Plan Review Details - Permit 16061443
Plan Review Stops For Permit 16061443
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2020-05-12 Cont ID  
Sent By shill Date 2020-05-12 Time 14:06 Rev Time 0.00
Received By shill Date 2020-05-12 Time 14:06 Sent To  
Notes
2020-05-12 14:07:08PASSED PER EMAIL FROM SYBILLE WELTER, 5/12/20
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-10-03 Cont ID  
Sent By jgomez Date 2017-10-03 Time 13:04 Rev Time 0.00
Received By shill Date 2017-09-29 Time 17:26 Sent To  
Notes
2017-10-03 13:04:46****PROVISOS****
 ****ISSUED AT APPLICANT'S RISK****
 ****REVISION REQUIRED (SEE ITEM 19)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2. PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3. INFORMATIONAL NO ACTION REQUIRED. 109.3.6 THRESHOLD
 BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4. PROVISO: UNDER A SEPARATE PERMIT. PERIMETER FENCING
 UNDER A SEPARATE PERMIT. PLEASE PROVIDE COMPLIANCE
 WITH: 2014 FBC-B 3306.5 BARRIERS. BARRIERS SHALL BE A
 MINIMUM OF 8 FEET (2438 MM) IN HEIGHT AND SHALL BE
 PLACED ON THE SIDE OF THE WALKWAY NEAREST THE
 CONSTRUCTION. BARRIERS SHALL EXTEND THE ENTIRE LENGTH
 OF THE CONSTRUCTION SITE.
  
 5. PROVISO: UNDER A SEPARATE PERMIT. 2014 FBC0B 3306.2
 WALKWAYS. A WALKWAY SHALL BE PROVIDED FOR PEDESTRIAN
 TRAVEL IN FRONT OF EVERY CONSTRUCTION AND DEMOLITION
 SITE UNLESS THE APPLICABLE GOVERNING AUTHORITY
 AUTHORIZES THE SIDEWALK TO BE FENCED OR CLOSED.
 WALKWAYS SHALL BE OF SUFFICIENT WIDTH TO ACCOMMODATE
 THE PEDESTRIAN TRAFFIC, BUT IN NO CASE SHALL THEY BE
 LESS THAN 4 FEET (1219 MM) IN WIDTH. WALKWAYS SHALL BE
 PROVIDED WITH A DURABLE WALKING SURFACE. WALKWAYS SHALL
 BE ACCESSIBLE IN ACCORDANCE WITH CHAPTER 11 AND SHALL
 BE DESIGNED TO SUPPORT ALL IMPOSED LOADS AND IN NO CASE
 SHALL THE DESIGN LIVE LOAD BE LESS THAN 150 POUNDS PER
 SQUARE FOOT (PSF).
  
 6. PROVISO: UNDER A SEPARATE PERMIT. 2014 FBC-B 3306.7
 COVERED WALKWAYS. COVERED WALKWAYS SHALL HAVE A CLEAR
 HEIGHT OF NOT LESS THAN 8 FEET (2438 MM) AS MEASURED
 FROM THE FLOOR SURFACE TO THE CANOPY OVERHEAD. ADEQUATE
 LIGHTING SHALL BE PROVIDED AT ALL TIMES. COVERED
 WALKWAYS SHALL BE DESIGNED TO SUPPORT ALL IMPOSED
 LOADS. IN NO CASE SHALL THE DESIGN LIVE LOAD BE LESS
 THAN 150 PSF FOR THE ENTIRE STRUCTURE.
  
 7. BUILDING PROVISO: PRODUCT APPROVALS LISTED BELOW CAN
 BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER THE
 DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND DESIGN
 CRITERIA IS REVIEWED AND APPROVED THEN THE SUBMITTALS
 CAN BE SUBMITTED AFTER PERMIT ISSUANCE. 107.3.4.2
 DEFERRED SUBMITTALS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 61G20-3, SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS, MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE AND EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G PRE-ENGINEERED A/C STANDS
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8. BUILDING PROVISO, DEFERRED SUBMITTALS PRODUCT
 APPROVALS & SHOP DRAWINGS.
 IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 9. BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR
 TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10. BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR
 TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11. BUILDING PROVISO: POOL AND JACUZZI ARE NOT PART OF
 THIS PERMIT, WILL REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES. FENCING AND GATES AROUND THE POOL WILL
 REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES.
  
 12. SEPARATE PERMITS (APPLICATION, PLANS, REVIEWS, AND
 FEES) REQUIRED FOR ALL ITEMS OTHER THAN MECHANICAL,
 ELECTRICAL, AND PLUMBING FOR THE BUILDING AS SHOWN ON
 THE PLANS. THIS INCLUDES SIGNS, FIRE ALARM, FIRE
 SPRINKLERS, LANDSCAPING.
  
 13. BUILDING PROVISO/ DEFERRED SUBMITTAL:
 AN APPROVED BUILDING INFORMATION CARD THAT CONTAINS,
 BUT IS NOT LIMITED TO, THE FOLLOWING INFORMATION,
 13.1-13.7:
  
 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES:
 PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE
 BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY
 CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT
 TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING
 POPULATION (I.E., DAY, NIGHT, WEEKEND);
  
 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT
 INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS
 (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND
 THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER,
 EMAIL ADDRESS;
  
 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES:
 THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS,
 COLUMNS, AND ROOF ASSEMBLY);
  
 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF
 EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION
 AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR
 DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT
 STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT
 STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF
 ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF
 ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR
 NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION
 OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY,
 LOCATION OF FREIGHT ELEVATOR BANKS;
  
 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT
 INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF
 BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF
 ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR,
 LOCATION OF NATURAL GAS SERVICE;
  
 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES:
 LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM,
 LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS
 PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF
 DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G.,
 DRY, WET, PRE-ACTION, ETC.); AND
  
 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES:
 LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS
 MATERIAL.
  
 14. BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02
 & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE
 REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 15. BUILDING PROVISO/ DEFERRED SUBMITTAL. ON THE TOP OF
 THE 8 FT. CONCRETE CANOPY WHAT PRODUCT WILL BE USED TO
 KEEP MOISTURE FROM SEEPING INTO THE CONCRETE SLAB AND
 REINFORCEMENT?
  
 16. BUILDING PROVISO/ DEFERRED SUBMITTAL. SHEET A4.01
 THE NORTH WALL ELEVATION ON THE GARAGE LEVELS 3-5 THE
 PLANS SHOW PERFORATED ALUMINUM PANEL SYSTEM. PLEASE
 PROVIDE PRODUCT LITERATURE, AND ENGINEERING ANALYSIS OF
 THE SYSTEM, WITH THE WIND DESIGN CRITERIA AND ANCHORING
 SYSTEMS REVIEWED BY THE ENGINEER OF RECORD. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW. 2014 FBC-B 1503.1 ROOF DECKS SHALL
 BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE
 BUILDING OR STRUCTURE IN ACCORDANCE WITH THE PROVISIONS
 OF THIS CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH THIS CODE AND THE APPROVED
 MANUFACTURER?S INSTRUCTIONS SUCH THAT THE ROOF COVERING
 SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE.
  
 17. SUB PERMITS (APPLICATION, SUB PERMIT FEE OF $80)
 ARE REQUIRED FOR MECHANICAL, ELECTRICAL, PLUMBING AND
 ROOFING PRIOR TO COMMENCEMENT OF WORK.
  
 18. DEFERRED SUBMITTAL: IF ACOUSTIC FLOORING
 UNDERLAYMENT IS PROPOSED, FBC B 603.1, ALLOWABLE
 MATERIALS IN NON COMBUSTIBLE BUILDINGS, SEE ITEM 2,
 EXCEPTION 2, ACOUSTICAL INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723. SUBMIT PRIOR TO
 INSTALLATION.
  
 19. REVISION REQUIRED; PER ARCHITECT, 2 HOUR SHAFT
 DETAIL ON SHEETS A3.05 AND 3.08A (AND ANY OTHER
 AFFECTED LOCATIONS NOT LISTED) WILL BE REVISED (FBC
 BUILDING 703.2.1, NEED HORIZONTAL ASSEMBLY). A REVISION
 IS REQUIRED PRIOR TO INSTALLATION.
  
 20. WHEN AVAILABLE, PROVIDE THE TEST PILE PROGRAM
 REPORT. REPORT IS TO BE REVIEWED BY SEOR PRIOR TO
 SUBMITTAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-07-27 Cont ID  
Sent By shill Date 2017-07-27 Time 11:54 Rev Time 0.00
Received By shill Date 2017-07-24 Time 10:36 Sent To  
Notes
2017-07-27 12:05:55REVISED 8/3/17
 IF ALL OTHER TRADES PASS, A PROVISO IS POSSIBLE UPON
 REQUEST
  
 [email protected]
 561-805-6724
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061443
 ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON 14 STORY
 THRESHOLD BUILDING
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-718-5987 / MARGARET LEON
 E-MAIL: MLEONDADLP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4TH REVIEW
 DATE: 7/27/17
 ACTION: DENIED
  
 5B) SEMI-COMPLIED. SHEET 5 OF 6 THERE IS NO CONTRACTOR
 SIGNATURE NOR NOTARY WORK COMPLETED (SI AGREEMENT). WPB
 AMENDMENT 109.3.6.2 W.P.B, THIS IS REQUIRED PRIOR TO
 PERMIT ISSUANCE.
  
 5E) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THRESHOLD INSPECTION FORMS , GUIDELINES AND POLICIES
 FOR PROJECTS WERE E-MAILED TO:
 [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME
 BACK UNDELIVERABLE. 07/14/2016 11:35 AM.
 [email protected]
  
 42) COMMENT FROM PREVIOUS LIST (REVIEW #3): THE SHEET
 M2.02 IN STAIRWELL # 2 NOTE # 7 INDICATES DUCT IN THE
 STAIRWELL TO HAVE A 2 HOUR FIRE RATING. TO USE
 FLAMEBAR. SHEET A6.01A DETAIL 01 DOES NOT SHOW A DUCT
 GOING THROUGH THE STAIRWELL. SHEET A6.03 DETAILS 03 &
 04 ARE CUT SECTIONS THROUGH THE STAIRWELL 2 BUT AGAIN
 NO DUCTS ARE SHOWN PENETRATING THE STAIRWELL ENCLOSURE.
 2014 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS.
  
 4TH REVIEW - RESPONSE LETTER STATES: "WE ARE PROVIDING
 A 2 HOUR RATED ENCLOSURE THAT ALLOWS MECHANICAL DUCTS
 TO RUN THRU IT WHILE ISOLATING THEM FROM THE STAIR."
  
 THE DETAIL 06 IS LABELED U415, BUT NOT CLEAR WHICH
 OPTION (OF UL U415) IS PROPOSED (SEE UL DIRECTORY;
 MULTIPLE OPTIONS AVAILABLE). THE TOP SHOWS 1/2" FIRE
 SEALANT; SHOULDN'T THIS BE A 2 HOUR HEAD OF WALL DETAIL
 IF USING THE STAIR LANDING AS A PART OF THE
 "ENCLOSURE"? RESPONSE LETTER STATES THAT THE 2 HOUR
 RATED ENCLOSURE ISOLATES THE DUCTS FROM THE STAIR, BUT
 IT APPEARS THAT YOU PROPOSE TO USE THE BOTTOM OF A
 STAIR LANDING AS A PART OF THE DUCT ENCLOSURE (DOES NOT
 APPEAR "ISOLATED"). PROPOSED CONSTRUCTION NOT CLEAR; IS
 THIS TO BE CONSTRUCTED AS A SHAFT, FBC B 713? IF
 PORTIONS OF THE STAIR ITSELF ARE UTILIZED FOR THIS
 ENCLOSURE, HOW HAS HEAT TRANSFER BEEN ADDRESSED? IT
 APPEARS THAT A FIRE IN THE SHAFT COULD RESULT IN LOSS
 OF THE ABILITY TO USE THE STAIR DUE TO HEAT. IT DOES
 NOT APPEAR THAT THE RATING IS TO THE INSIDE AS WELL AS
 THE OUTSIDE; IT APPEARS THAT THE RISK IS GREATER FROM
 THE INSIDE (FIRE RISK FROM DUCT TO INSIDE OF STAIR).
  
 PRIOR TO RESUBMITTING, SEND A DETAIL VIA EMAIL FOR
 PRELIMINARY REVIEW.
  
 43) FROM PREVIOUS LIST, COMMENT #12 UNDER MECHANICAL
 REVIEW #3. THE SHAFT ENCLOSING THE OAR-1 DUCT SHALL BE
 CONTINUOUS THROUGH THE ELEVATOR LOBBY AND GARAGE PER
 FBC B 707.5, 711.4 & 713.5.
  
 4TH REVIEW, RESPONSE IS THAT DUCT IS 2 HOUR RATED AND
 CONTINUOUS, INCLUDING OFFSETS. IT APPEARS THAT RATHER
 THAN PROVIDING A RATED SHAFT, FLAMEBAR IS PROPOSED.
 PLEASE ADVISE WHERE THIS IS PERMITTED IN THE CODE. IF
 THIS IS ALTERNATIVE MATERIALS AND METHODS, THIS MUST BE
 APPROVED BY BUILDING OFFICIAL.
  
 IF REQUESTING VIA ALTERNATIVE MATERIALS AND METHODS FBC
 104.11 - THIS SHOULD BE REQUESTED, IN WRITING VIA A
 SIGNED AND SEALED LETTER: "AN ALTERNATIVE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL BE APPROVED
 WHERE THE BUILDING OFFICIAL FINDS THAT THE PROPOSED
 DESIGN IS SATISFACTORY AND COMPLIES WITH THE INTENT OF
 THE PROVISIONS OF THIS CODE, AND THAT THE MATERIAL,
 METHOD OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY."
  
 ALL INFORMATION - PRODUCT DATA SHEETS, ENGINEERING
 ANALYSIS, TEST REPORTS, ETC. AS APPLICABLE SHOULD BE
 SUBMITTED WITH THE LETTER.
  
 44) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 45) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NEW COMMENTS:
  
 ** THERE IS A DISCREPANCY IN PROPOSED FFE BETWEEN
 CIVILS AND ARCHITECTURAL PAGES. SHEET C3 (AND OTHER
 PAGES) SPECIFY A FFE OF 15.50 NGVD29. SHEET A1.11
 SPECIFIES A FFE OF 13.75 NGVD29 (1.75' DISCREPANCY). AN
 EMAIL WAS SENT TO APPLICANT FOR CLARIFICATION. THIS
 POTENTIALLY AFFECTS CONNECTION TO CITY SYSTEMS (WATER,
 SEWER, ETC.) AND ACCESSIBILITY (ACCESSIBLE ROUTE), FBC
 2014 ACCESSIBILITY.
  
 PLEASE EITHER EXPLAIN THE DISCREPANCY OR SEND, VIA
 EMAIL, HOW THIS WILL BE ADDRESSED (PROVISO ITEM,
 REVISION MAY BE REQUIRED).
  
 ** FBC B TABLE 1607.1, ROOF SURFACES SUBJECT TO
 MAINTENANCE WORKERS, 300# LIVE LOAD REQUIRED, S1.01.
 THIS CAN BE A PROVISO ITEM UPON REQUEST (OR CLARIFY,
 VIA EMAIL, IF THERE IS NO EQUIPMENT ON THE ROOF).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-03-21 Cont ID  
Sent By jwitmer Date 2017-03-21 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2017-03-20 Time 11:11 Sent To  
Notes
2017-03-21 14:45:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061443
 ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON 14 STORY
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-718-5987 / MARGARET LEON
 E-MAIL: MLEONDADLP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. MARCH 21/2017
 ACTION: DENIED
  
 1) COMPLIED. 13 STORIES INCLUDING THE HABITABLE POOL,
 POOL DECK AND A2 DELI/ RESTAURANT AREAS.
  
 2) NOTICE: ART IN PUBLIC PLACES.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER
 ART IN PUBLIC PLACES COORDINATOR
 TEL: 822-1515
 E-MAIL: [email protected]
 WEBSITE: WPB.ORG/AIPP/
  
 3) 3RD REQUEST, TO BE SUBMITTED WHEN CONTRACTOR SUBMITS
 FOR PERMIT. THIS MAIN BUILDING PERMIT WILL INCLUDE THE
 FEES FOR THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING
 PERMITS. WHEN THE GENERAL CONTRACTOR COMES IN FOR A
 BUILDING PERMIT WITH THE SIGNED PERMIT APPLICATION FORM
 BY THE QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE ,
 IRRIGATION, TEST PILE, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR
 VALUE FROM THE OVERALL BUILDING VALUE OF
 $33,000,000.00. THE REMAINING BALANCE WILL BE
 AFFECTIVELY THE VALUE OF THE BUILDING YOU WILL BE
 PAYING FOR THIS PERMIT. THE BUILDING DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 108.3 BUILDING PERMIT VALUATION.
  
 4) SEMI-COMPLIED. PLEASE SHOW COMPLIANCE BY THE 2014
 FBC-ENERGY CODE. SEE MECHANICAL COMMENTS, THERE ARE
 NUMEROUS OMISSIONS AND INCONSISTENCIES SEE MECH.
 COMMENT # 1.
  
 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 5B) SEMI-COMPLIED. SHEET 5 OF 6 THERE IS NO CONTRACTOR
 SIGNATURE NOR NOTARY WORK COMPLETED. THIS SHEET WE WILL
 ACCEPT THE BOTTOM SIGNATURE AND SEAL OF THE ENGINEER OF
 RECORD.
 THRESHOLD INSPECTOR FORMS: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT.
  
 5C) COMPLIED. ARCHITECTURAL AND STRUCTURAL SHEETS.
 THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4/ 633 FLORIDA STATUTE.
  
 5D) COMPLIED. THE SPECIAL INSPECTORS ONSITE
 REPRESENTATIVE MARK PINA .
  
 5E) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THRESHOLD INSPECTION FORMS , GUIDELINES AND POLICIES
 FOR PROJECTS WERE E-MAILED TO:
 [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME
 BACK UNDELIVERABLE. 07/14/2016 11:35 AM.
 [email protected]
  
 5F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 5G) PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 5H) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 5H) INFORMATIONAL NO ACTION REQUIRED. 109.3.6 THRESHOLD
 BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 6) COMPLIED. UNITY OF TITLE.
  
 7) PROVISO: UNDER A SEPARATE PERMIT. PERIMETER FENCING
 UNDER A SEPARATE PERMIT. PLEASE PROVIDE COMPLIANCE
 WITH: 2014 FBC-B 3306.5 BARRIERS. BARRIERS SHALL BE A
 MINIMUM OF 8 FEET (2438 MM) IN HEIGHT AND SHALL BE
 PLACED ON THE SIDE OF THE WALKWAY NEAREST THE
 CONSTRUCTION. BARRIERS SHALL EXTEND THE ENTIRE LENGTH
 OF THE CONSTRUCTION SITE.
  
 8) PROVISO: UNDER A SEPARATE PERMIT. 2014 FBC0B 3306.2
 WALKWAYS. A WALKWAY SHALL BE PROVIDED FOR PEDESTRIAN
 TRAVEL IN FRONT OF EVERY CONSTRUCTION AND DEMOLITION
 SITE UNLESS THE APPLICABLE GOVERNING AUTHORITY
 AUTHORIZES THE SIDEWALK TO BE FENCED OR CLOSED.
 WALKWAYS SHALL BE OF SUFFICIENT WIDTH TO ACCOMMODATE
 THE PEDESTRIAN TRAFFIC, BUT IN NO CASE SHALL THEY BE
 LESS THAN 4 FEET (1219 MM) IN WIDTH. WALKWAYS SHALL BE
 PROVIDED WITH A DURABLE WALKING SURFACE. WALKWAYS SHALL
 BE ACCESSIBLE IN ACCORDANCE WITH CHAPTER 11 AND SHALL
 BE DESIGNED TO SUPPORT ALL IMPOSED LOADS AND IN NO CASE
 SHALL THE DESIGN LIVE LOAD BE LESS THAN 150 POUNDS PER
 SQUARE FOOT (PSF). WILL THE WALKWAYS ON THE SOUTH SIDE
 OF TRINITY PLACE BE CLOSED?
  
 9) PROVISO: UNDER A SEPARATE PERMIT. 2014 FBC-B 3306.7
 COVERED WALKWAYS. COVERED WALKWAYS SHALL HAVE A CLEAR
 HEIGHT OF NOT LESS THAN 8 FEET (2438 MM) AS MEASURED
 FROM THE FLOOR SURFACE TO THE CANOPY OVERHEAD. ADEQUATE
 LIGHTING SHALL BE PROVIDED AT ALL TIMES. COVERED
 WALKWAYS SHALL BE DESIGNED TO SUPPORT ALL IMPOSED
 LOADS. IN NO CASE SHALL THE DESIGN LIVE LOAD BE LESS
 THAN 150 PSF FOR THE ENTIRE STRUCTURE.
  
 10) COMPLIED. POLLUTION PREVENTION PLAN. 2014 FBC-B
 3307.
  
 11) PROVISO: DEFERRED SUBMITTAL . 2014 FBC-B 3306.9
 ADJACENT TO EXCAVATIONS. STRUCTURAL NOTES S1.01.
  
 11A) PROVISO: DEFERRED SUBMITTAL. STRUCTURAL NOTES
 S1.01 AND SOILS REPORT BY LANGAN ENGINEERING SOILS
 REPORT MAY 21/ 2015. 2014 FBC-B 3307.1 PROTECTION
 REQUIRED. ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL
 BE PROTECTED FROM DAMAGE DURING CONSTRUCTION AND
 DEMOLITION WORK. PROTECTION SHALL BE PROVIDED FOR
 FOOTINGS, FOUNDATIONS, PARTY WALLS, CHIMNEYS, SKYLIGHTS
 AND ROOFS. WITH THE EXCAVATION AND AUGER CAST PILE HOW
 WILL THE BUILDING TO THE SOUTH BE PROTECTED FROM
 SETTLEMENT?
  
 11B) COMPLIED. NOTED ON PLAN. 2014 FBC-B 3307.1 THE
 PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL
 PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING
 BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE
 MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE
 PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT
 LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE
 OF THE EXCAVATION.
  
 12) COMPLIED. NOTED ON PLAN. WHEN EXCAVATING WILL THE
 EXCESS SOILS BE STORED ON SITE? 2014 FBC-B 3304.1.2
 SURCHARGE. NO FILL OR OTHER SURCHARGE LOADS SHALL BE
 PLACED ADJACENT TO ANY BUILDING OR STRUCTURE UNLESS
 SUCH BUILDING OR STRUCTURE IS CAPABLE OF WITHSTANDING
 THE ADDITIONAL LOADS CAUSED BY THE FILL OR SURCHARGE.
 EXISTING FOOTINGS OR FOUNDATIONS WHICH CAN BE AFFECTED
 BY ANY EXCAVATION SHALL BE UNDERPINNED ADEQUATELY OR
 OTHERWISE PROTECTED AGAINST SETTLEMENT AND SHALL BE
 PROTECTED AGAINST LATER MOVEMENT.
  
 13-19) COMPLIED.
  
 20) SHEET A0.01;
 20A-C)COMPLIED.
  
  
 20D) BUILDING PROVISO: PRODUCT APPROVALS LISTED BELOW
 CAN BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER
 THE DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND
 DESIGN CRITERIA IS REVIEWED AND APPROVED THEN THE
 SUBMITTALS CAN BE SUBMITTED AFTER PERMIT ISSUANCE.
 107.3.4.2 DEFERRED SUBMITTALS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS, MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE AND EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G PRE-ENGINEERED A/C STANDS
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 20E) BUILDING PROVISO, DEFERRED SUBMITTALS PRODUCT
 APPROVALS & SHOP DRAWINGS.
 IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 20F) COMPLIED. ROOFING PRODUCT APPROVALS:
 MIAMI-DADE NOA 15-1026.10 SEAMAN CORP FIBER TITE SINGLE
 PLY ROOF SYSTEMS OVER CONCRETE DECK PAGE 25 OF 51 -240
 PSF LIMITATION # 9.
 FLORIDA APPROVAL 7989-R1 ATLAS ROOFING INSULATION AC
 FOAM III.
  
  
 21A) COMPLIED.
  
 21B) SEMI COMPLIED. ON SHEET A2.05 THE PLANS SHOW A
 TOTAL OF 3 ACCESSIBLE PARKING SPACES. IN THE
 RECONFIGURATION OF ACCESSIBLE PARKING SPACES THE
 PARKING SPACE ACCESS AISLE HAS BEEN LEFT OUT. 2014
 FBC-ACCESSIBILITY 502.3 (1-3) PARKING SPACE ACCESS
 AISLE. PLEASE ALSO NOTE ON SHEETS A2.03 AND A2.04 IN
 ALL NON- PARKING AREAS THE FLOOR IS DIAGONALLY STRIPED.
  
 22-24A) COMPLIED
  
 24B) COMPLIED. SHEET A1.12 LIFE SAFETY 3 STAIRS ARE A
 MINIMUM OF 57 INCHES/ 0.3= 190 OCC. X 3= 570 OCCUPANTS.
  
 24C) COMPLIED. CONFERENCE ROOMS 2 MEANS OF EGRESS.
  
 24D) 3RD REQUEST FOR CODE COMPLIANCE FOR A 2 STORY
 ATRIUM. THE RESPONSE INDICATES THIS IS NOT A 2 STORY
 ATRIUM BECAUSE IT DOES NOT COMMUNICATE WITH ANY OTHER
 FLOOR. SHEET A1.12 THE 2ND STORY HAS A NOTE STATING
 SMOKE SEPARATION FULL HEIGHT GLAZING WITH TYCO WS
 SPRINKLERS. THIS IS THE EXCEPTION 1 FOR 404.6
 ENCLOSURES OF ATRIUMS. WILL NEED TO MEET THE EXCEPTION
 1.1 AND 1.2 GLAZING IN A GASKETED FRAME.
 FBC-B 404.6 ATRIUMS SPACES SHALL BE SEPARATED FROM
 ADJACENT SPACES BY A 1 HOUR FIRE BARRIER.
  
 IF YOU DO NOT HAVE A FIRE BARRIER BETWEEN THE 1ST FLOOR
 AND SECOND FLOOR THEY WILL COMMUNICATE, THUS BEING A 2
 STORY ATRIUM. THE FIRE BARRIER BETWEEN THE 1ST FLOOR
 FIRE AREA AND 2ND FLOOR FIRE AREA IS A COMMON WALL A
 PORTION OF THE WALL IS GLAZED. COMPLIANCE WITH FBC-B
 707.3.10 AND TABLE 707.3.10 SHALL BE ACHIEVED . PLEASE
 ALSO REVIEW 707.6 OPENINGS IN FIRE BARRIERS AND THEIR
 EXCEPTIONS, PLEASE PROVIDE WHICH METHOD OF CODE
 COMPLIANCE WILL BE ACHIEVED.
  
 24E) COMPLIED.
  
 25A-D) COMPLIED.
  
 25E) SEMI-COMPLIED. SHEET A6.12 THE NOTE FOR BI-PARTING
 DOORS IS ONLY ON THE ONE FLOOR, PLEASE PLACE NOTE FOR
 ALL LEVELS SHOWING THIS IS A CLOSED SHAFT WITH OPENING
 PROTECTIVES IN COMPLIANCE WITH FBC-B 716.5 AND ALSO FOR
 FALL PROTECTION IN COMPLIANCE WITH FBC-B 1013.2 GUARDS.
  
 25F) COMPLIED.
  
 25G) SEMI-COMPLIED. SEE COMMENT 21B. SHEET A2.05 LIFE
 SAFETY PLAN INDICATES 2 ACCESSIBLE PARKING STALLS WITH
 COLUMNS IN THE ACCESS AISLE. PLEASE PROVIDE THE CLEAR
 WIDTH FROM THE COLUMN TO THE ACCESSIBLE PARKING STALL.
 FBC-ACCESSIBILITY CODE 502.3.1 WIDTH. ACCESS AISLES
 SERVING CAR AND VAN PARKING SPACES SHALL BE 60 INCHES
 (1525 MM) WIDE MINIMUM.
  
  
  
 26) SHEET A1.16 6TH FLOOR LIFE SAFETY PLAN & A7.05 &
 A7.06 ENLARGED FLOOR PLAN 6TH FLOOR.
 26A-E) COMPLIED.
  
