Plan Review Details - Permit 16070007
Plan Review Stops For Permit 16070007
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-09-13 Cont ID  
Sent By cthroop Date 2016-09-13 Time 12:57 Rev Time 0.00
Received By cthroop Date 2016-09-13 Time 12:37 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By cthroop Date 2016-08-10 Time 10:28 Rev Time 0.00
Received By cthroop Date 2016-08-10 Time 09:35 Sent To  
Notes
2016-08-10 10:33:11BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/10/16
  
 1. PALM BEACH COUNTY IMPACT FEES REQUIRED.
 2. ROOFING PERMIT REQUIRED.
 3. HANDRAILS REQUIRED PER FBC R311.7.8 AT NEW LAUNDRY
 ENTRANCE AND MAIN ENTRANCE.
 4. PROVIDE ROOF SHEATHING FASTENER SCHEDULE BASED ON
 DESIGN WIND LOAD SCHEDULE.
 5. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 R311.7.8 HANDRAILS.
 HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF
 EACH CONTINUOUS RUN OF TREADS OR FLIGHT WITH FOUR OR
 MORE RISERS. R311.7.8.1 HEIGHT.
 HANDRAIL HEIGHT, MEASURED VERTICALLY FROM THE SLOPED
 PLANE ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF
 RAMP SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM)
 AND NOT MORE THAN 38 INCHES (965 MM).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW
 MULLION SUBMITTALS.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-21 Cont ID  
Sent By mvaldes Date 2016-09-21 Time 11:18 Rev Time 0.00
Received By mvaldes Date 2016-09-21 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-09-13 Cont ID  
Sent By albarran Date 2016-09-13 Time 16:00 Rev Time 0.00
Received By albarran Date 2016-09-13 Time 14:50 Sent To  
Notes
2016-09-13 16:39:05ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 285 CORDOVA RD
 DESCRIPTION: PLAN REVIEW COMMENTS & CORRECTIONS
 PERMIT # 16070007
  
 THOUGH NOT INDICATED ON RESUBMITTAL FORM, THE NEW
 SUBMITTAL HAS NEW ELECTRICAL SHEETS AND THEREFORE HAD
 TO BE REVIEWED ALL OVER. BELOW PLEASE FIND A LIST OF
 REQUIRED CORRECTIONS. ADDITIONAL CORRECTIONS MAY BE
 REQUIRED AFTER REVIEW OF SUBMITTED CORRECTIONS.
  
