmittner Date 2016-08-04 Time 11:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-11-28 Cont ID  
Sent By skennedy Date 2016-11-28 Time 12:30 Rev Time 0.00
Received By skennedy Date 2016-10-26 Time 11:02 Sent To  
Notes
2016-10-26 11:05:03R15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-10-18 Cont ID  
Sent By albarran Date 2016-10-18 Time 19:52 Rev Time 0.00
Received By albarran Date 2016-09-19 Time 13:53 Sent To  
Notes
2016-10-18 19:55:3310/18/16 COMPLETED THE REVIEW PROCESS AND IS READY FOR
 RESUBMITTAL OF CORRECTIONS. CONTACTED JON PACE VIA
 PHONE AND EMAIL. FILE SENT TO SMALL DENIED DRAWER "P".
 MA
2016-09-19 13:53:58R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 03:16 Rev Time 0.00
Received By tklarge Date 2016-07-01 Time 08:41 Sent To  
Notes
2016-07-27 16:09:37R15
2016-07-05 08:42:21B14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-11-08 Cont ID  
Sent By cthroop Date 2016-11-08 Time 11:32 Rev Time 0.00
Received By cthroop Date 2016-11-08 Time 11:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-10-03 Cont ID  
Sent By cthroop Date 2016-10-03 Time 10:45 Rev Time 0.00
Received By cthroop Date 2016-10-03 Time 09:28 Sent To  
Notes
2016-10-03 10:46:12BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By cthroop Date 2016-07-22 Time 11:29 Rev Time 0.00
Received By cthroop Date 2016-07-22 Time 11:29 Sent To  
Notes
2016-07-22 11:30:33BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/22/16
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-11-14 Cont ID  
Sent By ccole Date 2016-11-14 Time 09:51 Rev Time 0.00
Received By ccole Date 2016-11-14 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-12 Cont ID  
Sent By ccole Date 2016-10-12 Time 15:28 Rev Time 0.00
Received By ccole Date 2016-10-12 Time 15:28 Sent To  
Notes
2016-10-12 15:32:422ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070049
 10/12/16
  
 1) THE AC PLANS MUST BEAR THE SIGNATURE, TITLE BLOCK,
 AND LICENSE NUMBER OF THE AC CONTRACTOR WHO DREW THEM-
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-08 Cont ID  
Sent By ccole Date 2016-07-08 Time 15:31 Rev Time 0.00
Received By ccole Date 2016-07-08 Time 15:31 Sent To  
Notes
2016-07-08 15:49:181ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16070049
 7/8/16
  
 1) PROVIDE MECHANICAL PLANS INCLUDING AN AC EQUIPMENT
 SCHEDULE, DUCT LAYOUT PLAN, AIR DEVICE SCHEDULE, AIR
 HANDLER AND CONDENSER INSTALLATION DETAILS, AND A
 CONDENSATE DISPOSAL PLAN.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 COMPLIANCE WITH SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION, AND ENERGY CALCULATIONS PER SECTION
 R101.4.3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-10-15 Cont ID  
Sent By tklarge Date 2016-10-15 Time 06:29 Rev Time 0.00
Received By tklarge Date 2016-10-15 Time 05:54 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 03:16 Rev Time 0.00
Received By tklarge Date 2016-08-11 Time 02:43 Sent To  
Notes
2016-08-11 03:14:04BUILDING "A".
 1) SUBMIT AN EXISTING FLOOR PLAN THAT SHOWS THE CURRENT
 LOCATION OF ALL THE PLUMBING FIXTURES. THE PLANS ARE
 VAGUE AS TO THE SCOPE OF PLUMBING WORK THAT IS TO BE
 DONE. ARE THE NEW FIXTURES BEING REPLACED IN THE SAME
 EXACT LOCATIONS? CLARIFY THIS ON THE PLANS AND BE
 SPECIFIC. WPB AMEND. TO FBC SEC.107.2.1.
 2) SHOW THE FIXTURE CLEARANCES FOR THE PLUMBING
 FIXTURES IN ACCORDANCE WITH 2014 FBCR-P2705.1.
 3) SHOW THE LENGTH AND WIDTH DIMENSIONS OF ALL THE
 SHOWERS.COMPLY WITH 2014 FBCR- P2708.1.
 4) THE WATER HEATERS ARE SHOWN ON THE EXTERIOR OF THE
 STRUCTURE. INDDICATE IF THEY ARE LOCATED IN AN
 ENCLOSURE OR NOT. THE PLANS SHOW THE WATER HEATERS AS
 "EGH". I AM ASSUMING THIS MEANS "EXISTING GAS HEATER."
 CLARIFY.
 5) THE SUBMITTED SANITARY RISER DOES NOT COMPLY WITH
 THE PLUMBING CODE. COMPLY WITH 2014 FBCR-SEC. P3108.1
 FOR FIXTURES PERMITTED ON A WET VENT. ALSO, REFER TO
 2014 FBCR-SEC. R202 FOR THE DEFINITION OF A BATHROOM
 GROUP.
 6) CLEANOUTS ARE REQUIRED IN THE BASE OF WASTE STACKS
 PER 2104 FBCR SEC.P3005.2.6.
  
