Plan Review Details - Permit 16070008
Plan Review Stops For Permit 16070008
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-05 Cont ID  
Sent By cthroop Date 2016-07-05 Time 08:15 Rev Time 0.00
Received By cthroop Date 2016-07-05 Time 08:15 Sent To E
Notes
2016-07-05 08:23:58BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 7/5/16
  
 1. CONFLICT BETWEEN STATED SCOPE OF WORK (LIMITED DEMO)
 AND DEMOLITION NOTES ON PLANS (ALL INT. WALLS). PLEASE
 CLARIFY.
 2. PLANS DO NOT REFERENCE GOVERNING CODES. (2014 FBC
 5TH EDITION)
 3. MECHANICAL, ELECTRICAL & PLUMBING REVIEWS REQUIRED.
 4. PLANS REQUIRED TO BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL. SUBMITTED PLANS APPEAR TO BE A COPY.
 5. VALUE APPEARS LOW.
 6. OWNERS SIGNATURE ON APPLICATION NOT NOTARIZED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK
 MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT
 ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
 (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE
 REVISED.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By mvaldes Date 2016-07-06 Time 15:11 Rev Time 0.00
Received By mvaldes Date 2016-07-06 Time 15:10 Sent To M
Notes
2016-07-06 15:22:54REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - FINAL APPROVAL REQUIRES COMPLIANCE WITH THE BUILDING
 REVIEWERS COMMENTS.
  
 - ELECTRICAL SUB PERMIT REQUIRED. ALL ELECTRICAL
 CONNECTIONS MUST BE CAPPED OFF AND IF EXISTING PANEL IS
 TO REMAIN AS A TEMPORARY, GFCI OUTLETS SHALL BE
 INSTALLED FOR POWER SOURCE. NEC 590.6
  
 - ELECTRICAL TEMPORARY IS ONLY GOOD FOR A STRICT TIME
 CONSTRAINT OF 90 DAYS. NEC 590.3(B) PLEASE REMOVE ALL
 TEMPORARY WIRING UPON COMPLETION OF CONSTRUCTION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-08 Cont ID  
Sent By gjohnson Date 2016-07-08 Time 14:11 Rev Time 0.00
Received By gjohnson Date 2016-07-01 Time 13:46 Sent To  
Notes
2016-07-06 19:01:57GEORGE JOHNSON
2016-07-01 13:46:15BLDG <5K

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By jvalido Date 2016-07-06 Time 18:58 Rev Time 0.00
Received By jvalido Date 2016-07-06 Time 18:46 Sent To  
Notes
2016-07-06 18:58:42CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 IDENTIFY ON THE PLANS WHAT DUCTS ARE GOING TO BE
 DISCONNECTED AND REMOVED. #6 ON DEMOLITION KEY.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-08 Cont ID  
Sent By gjohnson Date 2016-07-08 Time 13:46 Rev Time 0.00
Received By gjohnson Date 2016-07-08 Time 13:46 Sent To  
Notes
2016-07-08 14:11:161ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. DEMOLITION NOTES ARE CALLING OUT FOR ALL PLUMBING TO
 BE REMOVED AND CAPPED, THE PLAN SHOWS ONLY THE KITCHEN
 AND THE DEMOLITION KEY DOES NOT SHOW ANY PLUMBING.
 THE PERMIT APPLICATION INDICATES NO PLUMBING PLEASE
 CLARIFY WHAT PLUMBING WORK IS BEING DONE IF ANY REMOVE
 ALL REFERENCES TO PLUMBING IF NONE IS BEING DONE.
 PER WPB AMEND TO FBC 107.2.1
  
 2.IF GAS IS BEING CAPPED IT MUST BE NOTED ON PLAN AND A
 GAS SUB PERMIT APPLIED FOR. PER WPB AMEND TO FBC
 107.2.1 - 105.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.