 1. NOTE THAT IT IS THE AMBIENT CONDITIONS WHICH
 DETERMINE CONDUCTOR INSULATION TYPE AND NOT THE WIRE
 GAUGE. ALL CONDUCTORS EXPOSED TO DAMP OR WET LOCATIONS
 SHALL BE LISTED ACCORDINGLY REGARDLESS OF GAUGE.
 CORRECT NOTE 12 ON THE ELECTRICAL SHEET.
 2. SHOW ON THE ELECTRICAL PLAN OR PROVIDE A SITE PLAN
 SHOWING THE LOCATION OF THE ELECTRIC UTILITY POLE
 SERVICE THE PROPERTY ALONG WITH THE LOCATION OF THE
 EXISTING METER AND MAIN DISCONNECT ALONG WITH THE NEW
 LOCATION. INDICATE ON THE DRAWING THE LOCATION OF THE
 SERVICE FEEDER WEATHER OVERHEAD OR UNDERGROUND.
 3. FBC-R4002.9 NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS. 15 AND 20 AMPERE, 125 AND 250 VOLT
 RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE AN
 ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15 AND 20 AMPERE,
 125 AND 250 VOLT NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE ?WR?. CORRECT NOTE 10 & 16
 ACCORDINGLY.
 4. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM
 SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS
 SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR
 SIZING AND INSULATION TYPE. FURTHERMORE, IT SHALL BE
 SITE SPECIFIC.
 5. FBC-RE3602.2/NEC 220.82 SERVICE LOAD: THE MINIMUM
 LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE 100 PERCENT OF THE DWELLING UNIT
 LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE
 E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37.
 6. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR. NO SITE TUBES WILL BE ACCEPTED THS VAN BE
 ADDRESSED WITH A BLOCK NOTE.
 7. FBC-ER3901.12 NEC 210.63 HVAC EQUIPMENT SERVICE
 OUTLET. A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED WITHIN 25 FT. OF THE
 EQUIPMENT. THE PLANS DO SHOW THIS RECEPTACLE BUT IT
 APPEARS TO BE BEHIND THE CU IN VIOLATION OF NEC 110.26.
 CORRECT ACCORDINGLY.
 8. FBC-ER404.1 A MINIMUM OF 75% OF THE LAMPS IN
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE
 HIGH-EFFICACY LAMPS OR A MINIMUM OF 75% OF THE
 PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN
 ONLY HIGH EFFICIENCY LAMPS. THIS TOO CAN BE ADDRESSED
 WITH A BLOCK NOTE.
 9. FBC-RE3803.10/NEC 300.5(B) WET LOCATIONS: THE
 INTERIOR OF ENCLOSURES OR RACEWAYS INSTALLED
 UNDERGROUND SHALL BE CONSIDERED TO BE A WET LOCATION.
 INSULATED CONDUCTORS AND CABLES INSTALLED IN SUCH
 ENCLOSURES OR RACEWAYS IN UNDERGROUND INSTALLATIONS
 SHALL BE LISTED FOR USE IN WET LOCATIONS. CONNECTIONS
 OR SPLICES IN AN UNDERGROUND INSTALLATION SHALL BE
 APPROVED FOR WET LOCATIONS. INDICATE PROPOSED CONDUCTOR
 TYPES ON THE ELECTRICAL RISER DIAGRAM.
 10. PLANS REFLECT TWO DIFFERENT AND CONFLICTING
 ELECTRICAL RISER DIAGRAMS. DELETE THE ONE NOT
 APPLICABLE TO THE PERMIT IN QUESTION AND CORRECT THE
 OTHER ACCORDING TO THE COMMENTS ABOVE.
 11. FBC-R3706.2 NEC 408.4(A) REQUIRES THAT YOU PROVIDE
 A PANEL SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY
 INDICATING THE SPECIFIC PURPOSE OF EVERY CIRCUIT.
 PROVIDE A CIRCUIT DIRECTORY FOR EVERY PANEL BEING
 WORKED ON AND HAVE IT MATCH THE ELECTRICAL RISER
 DIAGRAM.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-15 Cont ID  
Sent By albarran Date 2016-07-15 Time 11:18 Rev Time 0.00
Received By albarran Date 2016-07-14 Time 18:34 Sent To  
Notes
2016-07-15 11:18:22IMPORTANT NOTICE:
 1. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR.
 NO SITE TUBES WILL BE ACCEPTED
 2. UNLESS THE HVAC EQUIPMENT IN THE ATTIC IS WITHIN 6?
 OF ENTRY ADHERENCE TO NEC 210.70(3) WILL BE REQUIRED.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 12:06 Rev Time 0.00
Received By gjohnson Date 2016-09-20 Time 12:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2016-08-01 Time   Rev Time 0.00
Received By gjohnson Date 2016-08-01 Time 12:06 Sent To  
Notes
2016-08-01 12:39:281ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PE PIPE UNDER HOUSE TO COOK TOP IS NOT APPROVED. PER
 FBC FUEL GAS 404.17.1 LIMITATIONS. PLASTIC PIPE SHALL
 BE INSTALLED OUTDOORS UNDERGROUND ONLY. PLASTIC PIPE
 SHALL NOT BE USED WITHIN OR UNDER ANY BUILDING OR SLAB
 OR BE OPERATED AT PRESSURES GREATER THAN 100 PSIG (689
 KPA) FOR NATURAL GAS OR 30 PSIG (207 KPA) FOR LP-GAS
  
 2. DRIP OR SEDIMENT TRAPS CAN NOT BE INSTALLED IN-THE
 RUN THEY SHALL BE AT THE 90. PER FBC FUEL GAS 408.4
 SEDIMENT TRAP.
 WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE
 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT
 TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS,
 DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED
 FIREPLACES, GAS FIREPLACES, AND OUTDOOR GRILLS NEED NOT
 BE SO EQUIPPED.
  