  
 26F) BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR
 TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26G) BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR
 TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26H) **IN REVIEW BY THE BUILDING OFFICIAL / ALTERNATE
 MATERIALS & METHODS OF CONSTRUCTION 107.11**
 COMMON COMMENT FOR ALL FLOORS (6-12) WHERE THE
 ALLOWABLE COMMON PATH OF TRAVEL IS EXCEEDED. EXAMPLE:
 ROOMS 604 & 605 FROM THE MOST REMOTE POINT IN THE SUITE
 TO THE NEAREST VERTICAL EXIT IS OVER THE ALLOWABLE 75
 FT. TO ACHIEVE THE ALLOWABLE 75 FT. A RATED WALL IS
 INSTALLED IN THE EXIT ACCESS CORRIDOR, ON THE DOOR
 SCHEDULE THIS DOOR IS NOT FIRE RATED. PLEASE PROVIDE A
 CODE SECTION WHERE THIS IS ALLOWED TO BE CONSIDERED
 CODE COMPLIANT. 2014 FBC-B TABLE 1014.3. DEFINITION:
 COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT
 ACCESS WHICH THE OCCUPANTS ARE REQUIRED TO TRAVERSE
 BEFORE TWO SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL
 TO TWO EXITS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON
 PATHS OF TRAVEL. COMMON PATHS OF EGRESS TRAVEL SHALL BE
 INCLUDED WITHIN THE PERMITTED TRAVEL DISTANCE.
  
 27) **IN REVIEW BY THE BUILDING OFFICIAL / ALTERNATE
 MATERIALS & METHODS OF CONSTRUCTION 107.11**
 SHEET A1.18 & A7.09 & A7.10. THE 8TH, 10TH & 12TH
 FLOORS. THIS COMMENT FOR THE ROOMS 818,819,1018,
 1019,1218 & 1219 ALL EXCEED THE ALLOWABLE 75 FT.
 ALLOWABLE COMMON PATH OF TRAVEL OF 75 FT. 2014 FBC-B
 TABLE 1014.3
  
 28) COMPLIED.
  
 29) SHEET A2.09 & A7.41 13TH FLOOR ROOFTOP GARDEN:
  
 29A-E) COMPLIED.
  
 29F) 3RD REQUEST. SHEET A6.14 SHOWS THE ROOF HATCH TO
 BE 2.5 FT X 3 FT. = 7.5 FEET NOT 16 FEET. SEE COMMENTS
 BELOW. STAIRWELL # 1 SHOWS A LADDER TO GAIN ACCESS TO
 THE ROOF TOP EQUIPMENT. PLEASE REVIEW :
 2014 FBC-B 1009.16.1 EXCEPTION. IN BUILDINGS WITHOUT AN
 OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE PERMITTED TO
 BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE
 FEET IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET .
  
 30) BUILDING PROVISO: POOL AND JACUZZI ARE NOT PART OF
 THIS PERMIT, WILL REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES.
  
 31) BUILDING PROVISO: FENCING AND GATES AROUND THE POOL
 WILL REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED
 FEES.
  
  
  
  
  
 32-34) COMPLIED.
  
 35) BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02
 & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE
 REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 36A-B) COMPLIED.
  
 36C) BUILDING PROVISO/ DEFERRED SUBMITTAL. ON THE TOP
 OF THE 8 FT. CONCRETE CANOPY WHAT PRODUCT WILL BE USED
 TO KEEP MOISTURE FROM SEEPING INTO THE CONCRETE SLAB
 AND REINFORCEMENT?
  
 37) BUILDING PROVISO/ DEFERRED SUBMITTAL. SHEET A4.01
 THE NORTH WALL ELEVATION ON THE GARAGE LEVELS 3-5 THE
 PLANS SHOW PERFORATED ALUMINUM PANEL SYSTEM. PLEASE
 PROVIDE PRODUCT LITERATURE, AND ENGINEERING ANALYSIS OF
 THE SYSTEM, WITH THE WIND DESIGN CRITERIA AND ANCHORING
 SYSTEMS REVIEWED BY THE ENGINEER OF RECORD. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW. 2014 FBC-B 1503.1 ROOF DECKS SHALL
 BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE
 BUILDING OR STRUCTURE IN ACCORDANCE WITH THE PROVISIONS
 OF THIS CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH THIS CODE AND THE APPROVED
 MANUFACTURER?S INSTRUCTIONS SUCH THAT THE ROOF COVERING
 SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE.
  
 38) COMPLIED. FIRE COMMAND CENTER LAYOUT. FBC-B
 911.1.4.
  
  
  
 38A) PLEASE SHOW COMPLIANCE WITH FBC-B 911.1.4. LAYOUT
 APPROVAL. A LAYOUT OF THE FIRE COMMAND CENTER AND ALL
 FEATURES REQUIRED BY THIS SECTION TO BE CONTAINED
 THEREIN SHALL BE SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION.
  
 38B) 911.1.5 REQUIRED FEATURES.
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES:
  
 1-5) SHEET E4.02
  
 6. COMPLIED 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED
 IN THE BUILDING.
  
 7-12) E4.02.
  
 BUILDING PROVISO/ DEFERRED SUBMITTAL:
 13. AN APPROVED BUILDING INFORMATION CARD THAT
 CONTAINS, BUT IS NOT LIMITED TO, THE FOLLOWING
 INFORMATION, 13.1-13.7:
  
 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES:
 PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE
 BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY
 CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT
 TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING
 POPULATION (I.E., DAY, NIGHT, WEEKEND);
  
 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT
 INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS
 (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND
 THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER,
 EMAIL ADDRESS;
  
 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES:
 THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS,
 COLUMNS, AND ROOF ASSEMBLY);
  
 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF
 EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION
 AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR
 DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT
 STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT
 STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF
 ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF
 ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR
 NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION
 OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY,
 LOCATION OF FREIGHT ELEVATOR BANKS;
  
 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT
 INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF
 BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF
 ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR,
 LOCATION OF NATURAL GAS SERVICE;
  
 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES:
 LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM,
 LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS
 PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF
 DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G.,
 DRY, WET, PRE-ACTION, ETC.); AND
  
 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES:
 LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS
 MATERIAL.
  
 14. COMPLIED. WORK TABLE.
  
 15.COMPLIED. E4.02. GENERATOR SUPERVISION DEVICES,
 MANUAL START AND TRANSFER FEATURES. E4.02
  
 16. COMPLIED. E4.02. PUBLIC ADDRESS SYSTEM, WHERE
 SPECIFICALLY REQUIRED BY OTHER SECTIONS OF THIS CODE.
  
 17 COMPLIED. E4.02. . ELEVATOR FIRE RECALL SWITCH IN
 ACCORDANCE WITH ASME A17.1.
  
 18. COMPLIED. E4.02. ELEVATOR EMERGENCY OR STANDBY
 POWER SELECTOR SWITCH(ES), WHERE EMERGENCY OR STANDBY
 POWER IS PROVIDED.
  
 39) COMPLIED. 2014 FBC-B 403.5.3 STAIRWAY DOOR
 OPERATION.
  
 40) COMPLIED. 909.4 ANALYSIS, SMOKE CONTROL.
  
 41) COMPLIED. FBC-B 403.5.5 LUMINOUS EGRESS PATH
 MARKINGS.
  
 42) NEW COMMENT, COMMENT #9 UNDER THIS MECHANICAL
 REVIEW. THE SHEET M2.02 IN STAIRWELL # 2 NOTE # 7
 INDICATES DUCT IN THE STAIRWELL TO HAVE A 2 HOUR FIRE
 RATING. TO USE FLAMEBAR. SHEET A6.01A DETAIL 01 DOES
 NOT SHOW A DUCT GOING THROUGH THE STAIRWELL. SHEET
 A6.03 DETAILS 03 & 04 ARE CUT SECTIONS THROUGH THE
 STAIRWELL 2 BUT AGAIN NO DUCTS ARE SHOWN PENETRATING
 THE STAIRWELL ENCLOSURE.
 2014 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL BE NO PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS.
  
 43) NEW COMMENT, COMMENT #12 UNDER THIS MECHANICAL
 REVIEW. THE SHAFT ENCLOSING THE OAR-1 DUCT SHALL BE
 CONTINUOUS THROUGH THE ELEVATOR LOBBY AND GARAGE PER
 FBC ?B 707.5, 711.4 & 713.5.
  
 44) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 45) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-01-12 Cont ID  
Sent By jwitmer Date 2016-12-13 Time   Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time 13:53 Sent To  
Notes
2016-12-14 16:28:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061443
 ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-718-5987 / MARGARET LEON
 E-MAIL: MLEONDADLP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. DEC.13/2016
 ACTION: DENIED
  
 1) COMPLIED. 13 STORIES INCLUDING THE HABITABLE POOL,
 POOL DECK AND A2 DELI/ RESTAURANT AREAS.
  
 2) NOTICE: ART IN PUBLIC PLACES.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER
 ART IN PUBLIC PLACES COORDINATOR
 TEL: 822-1515
 E-MAIL: [email protected]
 WEBSITE: WPB.ORG/AIPP/
  
  
 3) 2ND REQUEST, TO BE SUBMITTED WHEN CONTRACTOR SUBMITS
 FOR PERMIT. THIS MAIN BUILDING PERMIT WILL INCLUDE THE
 FEES FOR THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING
 PERMITS. WHEN THE GENERAL CONTRACTOR COMES IN FOR A
 BUILDING PERMIT WITH THE SIGNED PERMIT APPLICATION FORM
 BY THE QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE ,
 IRRIGATION, TEST PILE, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR
 VALUE FROM THE OVERALL BUILDING VALUE OF
 $33,000,000.00. THE REMAINING BALANCE WILL BE
 AFFECTIVELY THE VALUE OF THE BUILDING YOU WILL BE
 PAYING FOR THIS PERMIT. THE BUILDING DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 108.3 BUILDING PERMIT VALUATION.
  
 4) SEMI-COMPLIED. PLEASE SHOW COMPLIANCE BY THE 2014
 FBC-ENERGY CODE. SEE MECHANICAL COMMENTS, THERE ARE
 NUMEROUS OMISSIONS AND INCONSISTENCIES SEE MECH.
 COMMENT # 1.
  
 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN.
  
 5B) SEMI-COMPLIED. THE SUBMITTED FORMS WERE
 SEMI-COMPLETED, SHEET 3 OF 6 MISSING THE SPECIAL
 INSPECTOR SIGNATURE, DATE AND NOTARY NOTED SEE PREVIOUS
 PAGE. SIGNATURE FROM THE SPECIAL INSPECTOR PAGE 3 OF 6
 AND HAVE THE JOBSITE INSPECTOR REFILE THE FORM SO ALL
 THE SIGNATURES ARE ON THE SAME SHEET.
 SHEET 5 OF 6 THERE IS NO CONTRACTOR SIGNATURE NOR
 NOTARY WORK COMPLETED. THIS SHEET WE WILL ACCEPT THE
 BOTTOM SIGNATURE AND SEAL OF THE ENGINEER OF RECORD.
 THRESHOLD INSPECTOR FORMS: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT.
  
  
 5C) COMPLIED. ARCHITECTURAL AND STRUCTURAL SHEETS.
 THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4/ 633 FLORIDA STATUTE.
  
 5D) THE SPECIAL INSPECTORS ONSITE REPRESENTATIVE MARK
 PINA HAS PRODUCED A RESUME? BUT THE RESUME DOES NOT
 INCLUDE ANY POST TENSION SLAB INSPECTION HISTORY.
 BEFORE THIS INSPECTOR CAN BE APPROVED AS THE PRIMARY
 JOBSITE INSPECTOR, THERE WILL NEED TO SHOW A HISTORY OF
 THIS TYPE OF INSPECTION. 61G15-35.004.
  
 WILL THERE BE MORE THAN ONE REPRESENTATIVE FROM THE
 ENGINEERING COMPANY DOING THE STRUCTURAL THRESHOLD
 INSPECTIONS?
  
  
 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 5E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THRESHOLD INSPECTION FORMS , GUIDELINES AND POLICIES
 FOR PROJECTS WERE E-MAILED TO:
 [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME
 BACK UNDELIVERABLE. 07/14/2016 11:35 AM.
 [email protected]
  
 5F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 5G) PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 5H) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 5H) INFORMATIONAL NO ACTION REQUIRED. 109.3.6 THRESHOLD
 BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 6) 2ND REQUEST, IN THE PROCESS OF EITHER UNITY OF TITLE
 OR REPLAT. SHEET C-01 INDICATES THE PROPOSED SITE IS
 MADE UP OF 4 LOTS. UNDER THE 2014 FBC-B TABLE 602,
 BUILDINGS CANNOT BE BUILT OVER PROPERTY LINES. EITHER A
 REPLAT OF THE 4 LOTS WILL NEED TO OCCUR OR A UNITY OF
 TITLE.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT
 FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE. SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 7) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE
 PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 8) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE
 PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY
 CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE
 GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE
 FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH
 TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE
 SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE
 WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED?
  
 9) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS
 SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438
 MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY
 OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL
 TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT
 ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE
 LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE.
  
 10) COMPLIED. POLLUTION PREVENTION PLAN. 2014 FBC-B
 3307.
  
 11) PROVISO: DEFERRED SUBMITTAL . 2014 FBC-B 3306.9
 ADJACENT TO EXCAVATIONS. STRUCTURAL NOTES S1.01.
  
 11A) PROVISO: DEFERRED SUBMITTAL. STRUCTURAL NOTES
 S1.01 AND SOILS REPORT BY LANGAN ENGINEERING SOILS
 REPORT MAY 21/ 2015. 2014 FBC-B 3307.1 PROTECTION
 REQUIRED. ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL
 BE PROTECTED FROM DAMAGE DURING CONSTRUCTION AND
 DEMOLITION WORK. PROTECTION SHALL BE PROVIDED FOR
 FOOTINGS, FOUNDATIONS, PARTY WALLS, CHIMNEYS, SKYLIGHTS
 AND ROOFS. WITH THE EXCAVATION AND AUGER CAST PILE HOW
 WILL THE BUILDING TO THE SOUTH BE PROTECTED FROM
 SETTLEMENT?
  
 11B) COMPLIED. NOTED ON PLAN. 2014 FBC-B 3307.1 THE
 PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL
 PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING
 BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE
 MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE
 PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT
 LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE
 OF THE EXCAVATION.
  
 12) COMPLIED. NOTED ON PLAN. WHEN EXCAVATING WILL THE
 EXCESS SOILS BE STORED ON SITE? 2014 FBC-B 3304.1.2
 SURCHARGE. NO FILL OR OTHER SURCHARGE LOADS SHALL BE
 PLACED ADJACENT TO ANY BUILDING OR STRUCTURE UNLESS
 SUCH BUILDING OR STRUCTURE IS CAPABLE OF WITHSTANDING
 THE ADDITIONAL LOADS CAUSED BY THE FILL OR SURCHARGE.
 EXISTING FOOTINGS OR FOUNDATIONS WHICH CAN BE AFFECTED
 BY ANY EXCAVATION SHALL BE UNDERPINNED ADEQUATELY OR
 OTHERWISE PROTECTED AGAINST SETTLEMENT AND SHALL BE
 PROTECTED AGAINST LATER MOVEMENT.
  
 13-19) COMPLIED.
  
 20) SHEET A0.01;
 20A)COMPLIED.
  
 20B) SEMI- COMPLIED. THE RESPONSE INDICATED SEE REVISED
 SHEET M0.00 FOR THE BUILDING THERMOS INSULATION FOR
 EXTERIOR WALLS AND FOR THE ROOF. THE MINIMUM FOR THE
 ROOF IS STATED AS A R-19. THE POOL DECK (SHEET A2.10)
 NOR THE INTERSTITIAL SPACE (SHEET A2.09) ABOVE THE
 HIGHEST AIR CONDITIONED FLOOR SHOW INSULATION
 SEPARATING THE NON-CONDITIONED SPACE FROM AIR
 CONDITIONED SPACE. 2014 FBC-ENERGY CODE C402.2.5 FLOORS
 OVER OUTDOOR AIR OR UNCONDITIONED SPACE.
  
  
  
 20C) SEMI ?COMPLIED. THE INTENT OF THIS COMMENT WAS TO
 STATE WHEN LOCATED OUTSIDE OF THE HIGH VELOCITY
 HURRICANE ZONE WE CANNOT ENFORCE THE REQUIREMENTS OF
 THE HIGH VELOCITY HURRICANE ZONE. ONLY BROWARD AND
 MIAMI-DADE COUNTY ARE UNDER THE HIGH VELOCITY HURRICANE
 ZONE.
 THE CITY OF WEST PALM BEACH ACCEPTS BOTH PRODUCT
 APPROVALS FROM THE STATE OF FLORIDA APPROVAL SYSTEM AND
 THE MIAMI-DADE NOAS.
  
  
 1ST ROUND OF COMMENTS. UNDER THE HEADING BUILDING
 MATERIALS THE STATEMENT STATES ALL APPROVALS FOR
 WINDOWS AND DOORS ARE REQUIRED TO BE APPROVED BY
 MIAMI/DADE COUNTY REQUIREMENTS FOR HIGH VELOCITY
 HURRICANE ZONE REQUIREMENTS. PLEASE NOTE ONLY BROWARD
 AND MIAMI-DADE COUNTY ARE UNDER THE HIGH VELOCITY
 HURRICANE ZONE. SEE DEFINITIONS UNDER 202.
 HIGH-VELOCITY HURRICANE ZONE. THIS ZONE CONSISTS OF
 BROWARD AND DADE COUNTIES.
  
 20D) BUILDING PROVISO: PRODUCT APPROVALS LISTED BELOW
 CAN BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER
 THE DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND
 DESIGN CRITERIA IS REVIEWED AND APPROVED THEN THE
 SUBMITTALS CAN BE SUBMITTED AFTER PERMIT ISSUANCE.
 107.3.4.2 DEFERRED SUBMITTALS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS, MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE AND EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G PRE-ENGINEERED A/C STANDS
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 20E) BUILDING PROVISO, DEFERRED SUBMITTALS PRODUCT
 APPROVALS & SHOP DRAWINGS.
 IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 20F) 2ND REQUEST. ROOFING: FOR ALL ROOFING PRODUCTS
 PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR
 ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE
 PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS
 ALLOWED FOR ROOF ZONES 2 & 3. IF SO RAS 117
 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT
 OR ENGINEER. PLEASE ALSO PROVIDE A SHOP DRAWING FOR THE
 TAPERED ROOF INSULATION SHOWING COMPLIANCE WITH A
 MINIMUM VALUE OF R-19 ( NOT AN AVERAGED VALUE).
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 21A) 2ND REQUEST. SHEET A1.01.THE REVISED SITE PLAN
 SHOWS 72 PARKING SPACES. SHEET A2.03 THERE IS 26
 SPACES, SHEET A2.04 ANOTHER 26 SPACES AND SHEET A2.05
 22 SPACES OR A TOTAL OF 74 SPACES. PLEASE CORRECT THE
 TOTAL COUNT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
 21B) ON SHEET A2.05 THE PLANS SHOW A TOTAL OF 3
 ACCESSIBLE PARKING SPACES. WITH THE LOCATION OF THE 2
 SPACES LOCATED ON THE EXTERIOR WALL AND THE ENTRY INTO
 THE ELEVATOR LOBBY ONE OF THE ACCESSIBLE PARKING SPACES
 REQUIRES THE OCCUPANT TO HAVE TO TRAVEL BEHIND PARKED
 CARS.
 2014 FBC-ACCESS. CODE 208.3.1. PARKING SPACES COMPLYING
 WITH 502 THAT SERVE A PARTICULAR BUILDING OR FACILITY
 SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM
 PARKING TO AN ENTRANCE COMPLYING WITH 206.4. ALL SPACES
 MUST BE LOCATED ON AN ACCESSIBLE ROUTE THAT IS AT LEAST
 44 INCHES (1118 MM) WIDE AND SO THAT USERS ARE NOT
 COMPELLED TO WALK OR WHEEL BEHIND PARKED VEHICLES
 EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 1ST ROUND OF COMMENTS. SITE PLAN A1.01 INDICATES THERE
 ARE 79 PARKING SPACES WITHIN THE BUILDING. SHEET A1.15
 THE 5TH FLOOR LIFE SAFETY PLAN THE 3RD PARKING LEVEL
 SHOWS A TOTAL OF 4 ACCESSIBLE PARKING SPACES, OF THE 4
 ACCESSIBLE PARKING SPACES, (1) SPACE NEEDS TO COMPLY
 WITH THE VERTICAL ACCESSIBILITY REQUIREMENTS OF ACCESS.
 CODE 502.5 VERTICAL CLEARANCES FROM THE ENTRY OF THE
 1ST FLOOR, VEHICLE ELEVATORS INCOMING AND OUTGOING AND
 THE VEHICLE ROUTE SERVING THEM. SEE ACCESS. CODE 502.5.
 ADVISORY 502.5 VERTICAL CLEARANCE.
 SIGNS PROVIDED AT ENTRANCES TO PARKING FACILITIES
 INFORMING DRIVERS OF CLEARANCES AND THE LOCATION OF VAN
 ACCESSIBLE PARKING SPACES CAN PROVIDE USEFUL CUSTOMER
 ASSISTANCE.
  
 FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED
 THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF
 HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT
 WHERE THE VAN CANNOT BE MANEUVERED.
  
 FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT
 RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE
 WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION.
 ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT
 PROHIBITS A COVERED ENTITY FROM COMPLYING WITH
 REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN
 VIOLATION OF THE ADA.
  
 22) COMPLIED. VAN ACCESSIBILITY. 2014 FBC-ACCESS. 502.6
 IDENTIFICATION.
  
 23A) SHEET A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. THIS COMMENT WILL HOLD TRUE
 FOR ALL FLOORS, WITH THE EXCEPTION OF THE 3 PARKING
 FLOORS. NEITHER OF THESE PLANS HAVE LABELED, IDENTIFIED
 THE DOORS ON THE PLAN TO THE DOOR SCHEDULE FOUND ON
 A8.02. OPENING PROTECTIVES CANNOT BE REVIEWED UNDER
 FBC-B TABLE 716.5. EXAMPLE STAIR # 1 THERE ARE 3 DOORS
 ASSOCIATED WITH THE VERTICAL STAIR ENCLOSURE FOUND ON
 THE 1ST FLOOR.
  
 23B)SEMI- COMPLIED. LIFE SAFETY SHEET A1.THE OCCUPANCY
 LOAD SHOWN FOR THE 2ND FLOOR OF 569. THE CODE ANALYSIS
 INDICATES THERE ARE 2 STAIRS AT 57 INCHES WHICH WILL
 ACCEPT 190 OCCUPANTS NOT 206. THE 3RD STAIR IS LABELED
 AS 52 INCHES WIDE. THE 600 SERIES PLANS FOR STAIRS IT
 APPEARS ALL 3 STAIRS ARE 57 INCHES WIDE. 57/0.3= 190
 OCCUPANTS X 3 STAIRS= 570 OCCUPANTS. AGREED THE STAIRS
 APPEAR TO BE THE LIMITING FACTOR.
 TO USE THE 57/0.2 FACTOR NOT ONLY DOES THE BUILDING
 REQUIRE FIRE SPRINKLERS BUT COMPLIANCE WITH AN
 EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEM.
  
 23C)(1 & 2) COMPLIED.
  
 23D-G) COMPLIED.
  
 24A) COMPLIED.
  
 24B) COMPLIED. SHEET A1.12 LIFE SAFETY 3 STAIRS ARE A
 MINIMUM OF 57 INCHES/ 0.3= 190 OCC. X 3= 570 OCCUPANTS.
  
 24C) COMPLIED. CONFERENCE ROOMS 2 MEANS OF EGRESS.
  
 24D) 2ND REQUEST . SEMI-COMPLIED. SHEET FP2.02 SHOWS
 THE USE OF TYCO WINDOW SPRINKLERS, IT APPEARS THAT (2)
 SPRINKLERS ARE LOCATED ON THE VERTICAL MULLION. PLEASE
 PROVIDE A DETAIL FOR SPRINKLER AND WASHING OF THE
 GLAZING FOR THIS AREA. 404.6 EXCEPTION 1.1.
  
 1ST REVIEW COMMENTS. THERE IS A NOTE FOR S SMOKE
 PARTITION FOR THE 2 STORY ATRIUM USING THE EXCEPTION #1
 REQUIRING BOTH REQUIREMENTS OF 404.6 EXCEPTION 1.1 &
 1.2 BE MET. PLEASE PROVIDE DETAILS FOR THE SPACING OF
 THE FIRE SPRINKLERS AND COMPLIANCE WITH 1.2 1.2. THE
 GLASS WALL SHALL BE INSTALLED IN A GASKETED FRAME IN A
 MANNER THAT THE FRAMING SYSTEM DEFLECTS WITHOUT
 BREAKING (LOADING) THE GLASS BEFORE THE SPRINKLER
 SYSTEM OPERATES.
  
 24E) COMPLIED.
  
 25) SHEET A1.13 THE 3RD FLOOR PARKING & SHEET A2.03,
 THESE SHEETS WILL BE COMMON COMMENTS FOR THE 3RD, 4TH
 AND 5TH FLOORS.
  
 25A)(1) COMPLIED. FBC-B 3007.7.2. THE FIRE SERVICE
 ACCESS ELEVATOR LOBBY . SECTION 3007.7.3.
  
 25A)(2) NEW COMMENT, DESIGN ISSUE, NOT A CODE ISSUE.
 THE ACCESSIBLE PARKING SPACES ARE FOUND ON THE 5TH
 FLOOR PARKING. TO GAIN ACCESS TO ANY OF THE FLOORS A
 WHEELCHAIR BOUND PERSON WILL NEED TO USE THE FIREMEN?S
 ELEVATOR. IF THE BUILDING GOES INTO FIRE ALARM THE
 ACTUATION OF ANY BUILDING FIRE ALARM-INITIATING DEVICE
 SHALL INITIATE PHASE I EMERGENCY RECALL OPERATION ON
 ALL FIRE SERVICE ACCESS ELEVATORS IN ACCORDANCE WITH
 THE REQUIREMENTS IN ASME A17.1/CSA B44. THE OCCUPANT IN
 THE FIREMEN?S LOBBY ELEVATOR WILL BE STRANDED WITHOUT
 ANY MEANS OF COMMUNICATION!!!!
 AS YOU KNOW THE 2014 ACCESSIBILITY CODE SECTION 207.1
 REFERS YOU IN THE 2003 IBC TO SECTION 1007 FOR
 ACCESSIBLE MEANS OF EGRESS. IN SECTION 1007.6 IS THE
 SECTION FOR AREAS OF REFUGE. SECTION 1007.3 EXCEPTION 2
 AREAS OF REFUGE ARE NOT REQUIRED IN BUILDINGS THAT ARE
 EQUIPPED THROUGHOUT IN ACCORDANCE WITH SECTION
 903.3.1.1.
  
 25B-D) COMPLIED.
  
 25E) SEMI-COMPLIED. A6.12 NOW DOES SHOW VERTICAL
 BI-PARTING DOORS. THERE IS NO DOOR IDENTIFICATION TAG
 PROVIDED, NEITHER IS THERE INFORMATION ON THIS DOOR AS
 FAR AS HOURS OF RATING. THIS IS A 5 STORY SHAFT
 REQUIRING 2 HR. RATING OF WALLS AND 90 MINUTE OPENING
 PROTECTIVES, TABLE 716.5 OF THE 2014 FBC-B.
 1ST ROUND OF COMMENTS. THIS COMMENT IS A COMMON FOR THE
 3 PARKING FLOORS AND THE 1ST FLOOR. THE PLANS INDICATE
 TO PROVIDE FALL PROTECTION AT THE ENTRY OF THE
 AUTOMOBILE ELEVATOR. PLEASE PROVIDE COMPLIANCE WITH
 2014 FBC-B 1013.2 GUARDS SHALL BE LOCATED ALONG
 OPEN-SIDED, EQUIPMENT PLATFORMS, STAIRS, RAMPS AND
 LANDINGS THAT ARE LOCATED MORE THAN 30 INCHES (762 MM)
 MEASURED VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY
 POINT WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE
 EDGE OF THE OPEN SIDE. GUARDS SHALL BE ADEQUATE IN
 STRENGTH AND ATTACHMENT IN ACCORDANCE WITH SECTION
 1607.8.
  
 25F) COMPLIED. 1607.8.3 VEHICLE BARRIERS.
  
 25G)SEMI-COMPLIED. DEPENDING ON THE NEW LOCATION OF
 COMMENT (21D). SHEET A2.05 LIFE SAFETY PLAN INDICATES 2
 ACCESSIBLE PARKING STALLS WITH COLUMNS IN THE ACCESS
 AISLE. PLEASE PROVIDE THE CLEAR WIDTH FROM THE COLUMN
 TO THE ACCESSIBLE PARKING STALL. FBC-ACCESSIBILITY CODE
 502.3.1 WIDTH. ACCESS AISLES SERVING CAR AND VAN
 PARKING SPACES SHALL BE 60 INCHES (1525 MM) WIDE
 MINIMUM.
  
 26) SHEET A1.16 6TH FLOOR LIFE SAFETY PLAN & A7.05 &
 A7.06 ENLARGED FLOOR PLAN 6TH FLOOR.
  
 26A-E) COMPLIED
  
 26F) BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR
 TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26G) BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR
 TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26H) WE NEED A LETTER ADDRESSED TO THE BUILDING
 OFFICIAL ROBERT BROWN FOR REVIEW AND APPROVAL BY ROBERT
 BROWN UNDER THE 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION. MR.
 BROWN HAS ALREADY REVIEWED THIS CONCEPT, BUT WILL NEED
 THE LETTER TO BE SUBMITTED REQUESTING THE ALTERNATE
 DESIGN IN MEETING THE CODE REQUIREMENT.
  
 ** COMMON COMMENT FOR ALL FLOORS (7-12) WHERE THE
 ALLOWABLE COMMON PATH OF TRAVEL IS EXCEEDED. EXAMPLE:
 ROOMS 718 & 719 FROM THE MOST REMOTE POINT IN THE SUITE
 TO THE NEAREST VERTICAL EXIT IS OVER THE ALLOWABLE 75
 FT. TO ACHIEVE THE ALLOWABLE 75 FT. A RATED WALL IS
 INSTALLED IN THE EXIT ACCESS CORRIDOR, ON THE DOOR
 SCHEDULE THIS DOOR IS NOT FIRE RATED. PLEASE PROVIDE A
 CODE SECTION WHERE THIS IS ALLOWED TO BE CONSIDERED
 CODE COMPLIANT. 2014 FBC-B TABLE 1014.3. DEFINITION:
 COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT
 ACCESS WHICH THE OCCUPANTS ARE REQUIRED TO TRAVERSE
 BEFORE TWO SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL
 TO TWO EXITS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON
 PATHS OF TRAVEL. COMMON PATHS OF EGRESS TRAVEL SHALL BE
 INCLUDED WITHIN THE PERMITTED TRAVEL DISTANCE.
  
 27) WE NEED A LETTER ADDRESSED TO THE BUILDING OFFICIAL
 ROBERT BROWN FOR REVIEW AND APPROVAL BY ROBERT BROWN
 UNDER THE 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION SECTION 104.11 ALTERNATE MATERIALS,
 DESIGN AND METHODS OF CONSTRUCTION. MR. BROWN HAS
 ALREADY REVIEWED THIS CONCEPT, BUT WILL NEED THE LETTER
 TO BE SUBMITTED REQUESTING THE ALTERNATE DESIGN IN
 MEETING THE CODE REQUIREMENT.
  
 MR. BROWN HAS LOOKED AT THE ADDITIONAL COST INVOLVED IN
 THE 2 HR. RATING OF THE WHOLE CORRIDOR AND 1 1/2 HOUR
 RATING OF ALL DOORS WITHIN THE CORRIDOR.
  
 MR. BROWNS SUGGESTION IS TO CREATE A 2 HOUR VESTIBULE
 IN FRONT OF STAIRWELL NUMBER ONE. LEAVE THE 1 ? HOUR
 DOOR FOR THE STAIRWELL AND EXTEND THE 2 HOUR FIRE
 RATING TO JUST WEST OF THE ROOMS 715 & 722, A PAIR OF
 DOORS, SWING THE DOORS IN THE EGRESS TRAVEL AND HAVE
 THE DOORS ON HOLD OPENS. TO THE WEST OF THE STAIRWELL 1
 DOOR OPENING HAVE A SECOND PAIR OF DOORS ON HOLD OPENS
 IN LINE WITH UNITS 713 & 714, ON THE OPPOSITE WALL IT
 APPEARS A FIRE EXTINGUISHER CABINET WOULD HAVE TO BE
 RELOCATED. THIS DESIGN WOULD HOLD TRUE FOR THE FLOORS
 7-12. FLOOR 6 WE MEET THE TRAVEL DISTANCE SINCE THE
 STAIRWELL # 1 WAS EXTENDED WITH THE 2ND REQUIRED DOOR
 OPENING.
  
 SHEET A1.18 & A7.09 & A7.10. THE 8TH, 10TH & 12TH
 FLOORS. THIS COMMENT FOR THE ROOMS 818,819,1018,
 1019,1218 & 1219 ALL EXCEED THE ALLOWABLE 75 FT.
 ALLOWABLE COMMON PATH OF TRAVEL OF 75 FT. 2014 FBC-B
 TABLE 1014.3
  
 28) COMPLIED.
  
 29) SHEET A2.09 & A7.41 13TH FLOOR ROOFTOP GARDEN:
 29A-D) COMPLIED.
  
 29E) 2ND REQUEST. THE INTERIOR LOBBY/ DINING AREA SHOWS
 36 INDOOR SEATS AT TABLES NOT 26. 36X0.05= 1.8 OR (2)
 SEATS, COMPLIED.
 THE AREA OF NON-COMPLIANCE IS THE OUTDOOR LOUNGE AREA
 SHOWS TABLES AND 20 CHAIRS REQUIRING AT LEAST (1)
 ACCESSIBLE SEAT. 20X0.05= 1
 1ST ROUND OF COMMENTS. THE AREAS ROOF LOUNGE AND LOBBY,
 1313 & 1314 MAY NEED TO COMPLY WITH ACCESS. CODE 902.3
 IF THERE ARE TABLES PRESENT. THIS PLAN DOES NOT SHOW A
 SEATING ARRANGEMENT IN THE ROOF LOUNGE 1314.
  
 29F) 2ND REQUEST. STAIRWELL # 1 SHOWS A ROOF TOP HATCH
 FOR ACCESS TO THE UPPER ROOF WITH MECHANICAL EQUIPMENT
 ON THE ROOF TOP. PLEASE PROVIDE THE CLEAR OPENING FOR
 THE ROOF TOP ROOF HATCH AND COMPLIANCE WITH 2014 FBC-B
 SECTION 1009.16.1 EXCEPTION. IN BUILDINGS WITHOUT AN
 OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE PERMITTED TO
 BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE
 FEET IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET .
  
 1ST ROUND COMMENTS. STAIRWELL # 1 SHOWS A LADDER TO
 GAIN ACCESS TO THE ROOF TOP EQUIPMENT. 2014 FBC-B
 SECTION 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND
 RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH
 THE REQUIREMENTS OF SECTION 716. OPENINGS IN INTERIOR
 EXIT STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED
 EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY
 FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED
 SPACES AND FOR EGRESS FROM THE ENCLOSURE.
  
 30) POOL AND JACUZZI ARE NOT PART OF THIS PERMIT, WILL
 REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES.
  
 31) BUILDING PROVISO. FENCING AND GATES AROUND THE POOL
 WILL REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED
 FEES.
  
 32) COMPLIED.
  
 33-34) COMPLIED.
  
 35) BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02
 & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE
 REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 36) SHEET A4.01 SHOWS A NORTH ELEVATION WITH A NOTE FOR
 CONCRETE CANOPY WITH WOOD COMPOSITE UNDERNEATH FINISH.
 THE STRUCTURAL SHEET S5.21 DETAIL PROVIDES STRUCTURAL
 DETAILS AS TO THE THICKNESS OF THIS CANOPY, AND THE
 PLACEMENT OF REINFORCEMENT. THERE ARE 2 AREAS OF
 CONCERN:
  
 36A) 2ND REQUEST. SHEET A4.01 THERE IS A NOTE
 INDICATING THE MATERIAL ON THE UNDERSIDE OF THE CANOPY
 IS A CLADDING PANEL COMPOSITE. PLEASE PROVIDE THE
 LITERATURE ON THIS PRODUCT, IF THE PRODUCT DOES NOT
 MEET THE DEFINITION OF COMPOSITE THEN CHANGE THE
 TERMINOLOGY, BUT PRODUCT INFORMATION IS STILL GOING TO
 BE REQUIRED. PLEASE PROVIDE THE PRODUCT APPROVAL
 MIAMI-DADE NOA 15-0211.05 FOR REVIEW FOR WIND PRESSURES
 AS WELL AS FOR FLAME SPREAD AND SMOKE DEVELOPMENT.
 1ST ROUND OF COMMENTS. THE NOTE FOUND ON A4.01
 INDICATES THE UNDERNEATH SIDE OF THE CANOPY IS TO BE
 FINISHED WITH A WOOD COMPOSITE MATERIAL. WE FIND THIS
 SAME NOTE AT AROUND THE 155 FT. & 173.5 FT. ELEVATION.
 PLEASE PROVIDE PRODUCT LITERATURE ON THIS PRODUCT TO
 SEE HOW THIS MATERIAL WAS TESTED, TO WHAT STANDARD?
 DOES IT MEET THE DEFINITION OF A COMPOSITE MATERIAL.
  
 DEFINITION OF COMPOSITE MATERIAL: 703.5.2 COMPOSITE
 MATERIALS. MATERIALS HAVING A STRUCTURAL BASE OF
 NONCOMBUSTIBLE MATERIAL AS DETERMINED IN ACCORDANCE
 WITH SECTION 703.5.1 WITH A SURFACING NOT MORE THAN
 0.125 INCH (3.18 MM) THICK THAT HAS A FLAME SPREAD
 INDEX NOT GREATER THAN 50 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84 OR UL 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 2014 FBC-B 1406.2.1 TYPE I, II, III AND IV
 CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS,
 COMPLYING WITH THE FOLLOWING LIMITATIONS:
 1. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL NOT EXCEED
 10 PERCENT OF AN EXTERIOR WALL SURFACE AREA WHERE THE
 FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) OR LESS.
 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED
 TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
 3. COMBUSTIBLE EXTERIOR WALL COVERINGS CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION
 2303.2 FOR EXTERIOR INSTALLATION SHALL NOT BE LIMITED
 IN WALL SURFACE AREA WHERE THE FIRE SEPARATION DISTANCE
 IS 5 FEET (1524 MM) OR LESS AND SHALL BE PERMITTED UP
 TO 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE PLANE
 REGARDLESS OF THE FIRE SEPARATION DISTANCE.
 4. WOOD VENEERS SHALL COMPLY WITH SECTION 1405.5.
 1406.2.1.1.2 FIRE SEPARATION GREATER THAN 5 FEET. FOR
 FIRE SEPARATION DISTANCES GREATER THAN 5 FEET (1524
 MM), ANY EXTERIOR WALL COVERING SHALL BE PERMITTED THAT
 HAS BEEN EXPOSED TO A REDUCED LEVEL OF INCIDENT RADIANT
 HEAT FLUX IN ACCORDANCE WITH THE NFPA 268 TEST METHOD
 WITHOUT EXHIBITING SUSTAINED FLAMING. THE MINIMUM FIRE
 SEPARATION DISTANCE REQUIRED FOR THE EXTERIOR WALL
 COVERING SHALL BE DETERMINED FROM TABLE 1406.2.1.1.2
 BASED ON THE MAXIMUM TOLERABLE LEVEL OF INCIDENT
 RADIANT HEAT FLUX THAT DOES NOT CAUSE SUSTAINED FLAMING
 OF THE EXTERIOR WALL COVERING.
  
 36B) 2ND REQUEST. THE RESPONSE INDICATES A NEW SHEET
 A5.15 EYEBROW DETAILS 1-6 ALL SHOW THE RESYSTA CP 140
 COMPOSITE CLADDING PANEL AND ATTACHMENT OF THE PANELS
 PER THE NOA, BUT NO INFORMATION IS PROVIDED AS TO THE
 MECHANICAL ATTACHMENT OF THE 1 X 3 TO THE CONCRETE
 EYEBROW.
 1ST ROUND OF COMMENTS. THE WOOD COMPOSITE MATERIAL,
 PLEASE PROVIDE HOW THIS MATERIAL WILL BE ATTACHED TO
 THE SUB-STRUCTURE, ADHERED, PINNED? 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 36C) PROVISO: POLYMER MODIFIED CEMENT WATER PROOFING TO
 THE TOP OF THE CONCRETE EYEBROW. SUBMIT PRODUCT
 APPROVAL. TO BE REVIEWED BY THE DESIGNER OF RECORD
 BEFORE BEING SUBMITTED TO THE BUILDING DEPARTMENT.
  
 37) BUILDING PROVISO/ DEFERRED SUBMITTAL. SHEET A4.01
 THE NORTH WALL ELEVATION ON THE GARAGE LEVELS 3-5 THE
 PLANS SHOW PERFORATED ALUMINUM PANEL SYSTEM. PLEASE
 PROVIDE PRODUCT LITERATURE, AND ENGINEERING ANALYSIS OF
 THE SYSTEM, WITH THE WIND DESIGN CRITERIA AND ANCHORING
 SYSTEMS REVIEWED BY THE ENGINEER OF RECORD. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW. 2014 FBC-B 1503.1 ROOF DECKS SHALL
 BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE
 BUILDING OR STRUCTURE IN ACCORDANCE WITH THE PROVISIONS
 OF THIS CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND
 INSTALLED IN ACCORDANCE WITH THIS CODE AND THE APPROVED
 MANUFACTURERS INSTRUCTIONS SUCH THAT THE ROOF COVERING
 SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE.
  
  
 38A) COMPLIED. FIRE COMMAND CENTER LAYOUT. FBC-B
 911.1.4.
  
 38B) SEMI-COMPLIED) 911.1.5 REQUIRED FEATURES.
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES:
  
 1.-5) SHEET E4.02
 6. 2ND REQUEST, SEMI-COMPLIED. PLEASE REVIEW THE
 MECHANICAL PLANS REVIEW COMMENT # 3, 2ND REVIEW.
 THE FIREFIGHTERS CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
  
 7-12). SHEET E4.02.
  
 13) BUILDING PROVISO/ DEFERRED SUBMITTALS. (13.1-13.7)
 AN APPROVED BUILDING INFORMATION CARD THAT CONTAINS,
 BUT IS NOT LIMITED TO, THE FOLLOWING INFORMATION:
  
 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES:
 PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE
 BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY
 CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT
 TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING
 POPULATION (I.E., DAY, NIGHT, WEEKEND);
  
 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT
 INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS
 (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND
 THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER,
 EMAIL ADDRESS;
  
 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES:
 THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS,
 COLUMNS, AND ROOF ASSEMBLY);
  
 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF
 EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION
 AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR
 DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT
 STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT
 STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF
 ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF
 ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR
 NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION
 OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY,
 LOCATION OF FREIGHT ELEVATOR BANKS;
  
 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT
 INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF
 BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF
 ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR,
 LOCATION OF NATURAL GAS SERVICE;
  
 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES:
 LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM,
 LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS
 PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF
 DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G.,
 DRY, WET, PRE-ACTION, ETC.); AND
  
 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES:
 LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS
 MATERIAL.
  
 14. WORK TABLE.
  
 15. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
  
 16. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
  
 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
  
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED.
  
 39) COMPLIED. 2014 FBC-B 403.5.3 STAIRWAY DOOR
 OPERATION.
  
 40) SEMI ?COMPLIED. PLEASE REVIEW THE MECHANICAL PLANS
 REVIEW COMMENT # 3, 2ND REVIEW. 2014 FBC-B 403.4.7
 SMOKE REMOVAL./ 909.4 ANALYSIS. A RATIONAL ANALYSIS
 SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE
 EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS
 SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE
 UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION
 DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6.
  
 41) COMPLIED. FBC-B 403.5.5 LUMINOUS EGRESS PATH
 MARKINGS..
  
 42) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 43) COMPLIED, THANK YOU. FOR THE RESUBMISSION OF PLANS,
 PLEASE BREAK THE PLAN SETS DOWN TO SMALLER MANAGEABLE
 ROLLS. BUILDING AND ID DRAWINGS TOGETHER, STRUCTURAL BY
 ITSELF AND MEP TOGETHER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By jwitmer Date 2016-07-18 Time 06:28 Rev Time  
Received By jwitmer Date 2016-07-14 Time 06:00 Sent To  
Notes
2016-07-18 06:27:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061443
 ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-718-5987 / MARGARET LEON
 E-MAIL: MLEONDADLP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JULY 14/2016 - MON. JULY 18/2016
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS AND THE PERMIT APPLICATION. THE
 AMOUNT OF STORIES IN THIS PROJECT? THE PERMIT
 APPLICATION INDICATES THIS IS A 17 STORY HOTEL . SEE
 SHEET A0.01. INDICATES UNDER THE BUILDING DESCRIPTION
 THIS A 6 STORY MID-RISE. WHEN YOU REVIEW THE SHEET
 INDEX, THERE ARE 13 STORIES INCLUDING THE HABITABLE
 POOL, POOL DECK AND A2 DELI/ RESTAURANT AREAS.
  
 2) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/2014,
 AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO
 OR GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER
 ART IN PUBLIC PLACES COORDINATOR
 TEL: 822-1515
 E-MAIL: [email protected]
 WEBSITE: WPB.ORG/AIPP/
  
  
 3) THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR
 THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE ,
 IRRIGATION, TEST PILE, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR
 VALUE FROM THE OVERALL BUILDING VALUE OF
 $33,000,000.00. THE REMAINING BALANCE WILL BE
 AFFECTIVELY THE VALUE OF THE BUILDING YOU WILL BE
 PAYING FOR THIS PERMIT. THE BUILDING DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 108.3 BUILDING PERMIT VALUATION.
  
 4) PLEASE SHOW ENERGY CODE COMPLIANCE, MISSING
 DOCUMENTATION. SHOW COMPLIANCE BY THE 2014 FBC-ENERGY
 CODE C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 SHEET S1.02 IS LABELED STRUCTURAL INSPECTION PLAN THIS
 SHEET MAY NEED TO BE RENAMED TO THRESHOLD INSPECTION
 PLAN TO MEET THE COMMENT 3A.
  
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 5C) COMPLIED FOUND ON ARCHITECTURAL AND STRUCTURAL
 SHEETS. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 5D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED.
  
 5E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THRESHOLD
 INSPECTION FORMS , GUIDELINES AND POLICIES FOR PROJECTS
 WERE E-MAILED TO:
 [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME
 BACK UNDELIVERABLE. 07/14/2016 11:35 AM.
 [email protected]
  
 5F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 5G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 5H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 5I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 6) SHEET C-01 INDICATES THE PROPOSED SITE IS MADE UP OF
 4 LOTS. UNDER THE 2014 FBC-B TABLE 602, BUILDINGS
 CANNOT BE BUILT OVER PROPERTY LINES. EITHER A REPLAT OF
 THE 4 LOTS WILL NEED TO OCCUR OR A UNITY OF TITLE.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT
 FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE. SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 7) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE
 PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 8) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE
 PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY
 CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE
 GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE
 FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH
 TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE
 SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE
 WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED?
  
 9) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS
 SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438
 MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY
 OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL
 TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT
 ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE
 LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE.
  
 10) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION
 PREVENTION PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED.
 ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL BE
 PROTECTED FROM DAMAGE DURING CONSTRUCTION, REMODELING
 AND DEMOLITION WORK. PROVISIONS SHALL BE MADE TO
 CONTROL WATER RUNOFF AND EROSION DURING CONSTRUCTION OR
 DEMOLITION ACTIVITIES. THE PERSON MAKING OR CAUSING AN
 EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO
 THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT
 THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 11) PLEASE PROVIDE DETAILS SHOWING HOW COMPLIANCE WITH
 2014 FBC-B 3306.9 ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) IN HEIGHT. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHERE REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
  
 11A) PLEASE PROVIDE DETAILS SHOWING COMPLIANCE WITH
 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC
 AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE
 DURING CONSTRUCTION AND DEMOLITION WORK. PROTECTION
 SHALL BE PROVIDED FOR FOOTINGS, FOUNDATIONS, PARTY
 WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. WITH THE
 EXCAVATION AND AUGER CAST PILE HOW WILL THE BUILDING TO
 THE SOUTH BE PROTECTED FROM SETTLEMENT?
  
 11B) 2014 FBC-B 3307.1 THE PERSON MAKING OR CAUSING AN
 EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO
 THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT
 THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
  
 12) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON
 SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER
 SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 13) PLEASE DOCUMENT COMPLIANCE WITH: 2014 FBC-B 3313.1
 WHERE REQUIRED. AN APPROVED WATER SUPPLY FOR FIRE
 PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE
 MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES
 ON THE SITE. PLEASE PROVIDE WHERE THIS CONNECTION WILL
 BE MADE.
  
 14) NOTICE: 2014 FBC-B [F] 3311.1 WHERE REQUIRED. IN
 BUILDINGS REQUIRED TO HAVE STANDPIPES BY SECTION
 905.3.1, NOT LESS THAN ONE STANDPIPE SHALL BE PROVIDED
 FOR USE DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE
 INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE
 THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST
 LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE
 SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS
 AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
 15A) 2014 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 15B) 2014 FBC-B 3309.2 FIRE HAZARDS. THE PROVISIONS OF
 THIS CODE AND THE FLORIDA FIRE PREVENTION CODE SHALL BE
 STRICTLY OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS
 ATTENDANT UPON CONSTRUCTION OPERATIONS.
  
 16) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
 17) STRUCTURAL SHEET S1.01 UNDER THE HEADING OF AUGER
 CAST PILE INDICATES THERE WAS A GEOTECHNICAL STUDY
 COMPLETED BY LANGAN ENGINEERING & ENVIRONMENTAL
 SERVICES MAY 21/ 2015 REPORT # 300176801. PLEASE
 PROVIDE 3 SIGNED AND SEALED ORIGINAL REPORTS. 2014
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 18) SUBMIT PLANS FOR TEST PILE UNDER A SEPARATE PERMIT.
 COMPLIANCE WITH 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 SECTION 117 TESTS. THE BUILDING OFFICIAL MAY REQUIRE
 TESTS OR TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED
 TESTS ARE TO BE MADE AT THE EXPENSE OF THE OWNER, OR
 AGENT, BY AN APPROVED TESTING LABORATORY OR OTHER
 APPROVED AGENCY, PLEASE PROVIDE WHAT AGENCY WILL BE
 MONITORING OF THE TEST AND PRODUCTION PILE?
 19) WITH NO SOILS REPORT SUBMITTED PLEASE PROVIDE
 COMPLIANCE WITH 2014 FBC-B 1803.5.4 GROUND-WATER TABLE.
 A SUBSURFACE SOIL INVESTIGATION SHALL BE PERFORMED TO
 DETERMINE WHETHER THE EXISTING GROUND-WATER TABLE IS
 ABOVE OR WITHIN 5 FEET (1524 MM) BELOW THE ELEVATION OF
 THE LOWEST FLOOR LEVEL WHERE SUCH FLOOR IS LOCATED
 BELOW THE FINISHED GROUND LEVEL ADJACENT TO THE
 FOUNDATION. WILL A DEWATERING PLAN BE NECESSARY FOR
 THIS LOCATION?
 20) SHEET A0.01;
 20A) FIRE RESISTANCE RATINGS PER TABLE 601, THE
 DESIGNER OF RECORD DECIARES A REDUCTION IN HOUR RATING
 OF FIRE RATING PER FBC-B 403.2.1.1 FOR EXTERIOR BEARING
 WALLS, INTERIOR BEARING WALLS & THE PRIMARY STRUCTURAL
 FRAME. THE MATRIX DOES NOT SHOW A SEPARATE LINE ITEM
 FOR COLUMNS, UNDER SECTION
 B-403.2.1.1 THE EXCEPTION DOES NOT ALLOW THE REDUCTION
 OF COLUMNS SUPPORTING FLOORS. THE ONLY REDUCTION THAT
 CAN BE TAKEN WOULD BE UNDER FOOTNOTE ?A?.
  
 20B) THE BUILDING INSULATION VALUES MAY VERY FROM WHAT
 IS LISTED SINCE THE ENERGY CALCULATIONS WERE NOT
 PROVIDED NOR THE METHOD OF COMPLIANCE UNDER THE ENERGY
 CODE IS A UNKNOWN. 2014 FBC-ENERGY CODE C401.2
 APPLICATION.
  
 20C) UNDER THE HEADING BUILDING MATERIALS THE STATEMENT
 STATES ALL APPROVALS FOR WINDOWS AND DOORS ARE REQUIRED
 TO BE APPROVED BY MIAMI/DADE COUNTY REQUIREMENTS FOR
 HIGH VELOCITY HURRICANE ZONE REQUIREMENTS. PLEASE NOTE
 ONLY BROWARD AND MIAMI-DADE COUNTY ARE UNDER THE HIGH
 VELOCITY HURRICANE ZONE. SEE DEFINITIONS UNDER 202.
 HIGH-VELOCITY HURRICANE ZONE. THIS ZONE CONSISTS OF
 BROWARD AND DADE COUNTIES.
  
 20D) HEADING SUBMITTALS. PRODUCT APPROVALS LISTED BELOW
 CAN BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER
 THE DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND
 DESIGN CRITERIA IS REVIEWED AND APPROVED THEN THE
 SUBMITTALS CAN BE SUBMITTED AFTER PERMIT ISSUANCE.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS, MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE AND EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G PRE-ENGINEERED A/C STANDS
  
 20E) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 20F) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY
 EITHER A FLORIDA ARCHITECT OR ENGINEER.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 21) SITE PLAN A1.01 INDICATES THERE ARE 79 PARKING
 SPACES WITHIN THE BUILDING. SHEET A1.15 THE 5TH FLOOR
 LIFE SAFETY PLAN THE 3RD PARKING LEVEL SHOWS A TOTAL OF
 4 ACCESSIBLE PARKING SPACES, OF THE 4 ACCESSIBLE
 PARKING SPACES, (1) SPACE NEEDS TO COMPLY WITH THE
 VERTICAL ACCESSIBILITY REQUIREMENTS OF ACCESS. CODE
 502.5 VERTICAL CLEARANCES FROM THE ENTRY OF THE 1ST
 FLOOR, VEHICLE ELEVATORS INCOMING AND OUTGOING AND THE
 VEHICLE ROUTE SERVING THEM. SEE ACCESS. CODE 502.5.
 ADVISORY 502.5 VERTICAL CLEARANCE.
 SIGNS PROVIDED AT ENTRANCES TO PARKING FACILITIES
 INFORMING DRIVERS OF CLEARANCES AND THE LOCATION OF VAN
 ACCESSIBLE PARKING SPACES CAN PROVIDE USEFUL CUSTOMER
 ASSISTANCE.
  
 FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED
 THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF
 HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT
 WHERE THE VAN CANNOT BE MANEUVERED.
  
 FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT
 RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE
 WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION.
 ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT
 PROHIBITS A COVERED ENTITY FROM COMPLYING WITH
 REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN
 VIOLATION OF THE ADA.
  
 22) 2014 FBC-ACCESS. CODE ADVISORY 502.6
 IDENTIFICATION. THE REQUIRED ?VAN ACCESSIBLE?
 DESIGNATION IS INTENDED TO BE INFORMATIVE, NOT
 RESTRICTIVE, IN IDENTIFYING THOSE SPACES THAT ARE
 BETTER SUITED FOR VAN USE. ENFORCEMENT OF MOTOR VEHICLE
 LAWS, INCLUDING PARKING PRIVILEGES, IS A LOCAL MATTER.
 PARKING SPACE AND ACCESS AISLE CONFIGURATIONS REQUIRED
 FOR ALL ACCESSIBLE PARKING BY FLORIDA LAW, S.553.5041,
 F.S., MEET THE VAN ACCESSIBLE SPACE REQUIREMENTS OF THE
 ADA STANDARDS FOR ACCESSIBLE DESIGN. THEREFORE, NO
 ACCESSIBLE SPACE IS MORE SUITABLE THAN ANY OTHER
 ACCESSIBLE SPACE FOR ?VAN ACCESSIBLE? PARKING. FLORIDA
 LAW ONLY REQUIRES ?VAN ACCESSIBLE? PARKING SIGNS IN
 PARKING STRUCTURES WHERE VAN PARKING MAY BE LIMITED TO
 THE FIRST LEVEL ACCESSIBLE SPACES. FLORIDA ACCESSIBLE
 PARKING SIGNS MUST INCLUDE INDICATION OF THE PENALTY
 FOR ILLEGAL PARKING IN ADDITION TO THE ACCESSIBLE
 PARKING SYMBOL REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN.
 23A) SHEET A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. THIS COMMENT WILL HOLD TRUE
 FOR ALL FLOORS, WITH THE EXCEPTION OF THE 3 PARKING
 FLOORS. NEITHER OF THESE PLANS HAVE LABELED, IDENTIFIED
 THE DOORS ON THE PLAN TO THE DOOR SCHEDULE FOUND ON
 A8.02. OPENING PROTECTIVES CANNOT BE REVIEWED UNDER
 FBC-B TABLE 716.5. EXAMPLE STAIR # 1 THERE ARE 3 DOORS
 ASSOCIATED WITH THE VERTICAL STAIR ENCLOSURE FOUND ON
 THE 1ST FLOOR.
 23B) PLEASE NOTE THE LIFE SAFETY SHEET A1.12 & A2.02
 THE OCCUPANT LOAD GIVEN FOR THIS FLOOR IS 581/ 3 EXIT
 STAIRWELLS IS 194 OCCUPANTS THROUGH THE 3 VERTICAL EXIT
 DOORWAYS. PLEASE NOTE THE LIFE SAFETY PLAN INDICATES
 CLEAR WIDTH FOR ALL 3 DOORS IS 34 INCHES WHICH CAN ONLY
 TAKE 170 OCCUPANTS AT EACH DOORWAY. THE TYPICAL EGRESS
 CAPACITY LEGEND FOUND ON THE SAME PAGE USES THE MEANS
 OF EGRESS CAPACITY FACTOR OF 0.2 INCHES PER OCCUPANT
 OVER THE ALLOWABLE 170 OCCUPANTS THROUGH A CLEAR
 OPENING OF 34 INCHES FOR ALL EGRESS DOORS ON THE 2
 AFFECTED FLOORS 1ST AND 2ND FLOOR.
 PLEASE ALSO REVIEW THE EXCEPTION TO FBC-B 1005.3.2 THAT
 REDUCES THE MEANS OF EGRESS LOAD FACTOR FOR DOORS TO
 0.15 INCH (3.8 MM) PER OCCUPANT IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED
 IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 AND
 AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN
 ACCORDANCE WITH SECTION 907.5.2.2.
 23C) ON THE 1ST FLOOR THE WORST CASE SCENARIO OF 194
 OCCUPANTS IS NOT FOUND AS THE OCCUPANT LOAD FOR THE
 WORST CASE SCENARIO EXITS THE BUILDING. FBC-B 1005.3.2.
 23B) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. A2.01
 GROUND FLOOR PLAN. COMMON COMMENT FOR ALL FLOORS.
 NEITHER OF THESE SHEETS SHOW WALL IDENTIFICATION TAGS
 THAT CORRELATE TO THE WALL RATING FOUND ON SHEET A9.01,
 EXCEPTION THE 3 PARKING FLOORS. 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. WALL
 RATINGS. EXTERIOR WALLS SECTION 705, FIRE BARRIERS 707,
 FIRE PARTITIONS 708, SMOKE BARRIERS, SHAFTS 713.
 23C)(1) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. PLEASE NOTE THE VERTICAL EXIT
 DOES NOT END AT THE EXTERIOR OF THE BUILDING. THE PLANS
 SHOW A CONTINUATION OF THIS EXIT LABELED CORRIDOR # 109
 WITH A 3 HOUR FIRE RATED WALL ON ONE SIDE AND A 2 HOUR
 FIRE RATED WALL ON THE OTHER. PLEASE NOTE THIS
 EXTENSION OF THE VERTICAL EXIT NEEDS TO BE DEFINED AND
 BUILT AS A 2 HOUR EXIT PASSAGE WAY. 1022.10.1
 TERMINATION AND EXTENSION. A SMOKEPROOF ENCLOSURE OR
 PRESSURIZED STAIRWAY SHALL TERMINATE AT AN EXIT
 DISCHARGE OR A PUBLIC WAY.
 23C)(2) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. THE EXTERIOR DOOR TO CORRIDOR
 # 120 LIST THE CLEAR OPENING AS 68 INCHES AND THE
 MAXIMUM OCCUPANCY THROUGH THIS DOOR AT 340 OCCUPANTS.
 THE DOOR APPEARS TO BE A 3 FOOT WIDE DOOR. SEE FBC-B
 1005.3.2.
 23D) THERE IS A DINING ELEMENT TO THE 1ST FLOOR PLEASE
 PROVIDE WHERE COMPLIANCE WITH 2014 FBC-ACCESS. CODE :
 902.1. DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3.
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
 902.3 HEIGHT. THE TOPS OF DINING SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE
 LINES SHALL COMPLY WITH 904.5.
 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL COMPLY WITH 308.
 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 23E) ACCESS. CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
 23F) ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
 23G) SHEET THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. ON THE SOUTH PROPERTY LINE
 WALL THERE ARE PORTIONS OF THE WALL THAT ARE 1 HOUR
 FIRE RATED AND SOME PORTIONS RATED FOR 2 HOURS. FBC-B
 TABLE 601 LIST A 2 HOUR FIRE RATING FOR EXTERIOR FIRE
 BEARING WALLS. ADDITIONAL INFORMATION REQUIRED. IF
 THESE WALLS ARE GOING TO BE IN FILE NONBEARING WALLS
 HOW WILL THE WALL RATING BE MAINTAINED AT THE JOINT
 LINE TOP COURSE OF BLOCK WHERE THE BEAM WOULD ALREADY
 BE IN PLACE?
 24) SHEET A1.12 LIFE SAFETY 2ND FLOOR VS. A2.02 2ND
 FLOOR PLAN:
 24A) EXITS STAIRS 1,2 &3 ALL INDICATE THEY ARE 57
 INCHES WIDE. THE PROPOSED OCCUPANT LOAD FOR THE ENTIRE
 FLOOR IS 581 OCCUPANTS. 581 OCCUPANTS DIVIDE BY 3= 194
 OCCUPANTS PER STAIR. WHEN YOU DIVIDE THE 57 INCHES OF
 STAIR WIDTH BY THE 0.3 = 190 OCCUPANTS. THE PLANS ARE
 DEFICIENT BY 4 OCCUPANTS PER STAIRWELL. SEE FBC-B
 1005.3.1. THE CAPACITY, IN INCHES (MM), OF MEANS OF
 EGRESS STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE
 OCCUPANT LOAD SERVED BY SUCH STAIRWAY BY A MEANS OF
 EGRESS CAPACITY FACTOR OF 0.3 INCH (7.6 MM) PER
 OCCUPANT.
 24B) SHEET A1.12 LIFE SAFETY 2ND FLOOR VS. A2.02 2ND
 FLOOR PLAN SHOWS AN OCCUPANT LOAD OF 581 OCCUPANTS AND
 TABLE 1021.1 REQUIRES 3 EXITS THERE IS AN ISSUE WITH
 FBC-B SECTION 1028.2 FOR THE 2ND FLOOR PLEASE DEFINE
 THE MAIN EXIT. 1028.2 ASSEMBLY MAIN EXIT. IN A
 BUILDING, ROOM OR SPACE USED FOR ASSEMBLY PURPOSES THAT
 HAS AN OCCUPANT LOAD OF GREATER THAN 300 AND IS
 PROVIDED WITH A MAIN EXIT, THE MAIN EXIT SHALL BE OF
 SUFFICIENT WIDTH TO ACCOMMODATE NOT LESS THAN ONE-HALF
 OF THE OCCUPANT LOAD, BUT SUCH WIDTH SHALL NOT BE LESS
 THAN THE TOTAL REQUIRED WIDTH OF ALL MEANS OF EGRESS
 LEADING TO THE EXIT. WHERE THE BUILDING IS CLASSIFIED
 AS A GROUP A OCCUPANCY, THE MAIN EXIT SHALL FRONT ON AT
 LEAST ONE STREET OR AN UNOCCUPIED SPACE OF NOT LESS
 THAN 10 FEET (3048 MM) IN WIDTH THAT ADJOINS A STREET
 OR PUBLIC WAY. IN A BUILDING, ROOM OR SPACE USED FOR
 ASSEMBLY PURPOSES WHERE THERE IS NO WELL-DEFINED MAIN
 EXIT OR WHERE MULTIPLE MAIN EXITS ARE PROVIDED, EXITS
 SHALL BE PERMITTED TO BE DISTRIBUTED AROUND THE
 PERIMETER OF THE BUILDING PROVIDED THAT THE TOTAL WIDTH
 OF EGRESS IS NOT LESS THAN 100 PERCENT OF THE REQUIRED
 WIDTH.
 THE ISSUE WITH THE 2 EXITS GROUPED ON THE WEST SIDE OF
 THE BUILDING IF A FIRE BLOCKS THE 2 WEST EXITS 50% OF
 THE OCCUPANT LOAD IS STILL SUPPOSED TO EXIT OUT OF THE
 REMAINING EXITS.
 1028.3 ASSEMBLY OTHER EXITS. IN ADDITION TO HAVING
 ACCESS TO A MAIN EXIT, EACH LEVEL IN A BUILDING USED
 FOR ASSEMBLY PURPOSES HAVING AN OCCUPANT LOAD GREATER
 THAN 300 AND PROVIDED WITH A MAIN EXIT, SHALL BE
 PROVIDED WITH ADDITIONAL MEANS OF EGRESS THAT SHALL
 PROVIDE AN EGRESS CAPACITY FOR AT LEAST ONE HALF OF THE
 TOTAL OCCUPANT LOAD SERVED BY THAT LEVEL AND SHALL
 COMPLY WITH SECTION 1015.2. IN A BUILDING USED FOR
 ASSEMBLY PURPOSES WHERE THERE IS NO WELL-DEFINED MAIN
 EXIT OR WHERE MULTIPLE MAIN EXITS ARE PROVIDED, EXITS
 FOR EACH LEVEL SHALL BE PERMITTED TO BE DISTRIBUTED
 AROUND THE PERIMETER OF THE BUILDING, PROVIDED THAT THE
 TOTAL WIDTH OF EGRESS IS NOT LESS THAN 100 PERCENT OF
 THE REQUIRED WIDTH.
 24C) PLEASE REVIEW THE MEETING ROOM # 3 THE ROOM HAS AN
 OCCUPANT LOAD OF 107 OCCUPANTS THE PLEASE SEE SIDE WALL
 BETWEEN ROOMS 220 & 221. THIS SECTION OF WALL HAS 2
 DOORS SWINGING IN OPPOSITE DIRECTIONS. THE REMAINDER OF
 THE MEETING ROOMS (217, 218 & 219) ALSO HAVE AN
 OCCUPANT LOAD GREATER THAN 50 REQUIRING A SECOND MEANS
 OF EGRESS WITH THE DOOR SWINGING IN THE DIRECTION OF
 TRAVEL. FBC-B 1008.1.2.
 24D) THERE IS A NOTE FOR S SMOKE PARTITION FOR THE 2
 STORY ATRIUM USING THE EXCEPTION #1 REQUIRING BOTH
 REQUIREMENTS OF 404.6 EXCEPTION 1.1 & 1.2 BE MET.
 PLEASE PROVIDE DETAILS FOR THE SPACING OF THE FIRE
 SPRINKLERS AND COMPLIANCE WITH 1.2 1.2. THE GLASS WALL
 SHALL BE INSTALLED IN A GASKETED FRAME IN A MANNER THAT
 THE FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING)
 THE GLASS BEFORE THE SPRINKLER SYSTEM OPERATES.
 24E) THE DOOR SCHEDULE ON SHEET A8.02 INDICATES IN
 STAIRWELL 3 AN ACCESS HATCH IDENTIFIED AS S3, NOT
 IDENTIFIED ON THE FLOOR PLAN. FBC-B 1022.4. OPENINGS IN
 INTERIOR EXIT STAIRWAYS OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES
 AND FOR EGRESS FROM THE ENCLOSURE.
 25) SHEET A1.13 THE 3RD FLOOR PARKING & SHEET A2.03,
 THESE SHEETS WILL BE COMMON COMMENTS FOR THE 3RD,
 4TH AND 5TH FLOORS.
  
 25A) THIS WILL BE A COMMON COMMENT FOR ALL FLOORS. NONE
 OF THE FLOORS SHOW THE FIRE SERVICE ACCESS ELEVATOR
 LOBBY TO BE ENCLOSED BY A SMOKE BARRIER HAVING A FIRE
 RESISTANCE RATING OF NOT LESS THAN 1 HOUR. SEE FBC-B
 3007.7.2. THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL
 BE ENCLOSED WITH A SMOKE BARRIER HAVING A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR, EXCEPT
 THAT LOBBY DOORWAYS SHALL COMPLY WITH SECTION 3007.7.3.
 25B) COMMENT COMMON TO ALL FLOORS. THE FIRE SERVICE
 ACCESS ELEVATOR LOBBY ENTRY DOORS IN THE DOOR
 SCHEDULEA8.02 ARE NOT FIRE RATED. 3007.7.3 LOBBY
 DOORWAYS. OTHER THAN THE DOOR TO THE HOIST WAY, EACH
 DOORWAY TO A FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL
 BE PROVIDED WITH A 3/4-HOUR FIRE DOOR ASSEMBLY
 COMPLYING WITH SECTION 716.5. THE FIRE DOOR ASSEMBLY
 SHALL ALSO COMPLY WITH THE SMOKE AND DRAFT CONTROL DOOR
 ASSEMBLY REQUIREMENTS OF SECTION 716.5.3.1 WITH THE UL
 1784 TEST CONDUCTED WITHOUT THE ARTIFICIAL BOTTOM SEAL.
 25C) COMMENT COMMON TO THE 3 PARKING GARAGE FLOORS.
 DOOR 303A DOES NOT HAVE 18 INCHES FOR MANEUVERING
 CLEARANCES ON THE LATCH SIDE OF THE DOOR. SEE
 FBC-ACCESS. CODE 404.2.4.
 25D) NEITHER THE GENERATOR ROOM NOR THE DOOR TO THE
 GENERATOR ROOM SHOW A FIRE RATING. 2014 FBC-B 403.4.8.1
 REQUIRES 2 HOUR FIRE RATED WALLS WITH 1 ? HOUR OPENING
 PROTECTIVES. TABLE 716.5.
 25E) THIS COMMENT IS A COMMON FOR THE 3 PARKING FLOORS
 AND THE 1ST FLOOR. THE PLANS INDICATE TO PROVIDE FALL
 PROTECTION AT THE ENTRY OF THE AUTOMOBILE ELEVATOR.
 PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1013.2 GUARDS
 SHALL BE LOCATED ALONG OPEN-SIDED, EQUIPMENT PLATFORMS,
 STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN
 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR
 GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914 MM)
 HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. GUARDS SHALL
 BE ADEQUATE IN STRENGTH AND ATTACHMENT IN ACCORDANCE
 WITH SECTION 1607.8.
  
 25F) THIS IS A COMMON COMMENT FOR THE 3 GARAGE PARKING
 FLOORS ALL EXTERIOR WALLS WHERE A VEHICLE COULD RUN
 INTO THE WALL AND THE COMMON WALL BETWEEN THE PARKING
 GARAGE AND ATRIUM WILL NEED TO SHOW COMPLIANCE WITH
 1607.8.3 VEHICLE BARRIERS. VEHICLE BARRIERS FOR
 PASSENGER VEHICLES SHALL BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 6,000 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.3 OF ASCE 7. ASCE 7-10 SECTION 4.5.3 FOR
 DESIGN OF THE SYSTEM, THE LOADS SHALL BE ASSUME TO ACT
 BETWEEN 1FT. 6 INCHES AND 2 FT. 3 INCHES ABOVE THE
 FINISH FLOOR SURFACE, LOCATED TO PRODUCE A MAXIMUM LOAD
 EFFECTS. THE LOAD SHALL BE APPLIED ON AN AREA NOT TO
 EXCEED 12 IN. BY 12 IN.
  
 25G) SHEET A2.05 LIFE SAFETY PLAN INDICATES 2
 ACCESSIBLE PARKING STALLS WITH COLUMNS IN THE ACCESS
 AISLE. PLEASE PROVIDE THE CLEAR WIDTH FROM THE COLUMN
 TO THE ACCESSIBLE PARKING STALL. FBC-ACCESSIBILITY CODE
 502.3.1 WIDTH. ACCESS AISLES SERVING CAR AND VAN
 PARKING SPACES SHALL BE 60 INCHES (1525 MM) WIDE
 MINIMUM.
 26) SHEET A1.16 6TH FLOOR LIFE SAFETY PLAN & A7.05 &
 A7.06 ENLARGED FLOOR PLAN 6TH FLOOR.
 26A) COMMON COMMENT ALL FLOORS. THERE IS A UNKNOWN WALL
 TYPE NO SHOWN ON EITHER PLANS WITHIN THE LINEN SHOOT
 ENCLOSURE, THE WALL IN COMMON WITH THE HOUSE KEEPING
 ROOM IS NOT IDENTIFIED. THIS WALL SHOULD BE A 2 HOUR
 FIRE RATED WALL, IT IS PART OF THE SHAFT ENCLOSURE.
 FBC-B 713.4 FIRE-RESISTANCE RARING.
  
 26B) COMMON COMMENT ALL FLOORS. THE DOOR TO GAIN ENTRY
 INTO THE HOUSE KEEPING ROOM IS LABELED X23.
 SHEET A8.02 THE DOOR SCHEDULE INDICATES UNDER NOTE 22
 THIS DOOR IS A ?DUTCH DOOR? THIS DOOR PROVIDE 2 LEAVES,
 ONE ABOVE THE OTHER. PLEASE PROVIDE THE TESTED ASSEMBLY
 FOR THIS TYPE OF CONFIGURATION, WHERE IS THE BREAK IN
 THE DOOR TO OCCUR, WHERE WILL THE LOCK SET BE LOCATED,
 WHAT ASSEMBLY IS TO HOLD THE DOOR TOGETHER, WILL THE
 TOP AND BOTTOM PORTIONS OF THE DOOR BE ON SPRING TYPE
 HINGES, WILL BOTH HALVES OF THE DOOR BE ON HOLD OPEN
 DEVISES THAT WILL ACTIVATE UPON FIRE AND OR SMOKE
 ALARM? NOTE 19 INDICATES A VIEW PANEL, HOW LARGE OF A
 VIEW PANEL. MISSING INFORMATION 107.2.1.3. TABLE 716.5/
 716.5.8 GLAZING MATERIAL. FIRE-PROTECTION-RATED GLAZING
 CONFORMING TO THE OPENING PROTECTION REQUIREMENTS IN
 SECTION 716.5 SHALL BE PERMITTED IN FIRE DOOR
 ASSEMBLIES.
 716.5.8.1 SIZE LIMITATIONS. FIRE-PROTECTION-RATED
 GLAZING SHALL COMPLY WITH THE SIZE LIMITATIONS OF NFPA
 80, AND AS PROVIDED IN SECTIONS 716.5.8.1.1 AND
 716.5.8.1.2.
  
 26C) SHEET A6.13 LINEN CHUTE DETAIL SHEET. PLEASE NOTE
 SECTION DETAILS OF THE LINEN CHUTE ARE MISSING 2
 DETAILS;
 26C)(1) THE DETAIL DOES NOT INCLUDE THE HOUSING OR NOTE
 FOR THE REQUIREMENT OF FBC-B 903.2.11.2 RUBBISH AND
 LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES SHALL HAVE ADDITIONAL SPRINKLER HEADS
 INSTALLED AT ALTERNATE FLOORS AND AT THE LOWEST INTAKE.
 WHERE A RUBBISH CHUTE EXTENDS THROUGH A BUILDING MORE
 THAN ONE FLOOR BELOW THE LOWEST INTAKE, THE EXTENSION
 SHALL HAVE SPRINKLERS INSTALLED THAT ARE RECESSED FROM
 THE DROP AREA OF THE CHUTE AND PROTECTED FROM FREEZING
 IN ACCORDANCE WITH SECTION 903.3.1.1. SUCH SPRINKLERS
 SHALL BE INSTALLED AT ALTERNATE FLOORS, BEGINNING WITH
 THE SECOND LEVEL BELOW THE LAST INTAKE AND ENDING WITH
 THE FLOOR ABOVE THE DISCHARGE. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING. ACCESS DOOR REQUIRED.
  
 26C)(2) MISSING DETAIL FOR THE ACCESS DOOR INTO THE
 CHUTE ITSELF AND NOTE FOR THE FIRE RATING OF THE
 ASSEMBLY. FBC-B 713.13.1 REFUSE, RECYCLING AND LAUNDRY
 CHUTE ENCLOSURES. OPENINGS INTO THE SHAFT, INCLUDING
 THOSE FROM ACCESS ROOMS AND TERMINATION ROOMS, SHALL BE
 PROTECTED IN ACCORDANCE WITH THIS SECTION AND SECTION
 716. OPENINGS INTO CHUTES SHALL NOT BE LOCATED IN
 CORRIDORS. DOORS SHALL BE SELF- OR AUTOMATIC-CLOSING
 UPON THE ACTUATION OF A SMOKE DETECTOR IN ACCORDANCE
 WITH SECTION 716.5.9.3.
  
 26D) COMMON COMMENT FOR 6-12 FLOORS THE 2 HOUR FIRE
 RATED SHAFT BEHIND THE SERVICE ELEVATOR AND P1 ELEVATOR
 DO NOT HAVE THE WALL IDENTIFICATION TAGS. 107.2.1.3.
 ADDITIONAL INFORMATION REQUIRED.
  
 26E) PLEASE PROVIDE IF THERE ARE ANY DWELLING UNITS
 WITHIN THE FLOORS 6-12? DEFINITION:
 DWELLING UNIT. A SINGLE UNIT PROVIDING COMPLETE,
 INDEPENDENT LIVING FACILITIES FOR ONE OR MORE PERSONS,
 INCLUDING PERMANENT PROVISIONS FOR LIVING, SLEEPING,
 EATING, COOKING AND SANITATION.
  
 SLEEPING UNIT. A ROOM OR SPACE IN WHICH PEOPLE SLEEP,
 WHICH CAN ALSO INCLUDE PERMANENT PROVISIONS FOR LIVING,
 EATING, AND EITHER SANITATION OR KITCHEN FACILITIES BUT
 NOT BOTH. SUCH ROOMS AND SPACES THAT ARE ALSO PART OF A
 DWELLING UNIT ARE NOT SLEEPING UNITS.
  
 IF THERE ARE DWELLING UNITS THEN CODE REQUIREMENTS FOR
 :
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. FLOOR
 INSULATION. INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 26F) BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR
 TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26G) BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR
 TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26H) ** COMMON COMMENT FOR ALL FLOORS (6-12) WHERE THE
 ALLOWABLE COMMON PATH OF TRAVEL IS EXCEEDED. EXAMPLE:
 ROOMS 604 & 605 FROM THE MOST REMOTE POINT IN THE SUITE
 TO THE NEAREST VERTICAL EXIT IS OVER THE ALLOWABLE 75
 FT. TO ACHIEVE THE ALLOWABLE 75 FT. A RATED WALL IS
 INSTALLED IN THE EXIT ACCESS CORRIDOR, ON THE DOOR
 SCHEDULE THIS DOOR IS NOT FIRE RATED. PLEASE PROVIDE A
 CODE SECTION WHERE THIS IS ALLOWED TO BE CONSIDERED
 CODE COMPLIANT. 2014 FBC-B TABLE 1014.3. DEFINITION:
 COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT
 ACCESS WHICH THE OCCUPANTS ARE REQUIRED TO TRAVERSE
 BEFORE TWO SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL
 TO TWO EXITS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON
 PATHS OF TRAVEL. COMMON PATHS OF EGRESS TRAVEL SHALL BE
 INCLUDED WITHIN THE PERMITTED TRAVEL DISTANCE.
  
 27) SHEET A1.18 & A7.09 & A7.10. THE 8TH, 10TH & 12TH
 FLOORS. THIS COMMENT FOR THE ROOMS 818,819,1018,
 1019,1218 & 1219 ALL EXCEED THE ALLOWABLE 75 FT.
 ALLOWABLE COMMON PATH OF TRAVEL OF 75 FT. 2014 FBC-B
 TABLE 1014.3
  
 28) SHEET A2.08A THE INTERSTITIAL SPACE FLOOR PLAN. IN
 BOTH VERTICAL EXIT STAIR TOWERS 1 & 2 THERE IS A NOTE
 OF A DOOR LABELED S3 AND NOTE TO THE SIDE TO PROVIDE A
 3 FT. X 4 FT. ACCESS HATCH. THIS DOOR/ ACCESS HATCH IS
 WITHIN THE VERTICAL EXIT AND LEADS TO THE INTERSTITIAL
 SPACE BETWEEN FLOORS. PLEASE FIND ANOTHER WAY TO ACCESS
 THE INTERSTITIAL SPACE BETWEEN FLOORS. CODE COMPLIANCE
 FOR THE VERTICAL EXIT STAIRS CANNOT BE MET WITH THIS
 OPENING WITHIN THE STAIRS. PLEASE SEE THE 2014 FBC-B
 SECTION 1022.4 OPENINGS.
 INTERIOR EXIT STAIRWAY AND RAMP OPENING PROTECTIVES
 SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 716. OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS
 OTHER THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE
 LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO THE
 ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR EGRESS
 FROM THE ENCLOSURE.
  
 29) SHEET A2.09 & A7.41 13TH FLOOR ROOFTOP GARDEN:
 29A) THIS SHEET INDICATES A SECTION FOR RESTROOM 1321 &
 1322, PAGE A7.41 SECTION 04. PLEASE SEE ON THIS SHEET
 THE DETAIL IS MISSING. 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 29B) DOORS 1322, 1323,1324, 1325 & 1326 ARE MISSING
 FROM THE DOOR SCHEDULE FOUND ON SHEET A8.02, CANNOT BE
 CHECKED FOR SIZE, TYPE NOR FIRE RATING. 2014 FBC-B
 1008.1.1, TABLE 716.5.
  
 29C) DOORS NOT NUMBERS, THE DOOR ALL THE WAY TO THE
 LEFT OF THE PAGE SEPARATING AREAS 1313 & 1314 SWINGS
 AGAINST THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A
 ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE
 PERSONS OR A GROUP H OCCUPANCY. FBC-B 1008.1.2.
 29D) BARS 1311 AND 1312 WILL NEED TO SHOW COMPLIANCE
 WITH; 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 29E) THE AREAS ROOF LOUNGE AND LOBBY, 1313 & 1314 MAY
 NEED TO COMPLY WITH ACCESS. CODE 902.3 IF THERE ARE
 TABLES PRESENT. THIS PLAN DOES NOT SHOW A SEATING
 ARRANGEMENT IN THE ROOF LOUNGE 1314.
  
 29F) STAIRWELL # 1 SHOWS A LADDER TO GAIN ACCESS TO THE
 ROOF TOP EQUIPMENT. PLEASE REVIEW :
 2014 FBC-B SECTION 1022.4 OPENINGS. INTERIOR EXIT
 STAIRWAY AND RAMP OPENING PROTECTIVES SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716.
 OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER
 THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO
 THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE.
 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714.
  
 30) POOL AND JACUZZI ARE NOT PART OF THIS PERMIT, WILL
 REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES.
  
 31) FENCING AND GATES AROUND THE POOL WILL REQUIRE A
 SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES.
  
 32) SHEET A2.10 SHOWS AS HIDDEN LINES VARIOUS ROOF TOP
 EQUIPMENT. SHEET M2.10 SHOWS GENERIC ROOF TOP EQUIPMENT
 TIE DOWNS. DETAILS WILL NEED TO BE SPECIFIC FOR EACH
 TYPE AND SIZE OF ROOF TOP EQUIPMENT. FOR ALL ROOF TOP
 EQUIPMENT, CURBS OR A/C STANDS, DETAILED ATTACHMENT TO
 THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR
 ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 33) SHEET A2.10 PLEASE SHOW COMPLIANCE WITH: FBC-B 2014
 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 34) A.600 SERIES DRAWINGS FOR STAIRWELL 1, 2 & 3.
 PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-ACCESS.
 CODE SECTION 307.4 AND VIEW FIGURE 307.4 FOR VERTICAL
 CLEARANCES.
  