 BUILDING "B"
 1) SUBMIT AN EXISTING FLOOR PLAN THAT SHOWS THE CURRENT
 LOCATION OF ALL THE PLUMBING FIXTURES. THE PLANS ARE
 VAGUE AS TO THE SCOPE OF PLUMBING WORK THAT IS TO BE
 DONE. ARE THE NEW FIXTURES BEING REPLACED IN THE SAME
 EXACT LOCATIONS? CLARIFY THIS ON THE PLANS AND BE
 SPECIFIC. WPB AMEND. TO FBC SEC.107.2.1.
 2) SHOW THE FIXTURE CLEARANCES FOR THE PLUMBING
 FIXTURES IN ACCORDANCE WITH 2014 FBCR-P2705.1.
 3) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE
 SHOWER.COMPLY WITH 2014 FBCR- P2708.1.
 4) SUBMIT A SANITARY RISER FOR REVIEW. WPB AMEND. TO
 FBC SEC. 107.3.5.3..
 6) CLEANOUTS ARE REQUIRED IN THE BASE OF WASTE STACKS
 PER 2104 FBCR SEC.P3005.2.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-10-03 Cont ID  
Sent By cthroop Date 2016-10-03 Time 10:46 Rev Time 0.00
Received By cthroop Date 2016-10-03 Time 09:28 Sent To  
Notes
2016-10-03 10:47:01SEPERATE ROOFING PERMIT REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-07-22 Cont ID  
Sent By cthroop Date 2016-07-22 Time 11:30 Rev Time 0.00
Received By cthroop Date 2016-07-22 Time 11:30 Sent To  
Notes
2016-07-22 11:35:15BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/22/16
  
 1. PROVIDE PRODUCT APPROVALS FOR ALL NEW ROOF SYSTEM
 COMPONENTS.
 2. PROVIDE ROOF SHEATHING FASTENER SCHEDULE BASED ON
 WIND LOAD CALC'S.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW AND DOOR SUBMITTALS.
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-11-21 Cont ID  
Sent By fmittner Date 2016-11-21 Time 14:31 Rev Time 0.00
Received By fmittner Date 2016-11-21 Time 14:30 Sent To  
Notes
2016-11-21 14:31:34NEED LANDSCAPE PLAN AND PARKING/SITE PLAN. QUESTIONS
 CONTACT FRIEDERIKE MITTNER AT 822-1457.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-04 Cont ID  
Sent By fmittner Date 2016-08-04 Time 11:51 Rev Time 0.00
Received By fmittner Date 2016-08-04 Time 11:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved