Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-07-14 Cont ID  
Sent By rmcdouga Date 2016-07-14 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2016-07-14 Time 18:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-29 Cont ID  
Sent By rmcdouga Date 2016-06-29 Time 16:54 Rev Time 0.00
Received By rmcdouga Date 2016-06-29 Time 16:54 Sent To  
Notes
2016-06-29 16:54:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER'S LETTER IS FOR EXPOSURE D AND THE RAS
 117 CALCULATIONS SPECIFY EXPOSURE C. PLEASE COORDINATE
 THE DOCUMENTS. FBC 107.2.1
  
 2) THE CALCULATIONS AND LETTER SPECIFY THAT THE
 UNDERLAYMENT IN THE CORNERS REQUIRES TWO (2) ROWS OF
 FASTENERS SPACED 6" O.C. AT THE 4" LAP WITH 4 ROWS AT
 4"O.C. IN THE CORNER FIELD. PROVIDE A DRAWING THAT
 SHOWS THE LOCATION OF THE FASTENERS IN THE CORNER AND
 PERIMETER AREAS IN ORDER TO CLARIFY. FBC 107.2.1.2
 NOTE: ADDING AN ADDITIONAL ROW OF FASTENERS SPACE 6"
 O.C. TO THE 4" LAP WILL NOT WORK BECAUSE THE SPACING
 WILL BE LESS THAN THE MINIMUM FASTENER SPACING OF 4"
 REQUIRED BY RAS117.
  
 3) THE LETTER STATES " AT THE PERIMETER FOR 4' IN EACH
 DIRECTION REQUIRE THAT THE BASE SHEET BE SECURED AT 4"
 O.C. AT THE LAP AND WITH 3 ROWS AT 4" O.C. IN THE
 PERIMETER FIELD". EXPLAIN WHAT IS MEANT BY 4' IN EACH
 DIRECTION IN THE PERIMETER FIELD. FBC 107.2.1
  
 4) THE LETTER IS ADDRESSED TO PALM BEACH COUNTY
 BUILDING DEPARTMENT AND THIS IS THE CITY OF WEST PALM
 BEACH.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-14 Cont ID  
Sent By rmcdouga Date 2016-07-14 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2016-07-14 Time 12:48 Sent To  
Notes
2016-07-14 12:48:40RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-29 Cont ID  
Sent By rmcdouga Date 2016-06-29 Time 16:54 Rev Time 0.00
Received By rmcdouga Date 2016-06-28 Time 09:51 Sent To  
Notes
2016-06-29 09:52:10RMCDOUGAL'S DESK