 35) BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02
 & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE
 REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
 36) SHEET A4.01 SHOWS A NORTH ELEVATION WITH A NOTE FOR
 CONCRETE CANOPY WITH WOOD COMPOSITE UNDERNEATH FINISH.
 THE STRUCTURAL SHEET S5.21 DETAIL PROVIDES STRUCTURAL
 DETAILS AS TO THE THICKNESS OF THIS CANOPY, AND THE
 PLACEMENT OF REINFORCEMENT. THERE ARE 2 AREAS OF
 CONCERN:
  
 36A) THE NOTE FOUND ON A4.01 INDICATES THE UNDERNEATH
 SIDE OF THE CANOPY IS TO BE FINISHED WITH A WOOD
 COMPOSITE MATERIAL. WE FIND THIS SAME NOTE AT AROUND
 THE 155 FT. & 173.5 FT. ELEVATION. PLEASE PROVIDE
 PRODUCT LITERATURE ON THIS PRODUCT TO SEE HOW THIS
 MATERIAL WAS TESTED, TO WHAT STANDARD? DOES IT MEET THE
 DEFINITION OF A COMPOSITE MATERIAL.
  
 DEFINITION OF COMPOSITE MATERIAL: 703.5.2 COMPOSITE
 MATERIALS. MATERIALS HAVING A STRUCTURAL BASE OF
 NONCOMBUSTIBLE MATERIAL AS DETERMINED IN ACCORDANCE
 WITH SECTION 703.5.1 WITH A SURFACING NOT MORE THAN
 0.125 INCH (3.18 MM) THICK THAT HAS A FLAME SPREAD
 INDEX NOT GREATER THAN 50 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84 OR UL 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 2014 FBC-B 1406.2.1 TYPE I, II, III AND IV
 CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS,
 COMPLYING WITH THE FOLLOWING LIMITATIONS:
 1. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL NOT EXCEED
 10 PERCENT OF AN EXTERIOR WALL SURFACE AREA WHERE THE
 FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) OR LESS.
 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED
 TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
 3. COMBUSTIBLE EXTERIOR WALL COVERINGS CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION
 2303.2 FOR EXTERIOR INSTALLATION SHALL NOT BE LIMITED
 IN WALL SURFACE AREA WHERE THE FIRE SEPARATION DISTANCE
 IS 5 FEET (1524 MM) OR LESS AND SHALL BE PERMITTED UP
 TO 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE PLANE
 REGARDLESS OF THE FIRE SEPARATION DISTANCE.
 4. WOOD VENEERS SHALL COMPLY WITH SECTION 1405.5.
 1406.2.1.1.2 FIRE SEPARATION GREATER THAN 5 FEET. FOR
 FIRE SEPARATION DISTANCES GREATER THAN 5 FEET (1524
 MM), ANY EXTERIOR WALL COVERING SHALL BE PERMITTED THAT
 HAS BEEN EXPOSED TO A REDUCED LEVEL OF INCIDENT RADIANT
 HEAT FLUX IN ACCORDANCE WITH THE NFPA 268 TEST METHOD
 WITHOUT EXHIBITING SUSTAINED FLAMING. THE MINIMUM FIRE
 SEPARATION DISTANCE REQUIRED FOR THE EXTERIOR WALL
 COVERING SHALL BE DETERMINED FROM TABLE 1406.2.1.1.2
 BASED ON THE MAXIMUM TOLERABLE LEVEL OF INCIDENT
 RADIANT HEAT FLUX THAT DOES NOT CAUSE SUSTAINED FLAMING
 OF THE EXTERIOR WALL COVERING.
  
 36B) THE WOOD COMPOSITE MATERIAL, PLEASE PROVIDE HOW
 THIS MATERIAL WILL BE ATTACHED TO THE SUB-STRUCTURE,
 ADHERED, PINNED? 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 36C) ON THE TOP OF THE 8 FT. CONCRETE CANOPY WHAT
 PRODUCT WILL BE USED TO KEEP MOISTURE FROM SEEPING INTO
 THE CONCRETE SLAB AND REINFORCEMENT?
  
 37) SHEET A4.01 THE NORTH WALL ELEVATION ON THE GARAGE
 LEVELS 3-5 THE PLANS SHOW PERFORATED ALUMINUM PANEL
 SYSTEM. PLEASE PROVIDE PRODUCT LITERATURE, AND
 ENGINEERING ANALYSIS OF THE SYSTEM, WITH THE WIND
 DESIGN CRITERIA AND ANCHORING SYSTEMS REVIEWED BY THE
 ENGINEER OF RECORD. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. 2014
 FBC-B 1503.1 ROOF DECKS SHALL BE COVERED WITH APPROVED
 ROOF COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CHAPTER. ROOF
 COVERINGS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH THIS CODE AND THE APPROVED MANUFACTURER?S
 INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO
 PROTECT THE BUILDING OR STRUCTURE.
 38) SHEET A1.11 AND A2.01 BOTH SHOW THE 1ST FLOOR, BUT
 THERE ARE NO DIMENSIONS FOR SIZING OF THE FIRE COMMAND
 CENTER. THE FIRE COMMAND ROOM IS FOUND ON THIS FLOOR.
 FBC-B403.4.6 FIRE COMMAND. A FIRE COMMAND CENTER
 COMPLYING WITH SECTION 911 SHALL BE PROVIDED IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 38A) PLEASE SHOW COMPLIANCE WITH FBC-B 911.1.4. LAYOUT
 APPROVAL. A LAYOUT OF THE FIRE COMMAND CENTER AND ALL
 FEATURES REQUIRED BY THIS SECTION TO BE CONTAINED
 THEREIN SHALL BE SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION.
 38B) 911.1.5 REQUIRED FEATURES.
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES:
  
 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
  
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
  
 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR.
  
 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL.
  
 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
  
 6. THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
  
 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
  
 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS.
  
 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS.
  
 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM.
  
 11. FIRE PUMP STATUS INDICATORS.
  
 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS.
  
 13. AN APPROVED BUILDING INFORMATION CARD THAT
 CONTAINS, BUT IS NOT LIMITED TO, THE FOLLOWING
 INFORMATION:
  
 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES:
 PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE
 BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY
 CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT
 TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING
 POPULATION (I.E., DAY, NIGHT, WEEKEND);
  
 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT
 INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS
 (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND
 THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER,
 EMAIL ADDRESS;
  
 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES:
 THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS,
 COLUMNS, AND ROOF ASSEMBLY);
  
 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF
 EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION
 AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR
 DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT
 STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT
 STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF
 ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF
 ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR
 NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION
 OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY,
 LOCATION OF FREIGHT ELEVATOR BANKS;
  
 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT
 INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF
 BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF
 ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR,
 LOCATION OF NATURAL GAS SERVICE;
  
 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES:
 LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM,
 LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS
 PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF
 DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G.,
 DRY, WET, PRE-ACTION, ETC.); AND
  
 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES:
 LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS
 MATERIAL.
  
 14. WORK TABLE.
  
 15. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
  
 16. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
  
 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
  
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED.
  
 39) 2014 FBC-B 403.5.3 STAIRWAY DOOR OPERATION.
 STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS
 SHALL BE PERMITTED TO BE LOCKED FROM THE STAIRWAY SIDE.
 STAIRWAY DOORS THAT ARE LOCKED FROM THE STAIRWAY SIDE
 SHALL BE CAPABLE OF BEING UNLOCKED SIMULTANEOUSLY
 WITHOUT UNLATCHING UPON A SIGNAL FROM THE FIRE COMMAND
 CENTER.
  
 40) PLEASE SUBMIT DOCUMENTATION FOR THE FOLLOWING:
 FBC-B 403.4.7 SMOKE REMOVAL./ 909.4 ANALYSIS.
 A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 909.4.1 THROUGH 909.4.6.
  
 41) PLEASE SHOW HOW COMPLIANCE WITH FBC-B 403.5.5
 LUMINOUS EGRESS PATH MARKINGS.
 LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 1024. FBC-B 1024.1 APPROVED
 LUMINOUS EGRESS PATH MARKINGS DELINEATING THE EXIT PATH
 SHALL BE PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B,
 E, I, M, AND R-1 OCCUPANCIES IN ACCORDANCE WITH
 SECTIONS 1024.1 THROUGH 1024.5.
  
 42) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 43) FOR THE RESUBMISSION OF PLANS, PLEASE BREAK THE
 PLAN SETS DOWN TO SMALLER MANAGEABLE ROLLS. BUILDING
 AND ID DRAWINGS TOGETHER, STRUCTURAL BY ITSELF AND MEP
 TOGETHER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2017-10-04 Cont ID  
Sent By jpearson Date 2017-10-04 Time 07:59 Rev Time 0.00
Received By jpearson Date 2017-10-04 Time 07:59 Sent To  
Notes
2017-10-04 07:59:51NO NEW ELECTRICAL PROVIDED, PLANS ALREADY STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2017-07-05 Cont ID  
Sent By jpearson Date 2017-07-05 Time 13:55 Rev Time 0.00
Received By jpearson Date 2017-07-05 Time 13:55 Sent To  
Notes
2017-07-05 13:56:49REVIEWED PER COMMENTS ONLY, JP

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2017-03-20 Cont ID  
Sent By vperez Date 2017-03-20 Time 08:31 Rev Time 0.00
Received By vperez Date 2017-03-16 Time 15:01 Sent To  
Notes
2017-03-20 08:32:553RD ELECTRICAL REVIEW,
  
 PLEASE ADDRESS MECHANICAL COMMENTS RELATED TO
 ELECTRICAL FOR A COMPLETE APPROVAL., (DAMPERS MISSING)
  
 V. PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-12-14 Cont ID  
Sent By vperez Date 2016-12-14 Time 07:47 Rev Time 0.00
Received By vperez Date 2016-12-14 Time 07:47 Sent To  
Notes
2016-12-14 08:32:152NDL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PREVIOUS COMMENTS:
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL
 SUFFICE. (PLEASE PROVIDE ON SHEET E0.00)
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR GENERATOR, FIRE PUMP ALL LOW VOLTAGE SYSTEMS TO
 INCLUDE BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS,
 CCTV, PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR
 CHARGING STATIONS, CO2 FANS, POOL, KITCHEN HOODS, CAR
 LIFTS ETC. A NOTE WILL SUFFICE. (PLEASE PROVIDE ON
 SHEET E0.00)
 3. SHOW AT THE MAIN ELECTRICAL ROOM A NOTE TO REQUIRE
 PANIC HARDWARE AND DOORS TO SWING IN THE DIRECTION OF
 EGRESS. NEC 110.26C2 (REVISED DOOR STILL SHOWN SWINGING
 IN, PLEASE CORRECT SHEET E2.00)
 4. NOTE THAT PER NEC 230.2 THIS PROJECT MEETS THE
 REQUIREMENTS FOR MULTIPLE SERVICES DUE TO CAPACITY
 LIMITS. REGARDLESS, SPECIAL PERMISSION FROM AHJ TO BE
 GRANTED PER DESIGN SHOWN. PROVIDE IN WRITING A REQUEST
 PER CODE SECTION CITED TO AHJ. GENERAL NOTES TO BE
 PLACED FOR FIRST RESPONDER?S SAFETY. FIRE REVIEW MIGHT
 REQUIRE OTHER MEANS TO SHUNT SERVICES. FBC 107.3.5
 (PLEASE LABEL MAINS 1 OF 4, 2 OF 4 ETC. AS ONE SERVICE
 IS PROVIDED FRON VAULT AND 4 MAINS ARE SHOWN)
 5. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL
 AVAILABLE FAULT CURRENT AT THE VAULT TRANSFORMERS. FBC
 107.3.5 (PENDING)
 6. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 (PENDING)
 7. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED. (PROVIDE NOTE ON SHEET E5.01)
 8. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS. (ADDRESSED)
 9. MULTIPLE AREAS NEED TO SHOW GFCI PROTECTED PER NEC
 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI. (PLEASE
 CORRECT SHEET E- 2.02 AND 2.09, MENS RESTROOM TO GFCI
 PROTECTED CIRCUIT L-41 AND EMPLOYEE BREAKROOOM, SEE
 CIRCUITS L-26 AND L-20.
 10. PER FBC EC 405.7- 50% OF ALL RECEPTACLES 125V, 15
 AND 20A MUST BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND
 COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN
 MODULAR PARTITIONS. SHOW COMPLIANCE. ENERGY INPUT DATA
 REPORT NOT PROVIDED (ADDRESSED)
 11. LABEL GFCI ALL RECEPTACLES IN THE MEN?S AND WOMEN?S
 LOCKER ROOMS PER NEC 210.8B7 (ADDRESSED)
 12. LABEL GFCI ALL RECEPTACLES WITHIN 6FT OF SINKS,
 LAUNDRY, KITCHEN AND PREP AREA AND MULTIPLE AREAS NEC
 210.8B5 (ADDRESSED)
 13. SHEET E2.01 AND ABOVE REFLECTS DRINKING FOUNTAINS,
 LABEL ALL RECEPTACLES TO BE GFCI PROTECTED NEC 422.52
 MULTIPLE LOCATIONS- (SEE CIRCUIT RL-14 D/F LABEL GFCI
 PROTECTED)
 14. ADDRESS ALL FIRE REVIEWER COMMENTS RELATED TO
 ELECTRICAL. FBC 107.3.5 (PENDING)
 15. AT ROOFTOP AND EXTERIOR LOCATIONS LABEL MULTIPLE
 RECEPTACLES TO BE WP/GFCI RATED. NEC 406.9B (ADDRESSED)
 16. ALL GUEST UNITS TO BE PROVIDED WITH TAMPER
 RESISTANT RECEPTACLES. PROVIDE A NOTE. NEC 406.13
 (ADDRESSED)
 17. CLARIFY VERIFY ENTIRE RISER DIAGRAM. NOTES DO NOT
 MATCH, SEE ITEM15?? PLEASE ID ELECTRICAL ONE LINE WITH
 SERVICE AND FEEDER CONDUCTOR SIZES, ALL INFO NEEDED ON
 ONE LINE. FBC 107.3.5 (ADDRESSED)
 18. CLARIFY GROUNDING ELECTRODE CONDUCTOR SIZE FOR
 BUILDING STEEL, WATER ETC. NEC 250 (ADDRESSED)
 19. PROVIDE A NOTE FOR FIRE PUMP FEEDER CONDUCTORS TO
 BE 2HR PROTECTED. NEC 695.6A2CD (ADDRESSED)
 20. PANEL SCHEDULE HAS MULTIPLE DISCREPANCIES, SEE
 PANEL H FOR EXAMPLE, SHOWS 125A TRIP BUT TRANSFORMER
 SCHEDULE SHOWS 110A TRIP, WILL NEED TO CORRELATE THIS
 AND MULTIPLE OTHERS. ELEVATOR BREAKER FEEDER CONDUCTOR
 UNDERSIZED BASED ON TRIP RATING 110A. ALUMINUM #4
 SELECTED?? SHUNT TRIP ? REVISIT PANELS ENTIRELY FOR
 COMPLIANCE AND CORRELATION. NEC 240, NEC 310.15B16 FBC
 107.3.5 MINIMUM PLAN REVIEW (ADDRESSED)
 21. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
 NEW COMMENTS DUE TO ENTIRELY REVISED SHEET
  
 1. SHEET E2.00- PROVIDE A NOTE TO MAINTAIN BURIAL
 DEPTHS AND A WARNING RIBBON PER NEC 300.5 FOR ALL
 UNDERGROUND CONDUITS
 2. E-201A- ELEC. ROOM SHOULD NOT BE CONTROLLED
 AUTOMATICALLY BY SENSOR. PROVIDE SWITCH IN ALL ROOMS
 WITH PANELBORDS, MCC SWITHCHBOARDS ETC PER NEC
 110.26(D)
 3. E-2.02- CLARIFY ELEVATOR MACHINE ROOMS RECEPTACLE
 AND LIGHTING BRANCH CIRCUITS. PER NEC 620.23 A SEPERATE
 BRANCH CIRCUIT DEDICATED FOR THIS AREA MUST BE
 PROVIDED. NO OTHER OUTLETS TO BE ON THESE CIRCUITS.
 E/M/R ON SHEET E2.09 HAS SAME SCENARIO. PLEASE CORRECT.
 4. E-5.01- PLEASE PROVIDE THE SELECTIVE COORDINATION
 STUDY, WHICH CAN BE PROVISO,
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-12 Cont ID  
Sent By vperez Date 2016-07-12 Time 14:15 Rev Time 0.00
Received By vperez Date 2016-07-12 Time 14:15 Sent To  
Notes
2016-07-12 14:15:37INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL
 SUFFICE.
 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR GENERATOR, FIRE PUMP ALL LOW VOLTAGE SYSTEMS TO
 INCLUDE BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS,
 CCTV, PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR
 CHARGING STATIONS, CO2 FANS, POOL, KITCHEN HOODS, CAR
 LIFTS ETC. A NOTE WILL SUFFICE.
 3. SHOW AT THE MAIN ELECTRICAL ROOM A NOTE TO REQUIRE
 PANIC HARDWARE AND DOORS TO SWING IN THE DIRECTION OF
 EGRESS. NEC 110.26C2
 4. NOTE THAT PER NEC 230.2 THIS PROJECT MEETS THE
 REQUIREMENTS FOR MULTIPLE SERVICES DUE TO CAPACITY
 LIMITS. REGARDLESS, SPECIAL PERMISSION FROM AHJ TO BE
 GRANTED PER DESIGN SHOWN. PROVIDE IN WRITING A REQUEST
 PER CODE SECTION CITED TO AHJ. GENERAL NOTES TO BE
 PLACED FOR FIRST RESPONDER?S SAFETY. FIRE REVIEW MIGHT
 REQUIRE OTHER MEANS TO SHUNT SERVICES. FBC 107.3.5
 5. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL
 AVAILABLE FAULT CURRENT AT THE VAULT TRANSFORMERS. FBC
 107.3.5
 6. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5
 7. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC
 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE
 DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS
 AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS
 REQUIRED.
 8. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS
 FOR FEEDERS AND BRANCH CIRCUITS.
 9. MULTIPLE AREAS NEED TO SHOW GFCI PROTECTED PER NEC
 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI.
 10. PER FBC EC 405.7- 50% OF ALL RECEPTACLES 125V, 15
 AND 20A MUST BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND
 COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN
 MODULAR PARTITIONS. SHOW COMPLIANCE. ENERGY INPUT DATA
 REPORT NOT PROVIDED
 11. LABEL GFCI ALL RECEPTACLES IN THE MEN?S AND WOMEN?S
 LOCKER ROOMS PER NEC 210.8B7
 12. LABEL GFCI ALL RECEPTACLES WITHIN 6FT OF SINKS,
 LAUNDRY, KITCHEN AND PREP AREA AND MULTIPLE AREAS NEC
 210.8B5
 13. SHEET E2.01 AND ABOVE REFLECTS DRINKING FOUNTAINS,
 LABEL ALL RECEPTACLES TO BE GFCI PROTECTED NEC 422.52
 MULTIPLE LOCATIONS
 14. ADDRESS ALL FIRE REVIEWER COMMENTS RELATED TO
 ELECTRICAL. FBC 107.3.5
 15. AT ROOFTOP AND EXTERIOR LOCATIONS LABEL MULTIPLE
 RECEPTACLES TO BE WP/GFCI RATED. NEC 406.9B
 16. ALL GUEST UNITS TO BE PROVIDED WITH TAMPER
 RESISTANT RECEPTACLES. PROVIDE A NOTE. NEC 406.13
 17. CLARIFY VERIFY ENTIRE RISER DIAGRAM. NOTES DO NOT
 MATCH, SEE ITEM15?? PLEASE ID ELECTRICAL ONE LINE WITH
 SERVICE AND FEEDER CONDUCTOR SIZES, ALL INFO NEEDED ON
 ONE LINE. FBC 107.3.5
 18. CLARIFY GROUNDING ELECTRODE CONDUCTOR SIZE FOR
 BUILDING STEEL, WATER ETC. NEC 250
 19. PROVIDE A NOTE FOR FIRE PUMP FEEDER CONDUCTORS TO
 BE 2HR PROTECTED. NEC 695.6A2CD
 20. PANEL SCHEDULE HAS MULTIPLE DISCREPANCIES, SEE
 PANEL H FOR EXAMPLE, SHOWS 125A TRIP BUT TRANSFORMER
 SCHEDULE SHOWS 110A TRIP, WILL NEED TO CORRELATE THIS
 AND MULTIPLE OTHERS. ELEVATOR BREAKER FEEDER CONDUCTOR
 UNDERSIZED BASED ON TRIP RATING 110A. ALUMINUM #4
 SELECTED?? SHUNT TRIP ? REVISIT PANELS ENTIRELY FOR
 COMPLIANCE AND CORRELATION. NEC 240, NEC 310.15B16 FBC
 107.3.5 MINIMUM PLAN REVIEW
 21. A THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME
 DUE TO MANY INCONSISTENCIES AND DISCREPANCIES. COMMENTS
 MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE TO CONTACT
 ME SHOULD YOU HAVE ANY QUESTIONS REGARDING THIS
 PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2017-10-20 Cont ID  
Sent By squinone Date 2017-10-20 Time   Rev Time 0.00
Received By squinone Date 2017-10-20 Time   Sent To  
Notes
2017-10-20 10:06:41ENGINEERING REVIEW IS BEING DONE UNDER PERMIT
 E16100001.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2017-08-16 Cont ID  
Sent By skennedy Date 2017-08-16 Time 09:18 Rev Time 0.00
Received By skennedy Date 2017-08-16 Time 09:18 Sent To  
Notes
2017-08-16 09:21:26REVIEWS ARE DOCUMENTED UNDER E16100001. NOTE THE
 REQUREMENT TO OBTAIN RIGHT-OF-WAY PERMITS AND ESTABLISH
 AN MOT IN ADDITION TO THE REQUIREMENTS OF E16100001.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-11 Time 09:37 Rev Time 0.00
Received By shill Date 2017-05-11 Time 09:37 Sent To  
Notes
2017-05-11 09:37:37SEE PREVIOUS TWO ENGINEERING REVIEWS
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2016-12-29 Cont ID  
Sent By mgonzale Date 2016-12-29 Time   Rev Time 1.00
Received By mgonzale Date 2016-12-29 Time   Sent To I
Notes
2016-12-29 11:34:41ADDRESS PLANNING'S COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-10-03 Cont ID  
Sent By mgonzal Date 2016-10-03 Time   Rev Time 1.00
Received By mgonzale Date 2016-10-03 Time   Sent To I
Notes
2016-10-03 17:18:59COMMENTS WILL COME THRU ENGINEERING SERVICES.
  
 UNDER REVIEW!

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2017-10-04 Cont ID  
Sent By wjolin Date 2017-10-04 Time 12:32 Rev Time 0.00
Received By wjolin Date 2017-10-04 Time 12:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2017-07-14 Cont ID  
Sent By wjolin Date 2017-07-14 Time 11:07 Rev Time 0.00
Received By wjolin Date 2017-07-14 Time 09:56 Sent To  
Notes
2017-07-14 10:13:02718 SOUTH DIXIE HIGHWAY - 14 STORY HILTON
 PERMIT #16061443
 4TH ROUND REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 ENGINEERING RESPONSE LETTER TO THE FOLLOWING PLAN
 REVIEW COMMENTS CONTINUE TO NOT BE FULLY ADDRESSED:
  
 REPEAT COMMENT (4TH REQUEST) - SHEET C-10: PER NFPA 24
 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE
 MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1) A WALL POST INDICATOR VALVE
 (2) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING
 (3) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (4) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 REPEAT COMMENT (3RD REQUEST) SHEET FP2.05: THE
 SPRINKLERS PROTECTING THE FIRST FLOOR RESTAURANT AREA
 ARE LOCATED 75 FEET ABOVE THE FLOOR BEING PROTECTED.
 THIS ELEVATION DIFFERENCE AND SUSPENDED ARCHITECTURAL
 FEATURES WILL CERTAINLY DELAY SPRINKLER ACTIVATION IF
 ACTIVATION OCCURS AT ALL. HAS SMOKE/HEAT STRATIFICATION
 BEEN EVALUATED FOR THIS TALL CEILING? THIS AREA NEEDS
 AN IN-DEPTH ENGINEERING ANALYSIS. NFPA 13 SECTION
 8.1(3) INDICATES: SPRINKLERS SHALL BE POSITIONED AND
 LOCATED SO AS TO PROVIDE SATISFACTORY PERFORMANCE WITH
 RESPECT TO ACTIVATION TIME AND DISTRIBUTION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2017-03-14 Time   Rev Time 0.00
Received By wjolin Date 2017-03-14 Time 15:56 Sent To  
Notes
2017-03-14 16:00:22718 SOUTH DIXIE HIGHWAY - 14 STORY HILTON
 PERMIT #16061443
 3RD ROUND REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 REPEAT COMMENT (3RD REQUEST) - SHEET C-10: PER NFPA 24
 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE
 MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1) A WALL POST INDICATOR VALVE
 (2) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING
 (3) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (4) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET A203, A204, A203A AND A204A APPEAR IN THE DRAWING
 SET TWICE WITH DIFFERING FLOOR PLANS. ALSO NEWLY ADDED
 SHEETS A203A AND A204A SHOW THE EMERGENCY GENERATOR ON
 DIFFERING FLOORS. CHECK ALL MEPF SHEETS; SEVERAL
 DUPLICATE SHEETS (PARTICULARLY ELECTRICAL) WITH OLD
 FLOOR PLANS ARE IN THE REVISED SET OF DRAWINGS.
  
 SHEET E4.02: PER FFPC SECTION11.9 (NFPA 1) THE
 FOLLOWING CONTROLS/INDICATORS COULD NOT BE LOCATED IN
 THE EMERGENCY COMMAND CENTER:
  
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 REPEAT COMMENT (2ND REQUEST) SHEET FP2.05: THE
 SPRINKLERS PROTECTING THE FIRST FLOOR RESTAURANT AREA
 ARE LOCATED 75 FEET ABOVE THE FLOOR BEING PROTECTED.
 THIS ELEVATION DIFFERENCE AND SUSPENDED ARCHITECTURAL
 FEATURES WILL CERTAINLY DELAY SPRINKLER ACTIVATION IF
 ACTIVATION OCCURS AT ALL. HAS SMOKE/HEAT STRATIFICATION
 BEEN EVALUATED FOR THIS TALL CEILING? WILL THE WATER
 DROPLETS FROM STANDARD SPRAY SPRINKLERS BE ABLE TO
 REACH THE SEAT OF THE FIRE OR WILL EVAPORATION BE A
 FACTOR ALLOWING A FIRE IN THIS AREA GROW TO A SIZE THAT
 CANNOT BE CONTROLLED BY THE CEILING SPRINKLERS? THIS
 AREA NEEDS AN IN-DEPTH ENGINEERING ANALYSIS.
  
 SHEET K1EP: PROVIDE UL LISTING (OR EQUAL), APPLIANCE
 SPECIFICATIONS AND INSTALLATION DATA FOR THE SOLID FUEL
 COOKING EQUIPMENT. DATA SHALL INDICATE IF A SUPPRESSION
 SYSTEM IS REQUIRED FOR THIS APPLIANCE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-12-08 Cont ID  
Sent By wjolin Date 2016-12-08 Time 17:07 Rev Time 0.00
Received By wjolin Date 2016-11-17 Time 14:20 Sent To  
Notes
2016-12-08 11:16:43718 SOUTH DIXIE HIGHWAY - 14 STORY HILTON
 PERMIT #16061443
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 REPEAT COMMENT - SHEET C-10: THE FIRE LINE BACKFLOW
 PREVENTERS CAN BE USED TO CONTROL THE WATER SUPPLY. THE
 ADDITIONAL PIVS SHOULD BE ELIMINATED. ALSO PER NFPA 24
 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE
 MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1) A WALL POST INDICATOR VALVE
 (2) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING
 (3) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (4) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET A1.14: PLANS INDICATE A COMMON PATH OF TRAVEL
 DISTANCE OF 115 FEET FROM STORAGE #405. THE FIRE CODE
 LIMITS THE COMMON PATH OF TRAVEL TO 100 FEET IN STORAGE
 OCCUPANCIES.
  
