Plan Review Details - Permit 16061546
Plan Review Stops For Permit 16061546 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-07-12 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-07-12 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-07-12 |
Time |
17:01 |
Sent To |
I |
|
Notes |
2016-07-12 17:20:44 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | SATISFACTORILY ADDRESSED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-06-29 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-06-29 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-06-29 |
Time |
14:08 |
Sent To |
I |
|
Notes |
2016-06-29 15:11:23 | 1ST ELECTRICAL REVIEW NOTES | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) | | | | 1. NEC 215.5: IN ADDITION TO THE RISER DIAGRAM | | SUBMITTED YOU SHALL SUBMIT LOAD CALCS AND A PANEL | | SCHEDULE. | | 2. NEC 250.9: AN INTER-SYSTEM BONDING TERMINAL IS | | REQUIRED AT THE SERVICE. | | 3. NEC 625 PART V: THERE ARE SPECIFIC REQUIREMENTS | | ACCORDING TO THE LOCATION OF THE CHARGERS. YOUR DRAWING | | DOES NOT REFLECT THE LOCATION OF THE CHARGERS THEREFORE | | THE REQUIREMENTS FOR SUCH ARE UNDETERMINED. PROVIDE A | | DOCUMENT INDICATING THE LOCATION OF EACH CHARGER ALONG | | WITH THE WIRING TO EACH. | | 4. EXPLAIN WHAT IS BEING DONE TO RELOCATE FPL FEEDER | | CONDUIT. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-07-12 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-07-12 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-07-11 |
Time |
10:58 |
Sent To |
|
|
Notes |
2016-07-12 17:24:39 | 7/12/16 PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY BIN "A". | | MA | 2016-07-12 10:58:17 | RESUB ROUTED TO MALBARRAN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
F |
Date |
2016-06-29 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-06-29 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-06-28 |
Time |
10:39 |
Sent To |
|
|
Notes |
2016-06-29 15:35:18 | 6/29/16 ELECTRICAL REVIEW FAILED AS NOTED. CONTRACTOR | | NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN "A". | | MA | 2016-06-29 10:40:22 | ELEC -$5000 |
|
|
|