 3. THE PE PIPE UP TO THE TEE FOR THE POOL HEATER AND
 TANKLESS SHALL BE 3/4 . PER FBC FUEL GAS TABLE
 402.4(36)
  
 4.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304
  
 5.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 6. THE GALV. PIPE COMING OF METER TO THE PE RISER SHALL
 BE !1/4IN. FBC-2014 FUEL GAS CODE TABLE 402.4(5)

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-07-20 Cont ID  
Sent By njwira Date 2016-07-19 Time 13:30 Rev Time 0.00
Received By fmittner Date 2016-07-20 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 12:06 Rev Time 0.00
Received By gjohnson Date 2016-08-31 Time 11:03 Sent To  
Notes
2016-09-02 11:04:11R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-10 Cont ID  
Sent By cthroop Date 2016-08-10 Time 10:21 Rev Time 0.00
Received By cthroop Date 2016-07-01 Time 15:57 Sent To  
Notes
2016-08-09 17:04:54ROUTED TO CHRIS THROOP 8/9/2016 JDV
2016-07-01 15:57:57R30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By cthroop Date 2016-08-24 Time 11:34 Rev Time 0.00
Received By cthroop Date 2016-08-24 Time 11:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By cthroop Date 2016-08-10 Time 10:21 Rev Time 0.00
Received By cthroop Date 2016-08-10 Time 10:21 Sent To  
Notes
2016-08-10 10:23:24BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/10/16
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-08-09 Cont ID  
Sent By jvalido Date 2016-08-09 Time 16:13 Rev Time 0.00
Received By jvalido Date 2016-08-09 Time 16:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-07-29 Cont ID  
Sent By gjohnson Date 2016-07-29 Time 17:51 Rev Time 0.00
Received By gjohnson Date 2016-07-29 Time 17:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-09-21 Cont ID  
Sent By skennedy Date 2016-09-21 Time 11:04 Rev Time 0.00
Received By skennedy Date 2016-09-21 Time 11:04 Sent To  
Notes
2016-09-21 11:06:22THE CONTRACTOR HAS AGREED TO PROVIDE A ROOFING
 SUBMITTAL AT TIME OF SELECTION OF THE PRODUCTS AS
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-09-13 Cont ID  
Sent By cthroop Date 2016-09-13 Time 12:53 Rev Time 0.00
Received By cthroop Date 2016-09-13 Time 12:37 Sent To  
Notes
2016-09-13 12:57:36 
 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 ACTION: DENIED
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR ROOFING COMPONENTS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-08-10 Cont ID  
Sent By cthroop Date 2016-08-10 Time 10:23 Rev Time 0.00
Received By cthroop Date 2016-08-10 Time 10:23 Sent To  
Notes
2016-08-10 10:28:12BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 ACTION: DENIED
 DATE: 8/10/16
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW ROOF SYSTEM
 COMPONENETS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-27 Cont ID  
Sent By fmittner Date 2016-07-27 Time 13:38 Rev Time 0.00
Received By fmittner Date 2016-07-27 Time 13:38 Sent To  
Notes
2016-07-27 13:39:59SPOKE TO CONTRACTOR, WILL COORDINATE MANGO TREE REMOVAL
 WITH RAY CARANCI. FHM 7/27/16

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-19 Cont ID  
Sent By destro Date 2016-07-19 Time 13:27 Rev Time 0.00
Received By njwira Date 2016-07-19 Time 11:17 Sent To HIST
Notes
2016-07-19 13:30:297/19/16- FAILED
 SF-7
  
 FAILED
 1. REMOVAL OF TREES REQUIRES A TREE ALTERATION PERMIT.
  
 PASSED
 1. BUILDING HEIGHT IS 20FT AND THE REQUIRED LIMIT IS
 30FT.
 2. ONE(1)KITCHEN MEETING THE SINGLE FAMILY DWELLING
 UNIT LIMIT IN THE DISTRICT.
 3. SIDE SETBACK IS 18.8FT. AND THE REQUIRED SETBACK IS
 5FT.
 4. BUILDING IS NOT BUILT INTO THE REAR SETBACK.
 5. MECHANICAL EQUIPMENT IS NOT BEING PLACED IN A
 SETBACK.
  
 PLEASE CONTACT:
 NATHAN WIRA
 (561)822-1442
 [email protected]
  