 REPEAT COMMENT: NO 3 FOOT HIGH PONY WALL PROVIDED. THE
 DETAILS ON THE ARCHITECTURAL AND FIRE PROTECTION
 DRAWINGS ARE INSUFFICIENT TO ENSURE GLAZING DESIGN,
 MULLION DEPTHS AND SPRINKLER COVERAGE IS CORRECT.
 ORIGINAL COMMENT - SHEET A1.12 & A8.05: PLANS INDICATE
 THE USE OF TYCO WINDOW SPRINKLERS (WINDOW TYPES UU, WW
 & YY) IN LIEU OF FIRE RATED GLAZING. PROVIDE A
 SPRINKLER INSTALLATION WINDOW DETAIL ACCORDING TO THE
 MANUFACTURER'S LISTING CRITERIA. THE SPRINKLER LISTING
 DETAILS ARE VERY PARTICULAR AND REQUIRE SPRINKLERS ON
 BOTH SIDES OF THE GLAZING. THE MAXIMUM GLAZING HEIGHT
 IS LIMITED TO 13 FEET. THE GLASS CURTAIN WALL NEEDS TO
 BE ATTACHED TO A THREE FOOT HIGH PONY WALL TO KEEP
 COMBUSTIBLE MATERIALS AT LEAST TWO-INCHES AWAY FROM THE
 GLAZING. VERTICAL MULLIONS SHALL BE OF A DEPTH THAT
 PREVENTS COLD SOLDERING OF ADJACENT SPRINKLERS. THE
 SPRINKLER DESIGN SHOULD INDICATE WHICH WINDOW SPRINKLER
 MODEL WILL BE USED (HORIZONTAL SIDEWALL OR PENDENT
 VERTICAL SIDEWALL) AS THIS WILL AFFECT HOW DEEP THE
 VERTICAL MULLIONS NEED TO BE. A MULLION WILL ACT AS A
 BAFFLE WHEN THE MULLION EXTENDS TO THE BACK OF
 SPRINKLER DEFLECTOR (PENDENT VERTICAL SIDEWALL) OR WHEN
 THE MULLION EXTENDS TO THE SPRINKLER WRENCH FLAT
 (HORIZONTAL SIDEWALL).
  
 SHEET P2.04: PIPE SHALL NOT BE ROUTED THROUGH THE FIRE
 RATED EXIT STAIR ENCLOSURE OF STAIR #3. THIS IS
 PROHIBITED BY NFPA 101.
  
 REPEAT COMMENT: THE GREASE DUCT DISCHARGE IS NOT PER
 NFPA 96 SECTION 7.8.3. THE GENERATOR AIR INTAKE IS
 DIRECTLY ABOVE THE GREASE DUCT EXHAUST. PER NFPA 96 THE
 CLOSEST POINT OF ANY AIR INTAKE OR OPERABLE DOOR OR
 WINDOW ABOVE THE PLANE OF THE EXHAUST TERMINATION SHALL
 BE A MINIMUM OF 10 FEET IN DISTANCE, PLUS 3-INCHES FOR
 EACH 1 DEGREE FROM HORIZONTAL, THE ANGLE OF DEGREE
 BEING MEASURED FROM THE CENTER OF THE EXHAUST
 TERMINATION TO THE CENTER OF THE AIR INTAKE OR OPERABLE
 DOOR OR WINDOW, AS INDICATED IN FIGURE 7.8.3.
 ORIGINAL COMMENT - SHEET M2.01: THE THREE KITCHEN
 EXHAUST FANS INDICATE SIDEWALL DISCHARGE; HOWEVER, THE
 AIR LOUVERS FOR THE GARAGE APPEAR TO BE LOCATED WITHIN
 32 FEET OF THE GREASE DUCT DISCHARGE PER NFPA 96
 SECTION 7.8.3.
  
 SHEET FP2.02: PROVIDE STANDPIPE AND HOSE VALVES IN NEW
 STAIR #3.
  
  
 SHEET FP2.02: HOW WILL THE TYCO WINDOW SPRINKLERS ON
 THE WEST SIDE OF THE GLAZING BE ATTACHED TO THE
 STRUCTURE? TWO SPRINKLERS ARE LOCATED ON THE VERTICAL
 MULLION. WHAT IS THE DEPTH OF THE MULLION AND HOW WILL
 BE ENSURED THAT THE ENTIRE SURFACE OF THE GLAZING IS
 WETTED? WHAT WINDOW SPRINKLER MODEL IS BEING USED
 (PENDENT VERTICAL SIDEWALL OR HORIZONTAL SIDEWALL)?
 SPRINKLER SCHEDULE INDICATES THE USE OF A VIKING
 SPRINKLER.
  
 SHEET FP2.05: THE SPRINKLERS PROTECTING THE FIRST FLOOR
 RESTAURANT AREA ARE LOCATED 75 FEET ABOVE THE FLOOR
 BEING PROTECTED. THIS ELEVATION DIFFERENCE AND
 SUSPENDED ARCHITECTURAL FEATURES WILL CERTAINLY DELAY
 SPRINKLER ACTIVATION IF ACTIVATION OCCURS AT ALL. HAS
 SMOKE/HEAT STRATIFICATION BEEN EVALUATED FOR THIS TALL
 CEILING? WILL THE WATER DROPLETS FROM STANDARD SPRAY
 SPRINKLERS BE ABLE TO REACH THE SEAT OF THE FIRE OR
 WILL EVAPORATION BE A FACTOR ALLOWING A FIRE IN THIS
 AREA GROW TO A SIZE THAT CANNOT BE CONTROLLED BY THE
 CEILING SPRINKLERS? THIS AREA NEEDS AN IN-DEPTH
 ENGINEERING ANALYSIS.
  
 RESPONSE COMMENT - NOTE #32 ON SHEET FP0.00 INDICATES
 THE CONTRACTOR IS RESPONSIBLE FOR PRESSURE CONTROL.
 CONCEPTUAL SYSTEM PRESSURE CONTROL WILL NEED TO BE
 SHOWN TO A DETERMINED FLOOR LEVEL AND BE PROVIDED ON
 THE FIRE PROTECTION ENGINEERING DOCUMENTS WHILE ACTUAL
 PRESSURE CONTROL WILL NEED TO BE SHOWN THE SPRINKLER
 SHOP DRAWINGS.
 ORIGINAL COMMENT - SHEET FP4.01: SPRINKLER AND
 STANDPIPE SYSTEM PRESSURES APPEAR TO EXCEED 165PSIG AND
 175PSIG RESPECTIVELY WITH NO MEASURES OF CONTROL.
  
 SHEET K1EP: PLAN INDICATES THE USE OF A WOOD FIRED
 PIZZA OVEN. HOW IS THIS OVEN BEING PROTECTED IN
 ACCORDANCE WITH NFPA 96 FOR SOLID FUEL COOKING
 OPERATIONS CONCERNING VENTING, FIRE SUPPRESSION, SOLID
 FUEL STORAGE, EXHAUST VENT CLEANING/MAINTENANCE,
 FLEXIBLE WATER HOSE, ASH DISPOSAL? SUBMIT PRODUCT AND
 INSTALLATION MANUAL FOR WOOD FIRED PIZZA OVEN.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-07-06 Cont ID  
Sent By wjolin Date 2016-07-06 Time 14:30 Rev Time 0.00
Received By wjolin Date 2016-07-01 Time 09:58 Sent To  
Notes
2016-07-01 10:01:51718 SOUTH DIXIE HIGHWAY - 14 STORY HILTON
 PERMIT #16061443
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION
 TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 PER NFPA 241, NEW FIRE HYDRANTS SHALL BE INSTALLED,
 INSPECTED, TESTED AND APPROVED PRIOR TO THE
 COMMENCEMENT OF VERTICAL CONSTRUCTION.
  
 FIRE SERVICE ELEVATORS: PLANS SHOW ONE FIRE SERVICE
 ELEVATOR; CONFIRM TWO ARE NOT REQUIRED BY THE FBC FOR
 BUILDINGS WITH AN OCCUPIABLE FLOOR ABOVE 120 FEET.
  
 SHEET C-10: THE FIRE LINE BACKFLOW PREVENTERS CAN BE
 USED TO CONTROL THE WATER SUPPLY. THE ADDITIONAL PIVS
 SHOULD BE ELIMINATED. ALSO PER NFPA 24 SECTION 6.2.1,
 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1) A WALL POST INDICATOR VALVE
 (2) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING
 (3) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (4) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET A0.01: PROJECT DATA BUILDING DESCRIPTION
 INDICATES THIS IS A 6-STORY MID-RISE BUILDING IN LIEU
 OF A HIGH-RISE BUILDING.
  
 SHEET A1.12: ONE FIRE OR OTHER EMERGENCY EVENT HAS THE
 ABILITY TO PROHIBIT THE USAGE OF STAIR #2 AND STAIR #3
 SIMULTANEOUSLY. PER SECTION 7.5.1.3.1 WHERE MORE THAN
 ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS REQUIRED
 FROM A BUILDING OR PORTION THEREOF, SUCH EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED
 FROM EACH OTHER AND BE ARRANGED TO MINIMIZE THE
 POSSIBILITY THAT MORE THAN ONE HAS THE POTENTIAL TO BE
 BLOCKED BY ANY ONE FIRE OR OTHER EMERGENCY CONDITION.
  
 SHEET A1.12: STAIR #3 ONLY INDICATES TWO OF THE FOUR
 WALLS HAVE A FIRE RESISTANCE RATING.
  
 SHEET A1.12 & A8.05: PLANS INDICATE THE USE OF TYCO
 WINDOW SPRINKLERS (WINDOW TYPES UU, WW & YY) IN LIEU OF
 FIRE RATED GLAZING. PROVIDE A SPRINKLER INSTALLATION
 WINDOW DETAIL ACCORDING TO THE MANUFACTURER'S LISTING
 CRITERIA. THE SPRINKLER LISTING DETAILS ARE VERY
 PARTICULAR AND REQUIRE SPRINKLERS ON BOTH SIDES OF THE
 GLAZING. THE MAXIMUM GLAZING HEIGHT IS LIMITED TO 13
 FEET. THE GLASS CURTAIN WALL NEEDS TO BE ATTACHED TO A
 THREE FOOT HIGH PONY WALL TO KEEP COMBUSTIBLE MATERIALS
 AT LEAST TWO-INCHES AWAY FROM THE GLAZING. VERTICAL
 MULLIONS SHALL BE OF A DEPTH THAT PREVENTS COLD
 SOLDERING OF ADJACENT SPRINKLERS. THE SPRINKLER DESIGN
 SHOULD INDICATE WHICH WINDOW SPRINKLER MODEL WILL BE
 USED (HORIZONTAL SIDEWALL OR PENDENT VERTICAL SIDEWALL)
 AS THIS WILL AFFECT HOW DEEP THE VERTICAL MULLIONS NEED
 TO BE. A MULLION WILL ACT AS A BAFFLE WHEN THE MULLION
 EXTENDS TO THE BACK OF SPRINKLER DEFLECTOR (PENDENT
 VERTICAL SIDEWALL) OR WHEN THE MULLION EXTENDS TO THE
 SPRINKLER WRENCH FLAT (HORIZONTAL SIDEWALL).
  
 SHEET A1.16: CORRIDOR DOORS USED TO SHRINK THE DEAD-END
 TRAVEL SHALL BE MARKED WITH OBVIOUS SIGNAGE STATING "NO
 EXIT." TYPICAL.
  
 SHEET A1.20: STAIR #2 MISSING THE FIRE RESISTANCE
 RATING.
  
 SHEET ID-210.C: THE TABLES AND CHAIRS COMPLETELY
 OBSTRUCT THE TWO SECONDARY MEANS OF EGRESS IN MEETING
 ROOM 1B (#218).
  
 SHEET ID-230.C: COORDINATION IS NEEDED BETWEEN THE
 FURNITURE PLAN AND THE LIFE SAFETY EGRESS PLAN.
  
 SHEET P2.02: GAS AND WATER PIPE SHALL NOT BE ROUTED
 THROUGH THE FIRE RATED EXIT STAIR ENCLOSURE OF STAIR
 #1. THIS IS PROHIBITED BY NFPA 101.
  
 SHEET M2.01: DUCTWORK, NOT ESSENTIAL TO THE FUNCTION OF
 THE STAIR, IS ROUTED THROUGH THE FIRE RATED EXIT
 PASSAGEWAY OF STAIR #1. THIS IS PROHIBITED BY NFPA 101.
  
 SHEET M2.01: KITCHEN SUPPLY FAN DUCTWORK IS ROUTED
 THROUGH THE FIRE PUMP ROOM. THIS IS PROHIBITED BY NFPA
 20.
  
 SHEET M2.01: THE THREE KITCHEN EXHAUST FANS INDICATE
 SIDEWALL DISCHARGE; HOWEVER, THE AIR LOUVERS FOR THE
 GARAGE APPEAR TO BE LOCATED WITHIN 32 FEET OF THE
 GREASE DUCT DISCHARGE PER NFPA 96 SECTION 7.8.3.
  
 SHEET M2.06: MECHANICAL PLANS INDICATE A 2-HOUR FIRE
 RATED CEILING IS NEEDED TO CONCEAL DUCTWORK IN STAIR
 #1. THIS IS NOT COORDINATED WITH THE ARCHITECTURAL
 DRAWINGS THAT SHOW THIS AREA AS NO CEILING - OPEN TO
 STRUCTURE.
  
 SHEET M8.01 - SMOKE CONTROL: PER SECTION 9.3.3
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR. SPECIAL INSPECTIONS AND TESTS SHALL BE
 PERFORMED TO VERIFY THE OPERATION OF THE FIRE
 PROTECTION SYSTEM IN ITS FINAL CONDITION FOR ACCEPTANCE
 BY THE AUTHORITY HAVING JURISDICTION. THE SPECIAL
 INSPECTOR'S RELEVANT EXPERIENCE IN THE DESIGN,
 INSTALLATION, AND TESTING OF THE FIRE PROTECTION
 SYSTEMS BEING TESTED SHALL BE DOCUMENTED. THE DESIGN
 DOCUMENTS SHALL PROVIDE THE PROCEDURES AND METHODS TO
 BE USED AND ITEMS SUBJECT TO SPECIAL INSPECTIONS AND
 TESTS. THE SPECIAL INSPECTOR SHALL SUBMIT AN INSPECTION
 AND TEST REPORT TO THE AUTHORITY HAVING JURISDICTION
 AND REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE. PER FBC SECTION 909.18.8.2: SPECIAL INSPECTORS
 SHALL HAVE EXPERTISE IN FIRE PROTECTION ENGINEERING,
 MECHANICAL ENGINEERING AND CERTIFICATION AS AIR
 BALANCERS. DEVICES USED FOR SMOKE CONTROL SHALL HAVE AN
 APPROVED IDENTIFYING TAG OR MARK ON THEM INDICATING THE
 LAST TIME THEY WERE TESTED AND BY WHOM.
  
 SHEET E2.02A: CONFIRM EMERGENCY LIGHTING HAS BEEN
 PROVIDED ALONG THE MEANS OF EGRESS PATHS INSIDE THE
 ASSEMBLY OCCUPANCY MEETING ROOMS.
  
 SHEET E2.06: NO ILLUMINATED EXIT SIGNS PROVIDED FOR
 OPEN-AIR TERRACE #634 OR ON FAR WEST CORRIDOR DOOR NEAR
 COLUMN LINE 8.
  
 SHEET E2.07: NO ILLUMINATED EXIT SIGNS PROVIDED IN FIRE
 SERVICE ELEVATOR LEADING INTO EXIT STAIR #1. TYPICAL.
  
 SHEET E2.09: INSUFFICIENT QUANTITY OF ILLUMINATED EXIT
 SIGNS PROVIDED. WITHOUT ADDITIONAL SIGNAGE, THE CURRENT
 SIGNS CANNOT BE READILY VIEWED BY MOST OCCUPANTS IN THE
 POOL DECK AND BAR AREAS.
  
 SHEET E4.01: PLANS INDICATE TO PROVIDE PANIC HARDWARE
 ON THE EXIT DOOR FOR EMERGENCY POWER #107; HOWEVER,
 THIS DOOR SWING WILL NEED TO BE REVERSED FOR PANIC
 HARDWARE USAGE.
  
 SHEET E4.02: COULD NOT LOCATE THE FOLLOWING: THE
 FIRE-FIGHTERS' SMOKE CONTROL PANEL, GENERATOR MANUAL
 START/TRANSFER, STATUS INDICATORS AND CONTROLS FOR AIR
 DISTRIBUTION SYSTEM AND ELEVATOR RECALL SWITCHES WITH
 POWER SELECTOR SWITCHES.
  
 FIRE COMMAND CENTER:
 PER FFPC SECTION 11.9.4 AND FBC SECTION 911.1.5 - THE
 FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND SHALL
 CONTAIN THE FOLLOWING FEATURES:
 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR.
 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL.
 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 6. THE FIRE-FIGHTERS' CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS
 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM.
 11. FIRE PUMP STATUS INDICATORS.
 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS.
 13. WORK TABLE.
 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
 16. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 17. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED.
  
 SHEET E5.01: FEEDER SCHEDULE INDICATES F-10 AS A 2-INCH
 CONCRETE ENCASEMENT OF CONDUCTORS FOR THE FIRE PUMP;
 HOWEVER, THIS SYMBOL IS NOT LOCATED ON THE PLAN.
  
 SHEET E5.01: COULD NOT LOCATE THE FIRE PROTECTION
 JOCKEY PUMP AND ASSOCIATED CONTROL PANEL.
  
 SHEET E5.01: RISER DIAGRAM INDICATES RISER KEY NOTE #15
 ON THE FIRE PUMP CONTROL PANEL; HOWEVER, THE DRAWING
 KEYNOT SCHEDULE STOPS AT #12.
  
 SHEET FP2.02: ARCHITECTURAL PLANS INDICATE THE USE OF
 TYCO WINDOW SPRINKLERS FOR THE GLASS CURTAINWALL;
 HOWEVER, THIS DESIGN CONCEPT IS NOT DEPICTED ON THE
 FIRE PROTECTION ENGINEERING DRAWINGS.
  
 SHEET FP4.01: SPRINKLER AND STANDPIPE SYSTEM PRESSURES
 APPEAR TO EXCEED 165PSIG AND 175PSIG RESPECTIVELY WITH
 NO MEASURES OF CONTROL.
  
 SHEET FA2.01: INFORMATION TEXT BOX IS CUT OFF NEAR THE
 FIRE PUMP ROOM.
  
 SHEET FA4.02: CONFIRM THE USE OF A BIDIRECTIONAL
 AMPLIFIER RADIO SYSTEM (BDA) WITH FIREFIGHTER PHONE
 JACKS AS A BACK-UP.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2017-10-19 Cont ID  
Sent By tklarge Date 2017-10-19 Time 09:24 Rev Time 0.00
Received By tklarge Date 2017-10-19 Time 03:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2017-08-11 Cont ID  
Sent By tklarge Date 2017-08-11 Time 12:17 Rev Time 0.00
Received By tklarge Date 2017-08-11 Time 11:37 Sent To  
Notes
2017-08-11 11:38:091) SHT. M2.09 - POOL EQUIPMENT ROOM COMBUSTION AIR
 CALCULATIONS - A REFERENCE IS MADE TO THE 2014 FUEL GAS
 CODE SEC.304.6.2.THIS SECTION REFERS TO ONE PERMANENT
 OPENING FOR COMBUSTION AIR YET THE PLAN REFERS TO TWO
 OPENINGS. CLARIFY.
 2) SHT. M2.09 - POOL EQUIPMENT ROOM COMBUSTION AIR
 CALCULATIONS - A REFERENCE IS MADE TO THE 2014 FUEL GAS
 CODE SEC.304.6.2.THIS SECTION REQIURES THE COMBUSTION
 AIR OPENING TO HAVE 1 SQUARE INCH PER 3,000 BTU'S YET
 THE PLAN NOTES THE TOTAL BTU LOAD BEING DIVIDED BY
 4,000. CLARIFY.
 3) PLEASE CLARIFY HOW THE 1058 FREE SQ. INCH AREA WAS
 DETERMINED. SEC. 304.10 OF THE 2014 FGC NOTES THAT
 METAL LOUVERSAND GRILLES WILL BE ASSUMED TO HAVE A 75
 PERCENT FREE AREA. THE DIMENSION OF THE LOUVERS ARE
 SHOWN AS 54 X 36= 1944 X.75 = 1458 SQ. INCHES PER
 LOUVER. CLARIFY.
 4) SPECIFICATIONS HAVE BEEN SUBMITTED FOR GAS SUPPLIED
 MID-RANGE IRONERS BUT THIS EQUIPMENT IS NOT SHOWN ON
 THE GAS RISER AND THE BTU LOAD IS NOT INCLUDED IN THE
 TOTAL. CLARIFY.SUBMIT COMBUSTION AIR CALCULATIONS FOR
 THIS PIECE OF EQUIPMENT.
 5) SHT. M2.02 - LAUNDRY APPLIANCE CALCULATIONS REFER TO
 SF-2.1 TWICE. CLARIFY.THE PLAN ALSO NOTES THAT THEY ARE
 THE MAKEUP AIR FANS FOR DBF 2.2 & 2.3. THE FAN SCHEDULE
 ON SHT. M6.01 NOTES THESE UNITS AS "NOT USED." CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-03-20 Cont ID  
Sent By tklarge Date 2017-03-20 Time 12:49 Rev Time 0.00
Received By tklarge Date 2017-03-20 Time 09:36 Sent To  
Notes
2017-03-20 10:25:561) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 REGULATORS. THE SUBMITTED NARRATIVE RESPONSE REFERS TO
 AN ATTACHED KITCHEN BROCHURE BY DEI. I COULD NOT FIND
 ANY BROCHURE FROM DEI. CLARIFY. 2014 FBC-FUEL GAS
 SECS.410.1, 410.2. 3RD REQUEST.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT AND APPLIANCES. GAS APPLIANCES REGULATED
 BY THE FUEL GAS CODE SHALL BE LISTED AND LABELED PER
 2014 FBC-FUEL GAS SEC.301.3. 2ND REQUEST.THE NARRATIVE
 RESPONSE REFERS TO A KITCHEN EQUIPMENT BROCHURE BY
 DEI.I COULD NOT FIND ANY SUCHBRROCHURE FROM DEI.
 CLARIFY.
 3) SHT. M2.01 & M2.02 - COMBUSTION AIR CALCULATIONS -
 WHERE COMBUSTION AIR IS MECHANICALLY SUPPLIED THROUGH
 AN HVAC SYSTEM, THE SYSTEM MUST DELIVER THE REQUIRED
 COMBUSTION AIR RATE ABOVE AND BEYOND ANY OUTDOOR AIR
 RATE SUPPLIED FOR VENTILATION OF THE OCCCUPIED
 SPACES.THE HVAC SYSTEM MUST ALSO BE INTERLOCKED WITH
 THE APPLIANCE(S) AS REQUIRED BY 2014 FBC FUEL GAS
 SEC.304.9.2. NEITHER CONTINUOUS OPERATION NOR PARALLEL
 OPERATION OF THE HVAC SYSTEM SATISFIES THE REQUIREMENT
 FOR A TRUE INTERLOCK AS REQUIRED BY 304.9.2. I CANNOT
 DETERMINE HOW THE REQUIREMENT FOR THE COMBUSTION AIR IN
 SEC. 304.9.3 HAS BEEN MET. CLARIFY.
 4) SHT.K1PRS SHOWS GAS APPLIANCE PBF-1 (DECK
 OVEN/PIZZA) AT 140 MBTU.I DO NOT SEE THIS APPLIANCE OR
 THE BTU VALUE ON THE GAS PLANS / RISER. SHOW ALL GAS
 APPLIANCES ON THE GAS RISER AND THE CORRESPONDING BTU
 LOAD. 2014 FBC-FUEL GAS SEC.402.2. THE NARRATIVE
 RESPONSE REFERS TO A KITCHEN EQUIPMENT BROCHURE BY
 DEI.I COULD NOT FIND ANY SUCHBRROCHURE FROM DEI.
 CLARIFY.
 5) SHT. P4.01 - I HAVE ADDED THE BTU LOAD OF EACH GAS
 APPLIANCE LISTED IN THE KEY NOTES 4 TIMES AND I STILL
 ARRIVE AT A TOTAL BTU LOAD OF 4363 MBTU'S. CLARIFY.
  
 THE FOLLOWING ITEMS WILL BE DEFERRED SUBMITTALS:
 1) SPECIFICATIONS FOR THE BOILER,VENT DETAILS,VENT
 PIPING, ETC.
 2) DETAILS FOR THE DRYER VENTS,VENT MATERIAL, ETC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-12-28 Cont ID  
Sent By tklarge Date 2016-12-28 Time 06:51 Rev Time 0.00
Received By tklarge Date 2016-12-27 Time 11:20 Sent To  
Notes
2016-12-27 11:56:19GAS REVIEW
 1) SHOW THE DEVELOPED LENGTH OF THE PIPING FROM THE
 SECOND STAGE REGULATOR TO THE FURTHEST OUTLET. THIS
 DISTANCE IS USED FOR THE SIZING OF THE LOW PRESSURE
 SYSTEM.2ND REQUEST.
 2) SHT. P4.10 - THE BTU LOAD FOR THE TWO DOMESTIC
 BOILERS ADDS TO 1,500 MBTU BUT THE PLANS SHOW 1,700
 MBTU. CLARIFY. 2ND REQUEST.
 3) SHT. P4.10 - KEYNOTE #10 SHOWS TWO BOILERS AT 199
 MBTU EACH WHICH IS 398 MBTU BUT THE RISER SHOWS 798
 MBTU. CLARIFY.2ND REQUEST.
 4) MY CALCULATION OF BTU'S AT ONE SECTION OF THE GAS
 RISER IS 1,898 MBTU BUT THE PLAN SHOWS 2,498 MBTU.
 THERE IS ANOTHER SECTION WITH A BTU LOAD OF 3,698 MBTU
 AND MY CALCULATIONS ADD TO 3,098 MBTU. CLARIFY.2ND
 REQUEST.
 5) THE TOTAL BTU LOAD ON THE SYSTEM SHOULD BE 4,413
 MBTU. PLEASE CHECK THE CALCULATIONS.2ND REQUEST.
 6) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 GAS REGULATORS. FGC SEC. 410.1, 410.2.2ND REQUEST.THE
 NARRATIVE REFERS TO NOTE #13 ON SHT. P4.10 - NOTE #13
 REFERS TO THE VENTLESS PRESSURE REGULATOR.
 7) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE ALL GAS
 EQUIPMENT AND APPLIANCES. APPLIANCES REGULATED BY THE
 CODE SHALL BE LISTED AND LABELED. FGC 301.3.
 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS
 FIRED EQUIPMENT (KITCHEN EQUIPMENT, DRYERS, POOL
 EQUIPMENT, BOILERS, ETC.) PER FGC SEC. 304. SEE FGC
 SEC. 304.9.3 FOR COMBUSTION AIR BEING SUPPLIED BY
 MECHANICAL SYSTEMS.
 9) SHT. M2.01 - KITCHEN GAS APPLIANCE CALCULATIONS - IN
 ACCORDANCE WITH 2014 FBC-FUEL GAS SEC.304.9.3 - THE
 MAKEUP AIR FOR THE EXHAUST FOR THE HOOD CANNOT BE USED
 TO SUPPLY COMBUSTION AIR TO THE APPLIANCES.
 10) SUBMIT SPECIFICATIONS FOR THE BOILER, VENT DETAILS,
 VENT PIPING, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SUBMIT DETAILS FOR DRYER VENTS, TERMINATION POINTS,
 VENT MATERIAL, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 12) SHT. K1 PRS SHOWS GAS APPLIANCE PBF-1 (DECK
 OVEN/PIZZA) AT 140 MBTU. I DO NOT SEE THIS APPLIANCE OR
 THE BTU VALUE ON THE GAS PLANS. CLARIFY.
 13) SUBMIT SPECS .FOR THE PVC VENTS FOR THE BOILERS TO
 CONFIRM PVC IS APPROVED.SHOW THE HEIGHT ABOVE THE ROOF,
 ANCHORING DETAILS (IF APPLICABLE), COMPLY WITH 2014
 FBC-FUEL GAS SEC.
 14) SUBMIT DETAILS FOR THE DRYER VENTS, VENT MATERIAL,
 HEIGHT ABOVE ROOF, ANCHORING DETAILS (IF APPLICABLE).
 IF PVC IS USED, SUBMIT DETAILS FROM DRYER MANUF. TO
 SHOW PVC IS APPROVED TO BE USED.ROOF THE RESPONSE
 NARRATIVE REFERS TO SHT. M2.10, NOTES #2,3,& 4. THESE
 NOTES HAVE NOTHING TO DO WITH THE DRYER VENTS. THE
 LAUNDRY IS ON THE 2ND FLOOR, NOT THE ROOF.
 15) INDICATE THE POOL/SPA BOILERS ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-08-16 Cont ID  
Sent By tklarge Date 2016-08-16 Time 13:50 Rev Time 0.00
Received By tklarge Date 2016-08-16 Time 13:47 Sent To  
Notes
2016-08-16 13:47:46GAS REVIEW
 1) SHT. P4.10 - GAS GENERAL NOTES ? AFTER THE SECOND
 STAGE REGULATOR PRESSURE IS NOTED AS 2 PSI YET THE
 TABLE THAT IS REFERENCED IS FOR LESS THAN A 2 PSI
 SYSTEM (402.4) (2). REVISE THE NOTE.
 2) SHOW THE DEVELOPED LENGTH OF THE PIPING FROM THE
 SECOND STAGE REGULATOR TO THE FURTHEST OUTLET. THIS
 DISTANCE IS USED FOR THE SIZING OF THE LOW PRESSURE
 SYSTEM.
 3) SHT. P4.10 - THE BTU LOAD FOR THE TWO DOMESTIC
 BOILERS ADDS TO 1,500 MBTU BUT THE PLANS SHOW 1,700
 MBTU. CLARIFY.
 4) SHT. P4.10 - KEYNOTE #10 SHOWS TWO BOILERS AT 199
 MBTU EACH WHICH IS 398 MBTU BUT THE RISER SHOWS 798
 MBTU. CLARIFY.
 5) MY CALCULATION OF BTU'S AT ONE SECTION OF THE GAS
 RISER IS 1,898 MBTU BUT THE PLAN SHOWS 2,498 MBTU.
 THERE IS ANOTHER SECTION WITH A BTU LOAD OF 3,698 MBTU
 AND MY CALCULATIONS ADD TO 3,098 MBTU. CLARIFY.
 6) THE TOTAL BTU LOAD ON THE SYSTEM SHOULD BE 4,413
 MBTU. PLEASE CHECK THE CALCULATIONS.
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 GAS REGULATORS. FGC SEC. 410.1, 410.2.
 8) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE ALL GAS
 EQUIPMENT AND APPLIANCES. APPLIANCES REGULATED BY THE
 CODE SHALL BE LISTED AND LABELED. FGC 301.3.
 9) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS
 FIRED EQUIPMENT (KITCHEN EQUIPMENT, DRYERS, POOL
 EQUIPMENT, BOILERS, ETC.) PER FGC SEC. 304. SEE FGC
 SEC. 304.9.3 FOR COMBUSTION AIR BEING SUPPLIED BY
 MECHANICAL SYSTEMS.
 10) SUBMIT SPECIFICATIONS FOR THE BOILER, VENT DETAILS,
 VENT PIPING, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SUBMIT DETAILS FOR DRYER VENTS, TERMINATION POINTS,
 VENT MATERIAL, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 12) SHT. K1 PRS SHOWS GAS APPLIANCE PBF-1 (DECK
 OVEN/PIZZA) AT 140 MBTU. I DO NOT SEE THIS APPLIANCE OR
 THE BTU VALUE ON THE GAS PLANS. CLARIFY.
 13) CARBON MONOXIDE ALARMS SHALL BE PROVIDED AND COMPLY
 WITH FBC SECS. 908.7, 908.7.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-12-11 Cont ID  
Sent By shill Date 2017-12-11 Time 09:38 Rev Time 0.00
Received By shill Date 2017-12-08 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-10-24 Cont ID  
Sent By lmarchan Date 2017-10-24 Time 13:51 Rev Time 0.00
Received By lmarchan Date 2017-09-27 Time 11:36 Sent To  
Notes
2017-09-27 11:36:54NEW PLANS IN C25 & C26

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-08-16 Cont ID  
Sent By skennedy Date 2017-08-16 Time 09:21 Rev Time 0.00
Received By skennedy Date 2017-06-22 Time 14:21 Sent To  
Notes
2017-06-30 14:21:22C25 & C26
  
 **OLD PLANS IN C27**

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-11 Cont ID  
Sent By shill Date 2017-04-10 Time 09:38 Rev Time 0.00
Received By shill Date 2017-03-06 Time 08:26 Sent To  
Notes
2017-03-06 08:26:33C25, 26 - OLD PLANS IN C27, C28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-12-29 Cont ID  
Sent By lmarchan Date 2016-12-29 Time 13:13 Rev Time 0.00
Received By lmarchan Date 2016-11-10 Time 14:02 Sent To  
Notes
2016-11-14 14:03:02NEW PLANS IN C25 & C26, OLD PLANS IN C27, 28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-10-03 Cont ID  
Sent By cpuell Date 2016-10-03 Time 15:04 Rev Time 0.00
Received By cpuell Date 2016-06-27 Time 10:24 Sent To  
Notes
2016-06-27 10:24:35C28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status P Date 2017-12-12 Cont ID  
Sent By shill Date 2017-12-12 Time 08:10 Rev Time 0.00
Received By shill Date 2017-12-12 Time 08:10 Sent To  
Notes
2017-12-12 08:10:23MU2017-14654, 150 ROOMS, $128,260.26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2017-12-11 Cont ID  
Sent By shill Date 2017-12-11 Time 09:38 Rev Time 0.00
Received By shill Date 2017-12-11 Time 09:37 Sent To  
Notes
2017-12-11 09:37:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE PLANS ARE STAMPED BY PALM BEACH COUNTY
 (MU2017-14654, 150 ROOMS, $128,260.26) BUT THE RECEIPT
 SHOWING THAT FEES DUE WERE PAID WAS NOT SUBMITTED.
  
 WHEN RESUBMITTING, PLEASE MAKE AN APPOINTMENT. THE
 PERMIT WILL BE ISSUED AT THAT TIME.
  
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-03-21 Cont ID  
Sent By jwitmer Date 2017-03-21 Time 14:48 Rev Time 0.00
Received By jwitmer Date 2017-03-21 Time 14:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-03-21 Cont ID  
Sent By jwitmer Date 2016-12-12 Time   Rev Time 0.00
Received By jwitmer Date 2016-12-12 Time   Sent To  
Notes
2017-03-21 14:47:57IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By jwitmer Date 2016-07-18 Time 06:27 Rev Time 0.00
Received By jwitmer Date 2016-07-16 Time 14:31 Sent To  
Notes
2016-07-16 14:31:44BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2017-10-16 Cont ID  
Sent By ccole Date 2017-10-16 Time 12:20 Rev Time 0.00
Received By ccole Date 2017-10-13 Time 16:17 Sent To  
Notes
2017-10-16 12:30:34MECHANICAL PROVISOS AND REQUIRED SUBMITTALS:
 10/16/2017
  
 PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOODS AND EXHAUST SYSTEMS, FIRE SUPPRESSION
 SYSTEMS, AND WALK IN COOLERS AND FREEZERS,
  
 THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR
 MECHANICAL EQUIPMENT, APPLIANCES, AND COMPONENTS.
 ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE
 EOR .
  
 1) COMMISSIONING PLAN
 2) DRYER AND IRONER SPECIFICATIONS
 3) MOTORIZED OUTSIDE AIR DAMPERS
 4) FIRE DAMPERS, AND FIRE SMOKE DAMPERS
 5) DUCT SMOKE DETECTORS
 6) CEILING ACCESS PANELS
 7) CO AND NO2 SENSORS
 8) BOILERS
 9) BOILER VENT -COPPER PIPE MATERIAL
 10) AC SYSTEMS
 11) DAMPER ACCESS PANELS
 12) GREASE RESERVOIRS
 13) FLAMEBAR DUCT (DUCT SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS)
 14) DUCT INSULATION
 15) FANS (INCLUDING ALL FANS ASSOCIATED WITH SMOKE
 CONTROL)
 16) KITCHEN APPLIANCE SPECIFICATIONS
 17) KITCHEN GREASE DUCT/FIRE-WRAP SPECIFICATIONS
 18) REFRIGERANT PIPE INSULATION
 19 LOUVERS
 20) WIND LOAD ENGINEERING, DESIGN CRITERIA,
 CALCULATIONS, AND DETAILS FOR TIE DOWN OF ALL ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING FLORIDA PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S FOR ROOF STANDS AND
 CURBS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-07-31 Cont ID  
Sent By ccole Date 2017-07-31 Time 15:48 Rev Time 0.00
Received By ccole Date 2017-07-31 Time 15:22 Sent To  
Notes
2017-07-31 17:34:504TH REVIEW FBC-2014 MECHANICAL
 CANOPY HOTEL BY HILTON
 PERMIT #16061443
 7/31/17
  
 1) IN REFERENCE TO PREVIOUS COMMENTS #9 & 16, THE USE
 OF FLAMEBAR DUCT TO CREATE CONTINUOUS VERTICAL AND
 HORIZONTAL FIRE-RATED SHAFTS FOR SMOKE CONTROL AND
 TOILET EXHAUST SYSTEMS WILL REQUIRE AN ALTERNATE
 MATERIALS AND METHOD APPROVAL BY THE BUILDING OFFICIAL.
 CURRENTLY, THERE ARE NO PROVISIONS IN THE FIFTH EDITION
 FLORIDA BUILDING CODE 2014 THAT ALLOW FOR THE USE OF
 FLAMEBAR DUCT IN
  
 THESE APPLICATIONS- SEE SECTION 713 SHAFT ENCLOSURES.
 ADDITIONALLY THE USE OF FLAMEBAR DUCT FOR THE SMOKE
 CONTROL SYSTEMS IS NOT SPECIFIED IN THE SUBMITTED
 RATIONAL ANALYSIS REPORT FOR THE CANOPY HOTEL BY SLS
 FIRE PROTECTION ENGINEERS- SEE PAGE 20 OF THE REPORT.
 THE FBC-14 DOES ALLOW FOR AN APPROVAL TO USE THE DUCTS
 UNDER SECTION 104.11 ALTERNATE MATERIALS, DESIGN AND
  
 METHODS OF CONSTRUCTION AND EQUIPMENT. IT IS THE TASK
 OF THE DESIGN PROFESSIONAL OF RECORD TO PROVIDE
 SUPPORTING EVIDENCE, REPORTS, AND TESTING DATA AND
 SUBMIT A REQUEST TO THE BUILDING OFFICIAL FOR AN
 APPROVAL. ADDITIONALLY, PLEASE SEE SECTION 703 FIRE
 RESISTANCE RATINGS AND FIRE TESTS FOR ASTM AND UL
 LISTING AND ASSEMBLY INFORMATION.
  
 2) SHEET M2.01, ADVISORY NOTE: ALTHOUGH THE KITCHEN
 HOOD EXHAUST SYSTEM IS UNDER SEPARATE PERMIT, ACCESS TO
 REQUIRED GREASE DUCT CLEANOUTS SHALL BE PROVIDED WHERE
 THE DUCTS ARE RUNNING ABOVE THE FPL VAULT- SECTIONS
 306.1 AND 306.5. PLEASE CONSULT WITH FPL REGARDING THIS
 MATTER AND PROVIDE DETAILS AND NOTES ON THE PLANS.
  
 3) M2.01, ADVISORY NOTE: PLEASE SEE SECTION 506.3.6
 REGARDING THE REQUIRED 18" REQUIRED CLEARANCE TO
 COMBUSTIBLES FOR THE GREASE DUCTS. IF THE INTENTION IS
 TO USE A UL APPROVED DUCT SYSTEM, OR A FIRE-WRAP,
 SPECIFICATIONS FOR EACH SYSTEM SHALL BE PROVIDED.
 PLEASE SEE SECTION 506.3.11.2 FOR FIELD APPLIED GREASE
 DUCT ENCLOSURE. IT IS IMPORTANT TO NOTE THAT WRAPS ARE
 REQUIRED TO BE
  
 APPLIED CONTINUOUSLY WHICH MAY POSE A PROBLEM WHEN
 USING INLINE FAN KEF-1.
  
 3) THE REQUESTED DETAILS FOR CEILING ACCESS PANEL
 CONSTRUCTION ARE NOT SHOWN ON SHEET A5.18 AS INDICATED
 IN THE NARRATIVE RESPONSE. THESE DETAILS MAY BE
 DEFERRED IF NECESSARY, BUT PLEASE NOTE THAT PANELS AS
 SHOWN ON M2.01 DO NOT APPEAR LARGE ENOUGH TO REMOVE THE
 FAN COIL UNITS. SECONDLY, THERE APPEARS TO BE A WOOD
 TRELLIS BLOCKING ACCESS TO THE PANELS AND THE UNITS-
  
 PLEASE CLARIFY.
  
 4) M2.02: PLEASE PLACE A NOTE ON THE PLAN PURSUANT TO
 SECTION 504.4 WHICH PROHIBITS CLOTHES DRYER EXHAUST
 DUCTS FROM RUNNING THROUGH OTHER DUCTS OR PLENUMS.
  
 5) M2.03: REFER TO SECTION 404.1(2) WHICH REQUIRES
 NITROGEN DIOXIDE SENSORS TO BE USED IN CONJUNCTION WITH
 CO SENSORS IN THE PARKING GARAGES- PLEASE REVISE THE
 PLAN ACCORDINGLY.
  
 6) ADVISORY: THE CURRENT LIST OF DEFERRED SUBMITTALS
 FOR THE PROJECT INCLUDE: COMMISSIONING PLAN, FLAMEBAR
 DUCT SPECIFICATIONS AND INSTALLATION INSTRUCTIONS,
 KITCHEN APPLIANCE SPECIFICATIONS, DRYER AND IRONER
 SPECIFICATIONS, CARBON MONOXIDE/NITROGEN DIOXIDE
 DETECTORS, CEILING ACCESS PANELS, FIRE/SMOKE DAMPERS,
 FIRE DAMPERS, MOTORIZED OUTSIDE AIR, DAMPER ACCESS
 PANELS,
  
 DUCT SMOKE DETECTORS, LOUVERS, GREASE RESEVOIRS, AC
 SYSTEMS, DUCTS, DUCT INSULATIONS, AND REFRIGERANT PIPE
 INSULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-03-16 Cont ID  
Sent By ccole Date 2017-03-16 Time 11:51 Rev Time 0.00
Received By ccole Date 2017-03-15 Time 07:23 Sent To  
Notes
2017-03-16 11:54:203RD REVIEW FBC-2014 MECHANICAL
 THE CANOPY HOTEL
 PERMIT #16061443
 3/16/17
  
 1) SHEET M2.01-NOTE #16: CLARIFY HOW THE SYSTEM
 SPECIFIED FOR ADJUSTING MAKEUP AIR TEMPERATURE WILL
 WORK WITH KS # 1 & 2 DIRECTLY PROVIDING UNTEMPERED
 MAKEUP AIR FROM THE OUTDOORS. TYPICALLY,
 PRE-CONDITIONED AIR MUST BE PROVIDED TO MEET COMPLIANCE
 WITH SECTION 508.1.1
  
 2) M2.01 & M601: ACCORDING TO SECTION 304.9.3 FBC-14
 FUEL GAS A MECHANICAL SYSTEM (FC-1.5) SHALL SUPPLY THE
 COMBUSTION AIR RATE OF 350 CFMS IN ADDITION TO THE
 VENTILATION RATE WHICH IS CALCULATED AT 145 CFMS.
  
 3) M2.01: SHOW THE LOCATION OF THE GREASE RESERVOIR AND
 PROVIDE A DETAIL SHOWING THE RESERVOIR CONNECTION TO
 THE FLOOR DRAIN. PLEASE REVISE THE PLUMBING RISER
 DRAWING TO IDENTIFY WHICH FLOOR DRAIN IS THE GREASE
 RECEPTOR.
  
 4) M0.00 & M2.01: ADVISORY: THE FLAMEBAR DUCTWORK HAS
 BEEN DESIGNATED AS A DEFERRED SUBMITTAL. PLEASE NOTE
 COMPLETE SPECIFICATIONS FOR USE OF THE DUCTWORK FOR
 GREASE EXHAUST MUST BE SUBMITTED PER NOTE # 1 ON M0.00.
  
 5) M2.01: ADVISORY: SPECIFICATIONS FOR THE 3HR RATED
 FLAMEBAR DUCT AND FIRESTOPPING DETAIL FOR THE VAULT
 CEILING PENETRATION ARE REQUIRED BUT MAY BE A DEFERRED
 SUBMITTAL.
  
 6) A3.01 & M2.01: SHOW HOW ACCESS WILL BE PROVIDED TO
 FC-1.6, 1.7, & 1.8 WHICH ARE LOCATED ABOVE THE DRYWALL
 CEILING WHICH IS SPECIFIED AT ELEV =+ 16'0". PLEASE
 REFER TO SECTION 306.5 WHICH REQUIRES AN APPROVED MEANS
 OF ACCESS.
  
 7) M0.00- CONSTRUCTION NOTE #18: PROVIDE CONSTRUCTION
 DETAILS FOR INSTALLATION OF THE ACCESS PANELS WHERE
 REQUIRED. PLEASE NOTE THAT PER SECTION 306.1 THE ACCESS
 OPENINGS MUST BE LARGE ENOUGH FOR REPLACEMENT OF ALL
 MECHANICAL EQUIPMENT, AND NOT REQUIRE DISABLING OR
 REMOVING ANY PERMANENT CONSTRUCTION.
  
 8) M2.01: THERE APPEAR TO BE FIRE DAMPERS MISSING WHERE
 THE O/A DUCTS ARE PENETRATING THE FIRE PUMP/WATER
 PUMP/STAIR #3 WALLS.
 .
 9) M2.02: REFER TO SECTION 1022 FBC-14 BUILDING AND
 RELOCATE THE DUCTS PENETRATING AND TRAVERSING THROUGH
 STAIR #2, UNLESS THEY ARE PLACED IN A 2HR FIRE-RATED
 ENCLOSURE (DETAILS NOT SHOWN ON THE ARCH. OR STRUCTURAL
 SHEETS).
  
 10) M2.03: ADVISORY- THE MANUFACTURER SPECIFICATIONS
 FOR THE VRF CONDENSERS MUST INDICATE THEY CAN BE
 LOCATED IN THE INTERIOR OF THE BUILDING.
  
 11) M2.03, 2.04, 2.05: ADVISORY- BOLLARD PLACEMENT FOR
 PROTECTION OF THE FANS IN THE GARAGES WILL BE VERIFIED
 IN THE FIELD.
  
 12) M2.05: THE SHAFT ENCLOSING THE OAR-1 DUCT SHALL BE
 CONTINUOUS THROUGH THE ELEVATOR LOBBY AND GARAGE PER
 SECTIONS 707.5, 711.4 & 713.5 FBC-14 BUILDING.
  
 13) M2.06, 2.07, & 2.08: IT APPEARS THAT THERE ARE
 MISSING FSD SYMBOLS AT THE PENETRATIONS OF THE O/A
 DUCTS ON EACH FLOOR INTO THE MAIN SHAFT.
  
 14) M2.07: PLEASE PROVIDE THE ROOM NUMBERS ON THE PLAN
 FOR COMPLETE AC CALCULATION REVIEW.
  
 15) M3.01: THE TRANSFER 14"X8" TRANSFER DUCTS IN THE
 KING SUITES F AND F-ADA ARE UNDERSIZED PER SECTION
 601.5 EXCEPTION 3. A MINIMUM OF 150 SQ. INCHES IS
 REQUIRED.
  
 16) M2.08A & M4.01: THE TOILET EXHAUST RISER SHAFTS
 SHALL BE CONTINUOUS THROUGH THE INTERSTITIAL SPACE UP
 TO THE ROOF SLAB TERMINATION PER SECTION 713.5 & 713.12
 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-12-12 Cont ID  
Sent By ccole Date 2016-12-12 Time 12:30 Rev Time 0.00
Received By ccole Date 2016-12-08 Time 18:27 Sent To  
Notes
2016-12-12 12:31:082ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16061443
 12/12/16
  
 1) PLEASE COMPARE THE SYSTEM COMPLIANCE DATA LISTED IN
 THE ENERGYGAUGE SUBMITTAL TO THE SYSTEM EQUIPMENT
 SCHEDULES ON M6.01. THERE ARE NUMEROUS INCONSISTENCIES
 AND OMISSIONS, SOME OF WHICH ARE LISTED BELOW. PLEASE
 PROOFREAD THE DOCUMENTS BEFORE RESUBMITTING.
 A) AHU/CU-13, CU-13FL-R19, CU-R9 ARE NOT LISTED IN THE
 SUBMITTAL.
 B) CU-R2A & B, CU-R3-B, CU-R9A&B, CU-R11A&B, CU-R13A&B
 ARE LISTED IN THE SUBMITTAL BUT NOT IN THE SCHEDULE.
 C) THE COMPLIANCE DATA LISTED IN THE SUBMITTAL FOR
 CU-R8B & CU-R14A&B DOESN'T MATCH THE SCHEDULE.
 D) THE EFFICIENCY RATINGS FOR THE VRF SHOWN IN THE
 SUBMITTAL DO NOT MATCH THE RATINGS SHOWN IN THE
 SCHEDULE.- SEE TABLE C403.2.3(11) FBC-14 ENERGY
 CONSERVATION.
  
 2) THE RESPONSE NARRATIVE INDICATES THAT THE REQUESTED
 COMMISSIONING PLAN IS TO BE A DEFERRED SUBMITTAL.
 PLEASE ADDRESS THE FOLLOWING SECTIONS FROM THE WPB
 AMENDMENTS TO THE FBC.
  
 A) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 B) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) SMOKE CONTROL/ RATIONAL ANALYSIS REPORT: A) PLEASE
 CLARIFY IF SEF-1 AT 2000 CFMS HAS BEEN SIZED TO EXHAUST
 ONLY ONE FLOOR OF INCIDENCE, OR HAS THE CAPACITY TO
 EXHAUST MULTIPLE FLOORS. B) VERIFY THE OARTU, WHICH HAS
 BEEN DESIGNATED AS PART OF THE SMOKE CONTROL SYSTEM, IS
 MEETING ALL APPLICABLE REQUIREMENTS LISTED ON PAGE 21
 OF THE REPORT AND SECTIONS 513.10 AND 513.10.5 FBC-14
 MECHANICAL. C) PLEASE NOTE THAT PRODUCT SUBMITTALS FOR
 ALL EQUIPMENT AND COMPONENTS OF THE SMOKE CONTROL
 SYSTEMS SHALL BE REVIEWED AND APPROVED WITH SIGNATURE
 BY THE EOR AND SUBMITTED TO THE BUILDING DEPARTMENT FOR
 REVIEW- SEE SECTION 513.10.
  
 4) 2ND REQUEST FOR COMPLETE COOLING AND HEATING
 CALCULATIONS. CALCULATIONS ARE STILL MISSING FOR
 AHU/CU'S 1-13 A, AND THE OARTU. CALCULATIONS HAVE BEEN
 SUBMITTED FOR FC-6-1 & 6-2 HOWEVER THESE SYSTEMS ARE
 NOT SHOWN IN THE SCHEDULES. B) CALCULATIONS HAVE BEEN
 SUBMITTED FOR SUITES 1-22 HOWEVER THOSE NUMBERS DO NOT
 MATCH THE ROOM IDENTIFICATIONS ON THE PLANS SO SIZING
 CANNOT BE VERIFIED.
  
 5) IN REFERENCE TO COMMENT #1G & 1H FROM THE 1ST REVIEW
 SEE SECTION 107.3.4.2 DEFERRED SUBMITTALS PRINTED UNDER
 COMMENT #2 OF THIS REVIEW. PLEASE NOTE THAT HOLDS ON
 INSPECTIONS MAY BE PLACED INTO THE SYSTEM UNTIL
 SUBMITTALS HAVE BEEN RECEIVED.
  
 6) REFER TO COMMENT #2 FROM THE 1ST REVIEW- SHEET
 M6.01: THE SUITE NUMBERS IN THE VENTILATION CALCULATION
 SCHEDULE DO NOT MATCH THE ROOM IDENTIFICATIONS ON THE
 PLANS.
  
 7) M2.01: KITCHEN GAS APPLIANCE CALCULATIONS: IN
 ACCORDANCE WITH SECTION 304.9.3 FBC-14 FUEL GAS, THE
 MAKEUP AIR FOR THE EXHAUST FOR THE HOOD CANNOT BE USED
 TO SUPPLY COMBUSTION AIR TO THE APPLIANCES.
  
 8) M2.01: THE KITCHEN EXHAUST SYSTEMS ARE ACKNOWLEDGED
 TO BE UNDER SEPARATE PERMIT. ADVISORIES: A) AS
 PREVIOUSLY NOTED THE GREASE DUCT EXHAUST TERMINATIONS
 ON THE NORTH SIDE OF THE BUILDING APPEAR TO BE IN A
 LOCATION WHERE THEY MAY NOT BE IN COMPLIANCE WITH
 SECTION 506.3.13.2. PLEASE PROVIDE CLEARANCE DISTANCE
 MEASUREMENTS TO THE PUBLIC SIDEWALK MEASURED
 HORIZONTALLY, TO GRADE, AND TO ALL INTAKES IN THE
 GENERAL VICINITY INCLUDING THE GENERATOR AND GARAGE AIR
 INTAKE. SEE SECTION 401.4. B) THE GREASE DUCT FOR KEF-2
 APPEARS TO BE PENETRATING INTERIOR WALLS WHICH IS NOT
 PERMITTED UNLESS THE DUCT IS ENCLOSED FROM THE POINT OF
 PENETRATION TO THE OUTLET TERMINAL- SECTION 506.3.11.
 C) PROVIDE A SUBMITTAL FOR THE GREASE RESERVOIR THE
 KEF-2 GREASE DUCT AND PROVIDE A DETAIL ON THE PLAN
 INDICATING COMPLIANCE WITH SECTION 506.3.7.1 ITEMS 1-7.
 PLEASE NOTE ITEM #5 REQUIRES THE UNIT TO BE SLOPED TO A
 POINT FOR DRAINAGE. INDICATE HOW THE GREASE WILL BE
 DRAINED AND PROVIDE THE DISCHARGE LOCATION.
 D) PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.1.1
 MAKEUP AIR TEMPERATURE WILL BE REQUIRED. COMPLIANCE
 WITH THIS SECTION MAY IMPACT THE MAIN MECHANICAL PLANS.
  
 9) M2.01: THE PRINT IN THE HEX SYMBOL LOCATED IN
 WOMEN'S RESTROOM 122 IS NOT LEGIBLE.
  
 10) M2.01: PLEASE PROVIDE THE FLEX DUCT SIZES OR PLACE
 THE FLEX TABLE ON M6.01 ON THIS PLAN SHEET AND ALL
 OTHERS WHERE DUCT SIZES ARE NOT SHOWN.
  
 11) M2.01: PLEASE PROVIDE CLEAR ACCESS PANEL SYMBOLS ON
 THE PLANS FOR THE FC'S AND CHANGEOVER BOXES AND ADD A
 KEYNOTE.
  
 12) M2.01: THE TRANSFER DUCT BETWEEN CORRIDOR 129 AND
 133 IS NOT PERMITTED PER SECTION 601.2.
  
 13) M2.02: THE USE OF DRYER BOOSTER FANS TO EXTEND THE
 LENGTHS OF DRYER DUCTS WAS REMOVED FROM THE CURRENT
 FBC-14 MECHANICAL CODE. DRYER DUCT LENGTHS SHALL BE
 DETERMINED BY THE DRYER MANUFACTURER'S INSTRUCTIONS-
 SECTION 504.6.4.2.
  
 14) M2.02: IDENTIFY WHICH PIECE OF EQUIPMENT IN THE
 LAUNDRY ROOM IS BEING EXHAUSTED USING THE 20" ROUND
 DUCT.
  
 15) M2.02: THE DRYER EXHAUST DUCTS FROM THE LAUNDRY
 ROOMS MUST BE IN FIRE RATED SHAFT ENCLOSURES PER
 SECTION 504.4. THE PLANS ARE INDICATING THE DUCTS
 THEMSELVES WILL BE 2HR. RATED. PLEASE PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE DUCTS WITH SHOP DRAWING STAMP AND
 APPROVAL SIGNATURE BY THE EOR. THE DOCUMENTS SHALL
 INDICATE THE DUCTS ARE COMPATIBLE WITH THE APPLIANCE
 MANUFACTURER'S SPECIFICATIONS, AND HAVE INSTRUCTIONS
 FOR INSTALLING THE LINT TRAPS AS SPECIFIED ON THE
 PLANS.
  
 16) M2.02: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE LOCKER ROOMS PER TABLE 403.3.
  
 17) M2.02: HOW IS AIR BEING RETURNED FOR THE SOILED
 LINEN ROOM. PLEASE NOTE THAT TABLE 6-4 ASHRAE 62.1-2010
 REQUIRES EXHAUST VENTILATION FOR SOILED LAUNDRY ROOMS.
  
 18) M2.02: PLEASE EMBOLDEN THE FC ACCESS PANEL
 LOCATIONS AND ADD A KEYNOTE TO THE PLAN TO IDENTIFY
 THEIR LOCATIONS.
  
 19) M2.03: PROVIDE COMPLIANCE DATA FROM THE CONDENSER
 MANUFACTURER'S INDICATING THE UNITS CAN BE INSTALLED
 INDOORS. PLEASE NOTE EXHAUST VENTILATION MAY BE
 REQUIRED.
  
 20) M2.03, M2.04, M2.05: THE CIRCULATOR FANS SHALL BE
 INSTALLED A MINIMUM OF 8FT. ABOVE THE GARAGE FLOOR-
 SECTION 304.6.
  
 21) M2.05: SHOW THE REQUIRED FSD AT THE 18X20 DUCT
 PENETRATING THE OAR-1 SHAFT. PLEASE NOTE THAT
 MANUFACTURER'S SPECIFICATIONS HAVE NOT BEEN SUBMITTED
 FOR THE FLAMEBAR DUCT TO VERIFY COMPLIANCE FOR
 INSTALLATION OF THE FSD IN THE DUCT, AND THE DESIGN
 DOES NOT CORRELATE WITH THE RATIONAL ANALYSIS.
  
 22) M2.05 & M4.01: O/A DUCTWORK SHOWN ON THE PLAN DOES
 NOT MATCH THE RISER DRAWING.
  
 23) M2.06, M2.07, & M2.08: FIRE/SMOKE DAMPERS REQUIRED
 FOR THE O/A DUCTS PENETRATING THE FIRE-RATED SHAFT. A)
 THE 28X5 AND THE 30X5 DUCTS AT THE OAR-1 ARE NOT SHOWN
 ON THE RISER DRAWING ON M.401
  
 24) M2.09: SHOW THE LOCATION OF KEF-1 AND THE EXHAUST
 TERMINATION ON THE PLAN. A) CLARIFY HOW MAKEUP AIR IS
 BEING PROVIDED FOR THE KITCHEN EXHAUST AND PROVIDE AN
 AIR BALANCE CALCULATION. B) PLACE A NOTE INDICATING
 SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST
 AND FIRE SUPPRESSION SYSTEMS. ADVISORY: PLEASE NOTE
 THAT COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE WILL BE REQUIRED. COMPLIANCE WITH THIS
 SECTION MAY IMPACT THE MAIN MECHANICAL PLANS. C) THE
 RESPONSE NARRATIVE TO THE 1ST REVIEW COMMENTS INDICATES
 THAT A ENLARGED KITCHEN DRAWING IS SHOWN ON M3.01,
 HOWEVER THE DRAWING IS NOT ON THE PLAN SHEET.
  
 25) M3.01: PROVIDE THE FLEX DUCT SIZES AND PLACE A
 KEYED NOTE TO IDENTIFY THE ACCESS PANEL LOCATIONS FOR
 THE FC UNITS AND CHANGEOVER BOXES.
  
 26) M4.01: THE DIRECTIONAL ARROWS AT THE TOP OF THE
 TOILET RISERS ARE POINTING IN THE WRONG DIRECTION. A)
 PLEASE INDICATE THE SIZE OF THE MAIN HORIZONTAL DUCT AT
 THE TOP OF THE RISER
  
 27) IN REFERENCE TO COMMENT #37 FROM THE 1ST REVIEW,
 THE DESIGN PROFESSIONAL WILL PROVIDE WIND LOAD DESIGN
 AND STRUCTURAL DETAILS AS DEFERRED SUBMITTALS FOR ALL
 ROOFTOP MECHANICAL EQUIPMENT AND COMPONENT
 INSTALLATIONS. PLEASE SEE SECTION 107.3.4.2 WPB
 AMENDMENTS FOR REQUIREMENTS.
  
 28) ADVISORY: TO HELP EXPEDITE THE PLAN AND FIELD
 INSPECTION APPROVALS, IT IS RECOMMENDED THAT THE DESIGN
 PROFESSIONAL PROVIDE A MASTER LIST OF ALL MECHANICAL
 EQUIPMENT AND COMPONENTS THAT WILL BE DEFERRED
 SUBMITTALS INCLUDING BUT NOT LIMITED TO ROOF STANDS,
 ROOF CURBS, LOUVERS, FIRE AND FIRE/SMOKE DAMPERS, DUCT
 SMOKE DETECTORS, O/A DAMPERS, CO SENSORS, THE FLAMEBAR
 DUCTS, THE BOILER, AND ALL FANS AND DUCTS ASSOCIATED
 WITH THE SMOKE CONTROL SYSTEM AS NOTED IN COMMENT #3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-14 Cont ID  
Sent By ccole Date 2016-07-14 Time 14:59 Rev Time 0.00
Received By ccole Date 2016-07-12 Time 15:11 Sent To  
Notes
2016-07-14 15:00:41REVIEW FBC-14 MECHANICAL
 PERMIT #16061443
 CANOPY HOTEL
 7/12/16
  
 NOTE: UNLESS NOTED OTHERWISE ALL COMMENTS REFERENCE THE
 FLORIDA BUILDING CODE FIFTH EDITION 2014 MECHANICAL.
  
 1) SUBMIT THE FOLLOWING LIST OF SUPPORTING DOCUMENTS
 FOR THE PROPOSED PROJECT:
  
 A) ENERGY CALCULATIONS- SECTION C101.2 & C401.2 FBC-14
 ENERGY CONSERVATION.
 B) SYSTEM COMMISSIONING PLAN- SECTION C408 FBC-14
 ENERGY CONSERVATION.
 C) SMOKE CONTROL SPECIAL INSPECTION AND TEST
 REQUIREMENTS REPORT- SECTION 513.3
 D) SMOKE CONTROL RATIONAL ANALYSIS- SECTION 513.4.
 E) AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION (PLEASE NOTE THAT
 THE CALCULATIONS SUBMITTED DO NOT INCLUDE THESE
 SYSTEMS: OARTU-1, AHU'S 1-12, AND VRV SYSTEMS FC-2.9,
 FC-2.10, FC-3T-H, FC-13.1, & FC-13.2).
 F) AC CALCULATION SUBMITTAL PACKAGE: PLEASE PROVIDE A
 SIGNED AND SEALED INDEX SHEET LISTING ALL UNITS
 CONTAINED IN THE DOCUMENT.
 G) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR ALL EXHAUST OUTLET AND AIR INTAKE LOUVERS, ROOFTOP
 AND SIDEWALL FANS, AC ROOF STANDS AND WALL BRACKETS,
 ROOFTOP AC AND FAN CURBS. ALL SUBMITTALS SHALL BEAR THE
 SHOP DRAWING APPROVAL SIGNATURE BY THE ENGINEER OF
 RECORD.
 H) PRODUCT DATA SUBMITTALS FOR ALL SMOKE CONTROL FANS,
 FIRE AND FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTORS,
 CARBON MONOXIDE DETECTORS, MOTORIZED DAMPERS, FLAMEBAR
 DUCTWORK, REFRIGERANT PIPING INSULATIONS, LAUNDRY
 APPLIANCES, KITCHEN COOKING APPLIANCES, KITCHEN EXHAUST
 HOODS AND FANS, VRV UNITS, AND BOILER AND BOILER VENT
 PIPING. ALL SUBMITTALS SHALL BEAR THE SHOP DRAWING
 APPROVAL STAMP AND SIGNATURES OF THE EOR.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES- TABLE 403.3. PROVIDE ON THE PLAN A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF OUTDOOR AIR FOR ALL ROOMS AND SPACES.
  
 3) PROVIDE EXHAUST VENTILATION CALCULATIONS INCLUDING A
 SCHEDULE ON THE PLAN INDICATING THE REQUIRED AND
 PROVIDED CFMS OF EXHAUST WHERE REQUIRED INCLUDING BUT
 NOT LIMITED TO THE PARKING GARAGES, THE GROUND FLOOR
 AND ROOFTOP KITCHENS, THE GENERATOR ROOM, THE LAUNDRY
 ROOM, SOILED LINEN ROOM, TRASH ROOM, JANITOR'S CLOSETS,
 POOL EQUIPMENT ROOM, LOCKER ROOMS ETC. PLEASE SEE TABLE
 403.3 AND SECTION 404 FBC-14 MECHANICAL, AND TABLE 6-4
 ASHRAE 62.1- 2010. A) THE PLAN INDICATES TOILET EXHAUST
 FROM THE GUEST ROOMS DISCHARGING INTO THE OARTU-1,
 HOWEVER PER TABLE 403.3 FOOTNOTE G, RECIRCULATION IS
 PROHIBITED EXCEPT THAT RECIRCULATION SHALL BE PERMITTED
 WHERE THE RESULTING SUPPLY AIRSTREAM CONSISTS OF NOT
 MORE THAN 10% AIR RECIRCULATED FROM THE TOILET ROOMS.
 PROVIDE CALCULATIONS TO VERIFY COMPLIANCE.
  
 4) PROVIDE AIR BALANCE CALCULATIONS- SECTION 501.4
  
 5) THE SUBMITTED AC CALCULATIONS ARE INCORRECTLY
 INDICATING MIAMI AS THE LOCATION OF THE PROJECT- PLEASE
 CORRECT.
  
 6) WHERE OUTDOOR AIR INTAKES ARE SHOWN ON THE
 MECHANICAL PLANS, PLEASE PROVIDE THE CLEARANCE DISTANCE
 MEASUREMENTS AS INDICATED IN SECTION 401.4. WHERE
 EXHAUST OUTLETS ARE SHOWN ON THE MECHANICAL PLANS
 PLEASE PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS AS
 INDICATED IN SECTION 501.3.1.
  
 7) SHEET M201: ADVISORY- SEPARATE PERMITS ARE REQUIRED
 FOR COMMERCIAL KITCHEN EXHAUST AND FIRE SUPPRESSION
 SYSTEMS, AND WALK-IN COOLERS AND FREEZERS- PLEASE PLACE
 A NOTE IN BOLD LETTERS ON THE PLANS.
  
 8) M201: SEE FIRE PLAN REVIEW COMMENTS CITING NFPA 101
 FOR PROHIBITION OF THE DUCTS SHOWN IN THE FIRE PUMP
 ROOM, AND SECTION 1023.6 FBC-14 BUILDING PROHIBITING
 THE DUCT AND DIFFUSER SHOWN IN THE EXIT PASSAGEWAY OF
 STAIR #1.
  
 9) A722 & M201: IT APPEARS THAT THE LOCATION OF THE
 GREASE EXHAUST TERMINATIONS FOR KEF 1 & 2 SHOWN ON THE
 PLAN BY THE FPL VAULT WOULD NOT MEET COMPLIANCE WITH
 REQUIRED DISCHARGE CLEARANCES AS OUTLINED IN SECTIONS
 506.3.13.2, 506.3.13.3, & 501.3.1 PLEASE PROVIDE
 ADDITIONAL INFORMATION INCLUDING CLEARANCE DISTANCE
 MEASUREMENTS, DETAILS, AND NOTES. PLEASE NOTE THAT KEF
 1, 2, & 3 AND KSF 1 & 2 WILL BE UNDER SEPARATE PERMIT
 WITH THE KITCHEN HOODS, HOWEVER SOME ISSUES MUST BE
 ADDRESSED ON THE MAIN PLANS FOR CONSTRUCTION PURPOSES.
 REVIEW SECTIONS 506, 507, & 508 AND PROVIDE ALL
 APPLICABLE DETAILS AND NOTES ON THE MAIN PLANS.
 ADDITIONALLY, PROVIDE AN INSTALLATION DETAIL FOR
 INSTALLATION OF KEF-1 WHICH IS LISTED AT 2260 LBS. ON
 THE SCHEDULE.
  
 10) M201: PROVIDE THE DUCT TRUNK SIZES FOR THE AC
 SUPPLY AND RETURN SYSTEMS, THE KITCHEN SUPPLY AND
 EXHAUST SYSTEMS, THE RESTROOM AND JANITOR EXHAUST
 SYSTEMS, AND THE O/A AIR SYSTEMS.
  
 11) M201: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF FC-1.3, 1.5, 1.6, 1.7, 1.8-
 SECTION 606.2.1.
  
 12) M201: INDICATE HOW ACCESS FOR MAINTENANCE AND
 REPLACEMENT OF UNITS FC-1.2, 1.3, & 1.4, 1.7, & 1.8
 SHOWN ABOVE DRYWALL CEILINGS ON SHEET A301 WILL BE
 PROVIDED- SECTION 306.1. PLEASE SHOW ACCESS PANEL
 LOCATIONS WHERE REQUIRED AND PROVIDE CONSTRUCTION
 DETAILS.
  
 13) M201: THE RESTROOMS FAN EF-1.1 IS NOT SHOWN IN THE
 SCHEDULE ON M601. PLEASE PROVIDE A SEQUENCE OF
 OPERATION FOR THE FAN- SEE TABLE 403.3
  
 14) M201: PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE
 TRASH ROOM 112 AND THE JANITOR'S CLOSET 118 - TABLE 6-4
 ASHRAE 62.1-2010.
  
 15) M201: CORRIDORS 109 AND 113 SHALL NOT BE USED AS
 RETURN AIR DUCTS FOR AIR BEING SUPPLIED TO ENGINEERING
 110 & DRY STORAGE 124; AND CORRIDOR 133 SHALL NOT
 TRANSFER AIR TO CORRIDOR 129- SEE SECTION 601.2.
  
 16 ) M201: REFER TO SECTION 304 FBC-14 FUEL GAS AND
 PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED
 COOKING APPLIANCES AND EQUIPMENT. INDICATE HOW THE
 COMBUSTION IS BEING SUPPLIED AND SEE SECTION 304.9.3
 FOR COMBUSTION AIR BEING SUPPLIED BY MECHANICAL
 SYSTEMS.
  
 17) M201: AS PREVIOUSLY NOTED, EXHAUST VENTILATION
 CALCULATIONS ARE REQUIRED FOR THE KITCHEN AND
 RECIRCULATION OF AIR FROM THOS SPACE IS PROHIBITED PER
 TABLE 403.3 FOOTNOTE B.
  
 18) M202 & A1.12. : FIRE DAMPERS MISSING AT THESE
 LOCATIONS- THE O/A DUCTS PENETRATING THE LAUNDRY ROOM
 WALLS, AC DUCTS PENETRATING WALLS AT THE LINEN STORAGE
 228, HOUSEKEEPING 229, STORAGE 223, STORAGE 213. PLEASE
 NOTE THERE ARE FIRE DAMPERS AT DUCTS PENETRATING WALLS
 ON THE MECHANICAL PLAN THAT ARE NOT SHOWN AS FIRE-RATED
 WALLS ON THE LIFE SAFETY PLAN.
  
 19) M202: THE LENGTH OF THE DRYER EXHAUST DUCTS ARE
 EXCEEDING THE MAXIMUM ALLOWABLE 35 FT. LENGTH PER
 SECTION 504.6.4.1, AND CAN ONLY BE APPROVED AS SHOWN IF
 THEY CONFORM TO MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AS NOTED IN SECTION 504.6.2. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE DRYERS AND THE IRONER.
 A) INDICATE THE TYPE AND GAGE OF DRYER AND IRONER
 EXHAUST DUCT, AND PROVIDE SUPPORT AND CONNECTION
 DETAILS. B) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 DRYERS PER SECTION 304 FBC-14 FUEL GAS. C) REVISE SHEET
 A401 TO SHOW EXHAUST OUTLET LOCATIONS ON THE ELEVATION
 DRAWING.
  
 20) M202: EXHAUST VENTILATION IS REQUIRED FOR THE
 KITCHEN (WARMING AREA 226) PER TABLE 403.3, AND TABLE
 6-4 ASHRAE 62.1-2010. PLEASE NOTE THAT PER FOOTNOTE B
 RECIRCULATION OF AIR FROM THE KITCHEN IS PROHIBITED.
  
 21) M202: THERE IS A TRANSFER DUCT RETURNING AIR INTO
 CORRIDOR 224, HOWEVER THE CORRIDOR SHALL NOT BE USED AS
 A RETURN AIR DUCT PER SECTION 601.2.
  
 22) M202: INDICATE HOW ACCESS FOR MAINTENANCE AND
 REPLACEMENT OF THE FAN COIL UNITS AND LAUNDRY MAKEUP
 AIR FANS WILL BE PROVIDED- SECTION 306.1. SHOW ACCESS
 PANEL LOCATIONS WHERE REQUIRED AND PROVIDE CONSTRUCTION
 DETAILS.
  
 23) M201 & M202: CLARIFY HOW ACCESS TO FD'S AND FSD'S
 WILL BE PROVIDED WHERE DAMPERS ARE IN CONCEALED
 LOCATIONS ABOVE HARD CEILINGS. SHOW LOCATIONS OF ACCESS
 PANELS AND PROVIDE CONSTRUCTION DETAILS.
  
 24) M202 & M601: PROVIDE AN EQUIPMENT SCHEDULE FOR
 EF-2.1. NOTE: SCHEDULES WILL BE REQUIRED FOR THE
 BOOSTER FANS IF THE UNITS ARE APPROVED FOR USE.
  
 25) M203, M204, M205- PARKING GARAGES: A) AS PREVIOUSLY
 REQUESTED IN THIS REVIEW PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE GARAGES PER TABLE 403.3 AND
 SECTION 404. B) CLARIFY HOW EXHAUST VENTILATION WILL BE
 PROVIDED AND SEQUENCED FOR THE AUTOMOBILE HOISTWAYS AND
 PROVIDE A CALCULATION. THE CURRENT PLAN IS NOT
 PROVIDING ANY HVAC NOTES OR DETAILS- SEE SECTION 404,
 AND SECTION 3004.1 FBC-14 BUILDING. C) PROVIDE MORE
 SPECIFIC INFORMATION FOR THE SEQUENCE OF OPERATIONS
 SHOWN ON M203- SEE SECTION 404.2 AND INDICATE WHICH FAN
 ON EACH FLOOR IS TO RUN AT ALL TIMES AND PROVIDE A
 CALCULATION TO VERIFY THE REQUIRED MINIMUM RATE OF .05
 CFM PER SQUARE FOOT WILL BE ACCOMPLISHED. D) SOME OF
 THE CIRCULATION FANS (CF-1) APPEAR TO BE LOCATED IN
 VEHICLE DRIVE AND PARKING AREAS. INDICATE THE HEIGHT
 FROM THE FINISH FLOOR TO THE BOTTOM OF THE FANS PER
 SECTION 304.6.
  
 26) M203: PLEASE PLACE A NOTE ON THE PLANS INDICATING
 THE EMERGENCY GENERATOR WILL BE DONE UNDER SEPARATE
 PERMIT.
  
 27) M205: AS PREVIOUSLY REQUESTED, SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE FLAMEBAR DUCT
 WITH SHOP DRAWING APPROVAL SIGNATURE BY THE EOR. A)
 PROVIDE A UL TESTED AND APPROVED FIRESTOPPING DETAIL
 FOR WALL AND CEILING PENETRATIONS.
  
 28) M206, M207, M208: FIRE/SMOKE DAMPERS NOT SHOWN FOR
 O/A DUCTS PENETRATING THE CORRIDORS/GUEST ROOM WALLS-
 SEE SECTION 513.5.2 AND 607.5.4.
  
 29) M206, M207, M208: CLARIFY HOW AIR IS BEING RETURNED
 TO EACH FC SHOWN ON THE PLANS- NO RETURN GRILLS ARE
 SHOWN ON THE PLANS.
  
 30) M206, M207, M208: INDICATE HOW ACCESS FOR
 MAINTENANCE AND REPLACEMENT OF THE FAN COIL UNITS WILL
 BE PROVIDED ABOVE THE DRYWALL CEILINGS- SECTION 306.1.
 SHOW ACCESS PANEL LOCATIONS AND PROVIDE CONSTRUCTION
 DETAILS.
  
 31) M208A: THE ACCESS HATCHES SHOWN IN THE STAIRWAY
 ENCLOSURES ARE NOT PERMITTED PER SECTION 1022.4 FBC-14
 BUILDING.
  
 32) M209: PROVIDE EQUIPMENT SCHEDULES FOR FC-13.1 &
 13.2, AND EF-13.1, 13.2, & 13.3.
  
 33) M209: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE COMMERCIAL KITCHEN. THE PLAN INDICATES AIR
 BEING RECIRCULATED IN THE KITCHEN WHICH IS PROHIBITED
 PER TABLE 403.3 FOOTNOTE B.
  
 34) M209: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF FC-13.2. PROVIDE A SYMBOL ON THE
 PLAN AND PROVIDE DETAILS.
  
 35) M209: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE POOL EQUIPMENT ROOM AND COMBUSTION AIR
 CALCULATIONS FOR GAS-FIRED POOL EQUIPMENT- SECTION 304
 FBC-14 FUEL GAS.
  
 36) M210: PROVIDE EXHAUST VENTILATION AND COMBUSTION
 AIR CALCULATIONS FOR THE ROOFTOP BOILER AND PUMP ROOM-
 REFER TO SECTION 304 FBC-14 FUEL GAS, AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR THE BOILERS AND
 BOILER VENTING
  
 37) M2.10: REFER TO SECTION 301.15 AND PROVIDE COMPLETE
 ENGINEERED DETAILS FOR TIE DOWN OF ALL THE ROOF TOP
 MECHANICAL EQUIPMENT INCLUDING BUT NOT LIMITED TO THE
 PRESSURIZATION AND SMOKE EXHAUST FANS AND CURBS, THE
 OARTU AND CURB, THE CU'S, CU ROOF STANDS, THE MD
 WEATHERHOODS, AND EXTERIOR DUCTWORK. PLEASE NOTE THE
 DETAILS ON SHEET M703 ARE INCOMPLETE.
  
 38) PROVIDE A SEQUENCE OF OPERATION FOR THE OARTU-1.
 CLARIFY HOW OUTDOOR AIR WILL BE SUPPLIED TO ALL THE
 VARIOUS FAN COIL UNITS IN THE ROOMS AND COMMON AREAS.
 WILL THE SYSTEMS BE DIGITALLY CONTROLLED? PLEASE REFER
 TO SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 39) REFER TO SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION- DEMAND CONTROLLED VENTILATION IS REQUIRED
 FOR THE RESTAURANT AND THE MEETING ROOMS. INDICATE HOW
 COMPLIANCE WILL BE MET AND PROVIDE DETAILS.
  
 40) M501: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 VRV UNITS WITH ALLOWABLE LENGTH TABLES FOR REFRIGERANT
 PIPING.
  
 41) M801: AS PREVIOUSLY NOTED, A RATIONAL ANALYSIS AND
 CALCULATIONS MUST BE SUBMITTED FOR THE SMOKE CONTROL
 SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2017-10-16 Cont ID  
Sent By lcrespo Date 2017-10-16 Time 16:47 Rev Time 0.00
Received By lcrespo Date 2017-10-16 Time 16:46 Sent To  
Notes
2017-10-16 16:48:1110/16/17, APPROVED BY PLUMBING AND PUT BACK IN "
 C25,26", LAC

Review Stop P PLUMBING
Rev No 4 Status F Date 2017-08-11 Cont ID  
Sent By tklarge Date 2017-08-11 Time 11:36 Rev Time 0.00
Received By tklarge Date 2017-08-02 Time 14:32 Sent To  
Notes
2017-08-02 14:33:281) THE TRENCH DRAIN DETAIL DOES NOT SHOW THAT THIS
 DRAIN IS EQUIPPED WITH A WATER SEAL TRAP. COMPLY WITH
 2014 FBC-PLUMBING SEC. 1002.1.
 2) SUBMIT COMPLETE SPECIFICATIONS / DETAILS FOR THE PCU
 UNIT. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT.P5.06 - THE SAMPLING PORT THAT SHOWS THE DOUBLE
 SANITARY TEE WITH A CAP AT THE BOTTOM IS NOT AN
 ACCEPTED DESIGN BY THE CITY. THE TWO WAY CLEANOUT ON
 THE DISCHARGE SIDE OF THE GREASE INTERCEPTOR CAN BE
 USED AS THE SAMPLING PORT AS LONG AS IT IS A MINIMUM OF
 4 INCHES IN DIAMETER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-03-20 Cont ID  
Sent By tklarge Date 2017-03-20 Time 09:36 Rev Time 0.00
Received By tklarge Date 2017-03-18 Time 05:15 Sent To  
Notes
2017-03-20 06:32:401) SHT. A7.41 - INDICATE ON THE PLANS THAT THE SHOWER
 SEAT IN ALTERNATE ROLL-IN SHOWER IS OF THE FOLDING
 TYPE. 2014 FBC-ACCESSIBILITY SEC.610.3. 2ND REQUEST.
 2) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING
 MACHINES PER 2014 FBC-PLUMBING SEC.1003.6. SUBMIT A
 DETAIL AND SIZING CALCULATIONS FOR THE UNIT. THE
 SUBMITTED RESPONSE NARRATIVE REFERS TO A DETAIL ON SHT.
 P5.01 BUT THERE IS NO DETAIL ON THIS PLAN AND I COULD
 NOT FIND A DETAIL ANYWHERE IN THE PLANS. 2ND REQUEST.
 3) SHT. P4.03 - SANITARY RISER # S/14 - 13TH FLOOR
 TOILET ROOM #1305 BY STAIR # 2 - THE SANITARY RISER
 DOEES NOT COMPLY WITH FBC 2014-PLUMBING SECS. 912 OR
 914 FOR A HORIZONTAL WET VET OR A CIRCUIT VENT. PLACING
 A VENT ON THE FIRST WATER CLOSET CONNECTED TO THE
 HORIZONTAL DRAIN WILLL CORRECT THIS ISSUE. 2ND REQUEST.
 4) SHT. P4.03 - SANITARY RISER S/14 - 7TH FLOOR KING
 SUITE AND FLOORS 8 - 11 - A MAXIMUM OF 4 FIXTURE UNITS
 ARE PERMITTED ON A 2 INCH WET VENT PER 2014
 FBC-PLUMBING SEC.912.3 & TABLE 912.3. THE RISER SHOWS 6
 FIXTURE UNITS ON A WET VENT.
 5) SHTS. P4.04 & P4.05 - WATER RISERS -WATER FILTERS,
 BEVERAGE DISPENSERS, COFFEE MACHINES AND NONCARBONATED
 BEVERAGE DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW
 PERR 2014 FBC-PLUMBING SECS.608.16.1 & 608.16.10. THESE
 APPLIANCES ARE USUALLY UNDER CONTINUOUS PRESSURE AND A
 ATMOSPHERIC VACUUM BREAKER AS CALLED OUT ON THE PLANS
 DOES NOT MEET COMPLIANCE WITH THE NOTED CODE SECTIONS.
 NONCARBONATED & CARBONATED BEVERAGE DISPENSERS, COFFEE
 MACHINES, ETC. SHALL BE PROTECTED AGAINST BACKFLOW BY A
 BACKFLOW PREVENTER CONFORMING TO ASSE 1022.
 6) SHT. P2.01 - # 25 SHOWS A 2 INCH DRAIN FROM A
 "SCRUBBER" TO THE GREASE WASTE AND SHT. P4.01 SHOWS A 1
 INCH DRAIN FROM THE "SCRUBBER"". CLARIFY. SUBMIT
 DETAILS / INFORMATION FOR THE SCRUBBER.
 7) SUBMIT FACTORY SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. 2014 FBC - PLUMBING SEC.1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-12-27 Cont ID  
Sent By tklarge Date 2016-12-27 Time 11:20 Rev Time 0.00
Received By tklarge Date 2016-12-17 Time 05:36 Sent To  
Notes
2016-12-21 10:45:201) SHT.A7.41 - THE ACCESSIBLE SHOWERS APPEAR TO BE OF
 THE ALTERNATE ROLL-IN TYPE.THE SEATS LOCATED IN THE
 HANDICAPPED ACCESSIBLE SHOWERS SHALL COMPLY WITH 2014
 FBC-ACCESS. SECS.610.3. THE SEAT SHALL EXTEND FROM THE
 ADJACENT SIDE WALL TO A POINT WITHIN 3 INCHES OF THE
 COMPARTMENT ENTRY. CLEARLY THE TYPE OF ROLL-IN SHOWER
 ON THE PLAN, STANDARD ROLL-IN TYPE OR ALTERNATE ROLL-IN
 TYPE.
 2) SHT.A7.41 - THE TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 2014 FBC-ACCESS. SEC.604.9.6 ( 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER). 2ND
 REQUEST.
 3) SHT.A7.41 - DETAIL #13 - THE SHOWER SEAT GRAB BAR
 ADJACENT TO THE SEAT SHALL BE A MAXIMUM OF 6 INCHES
 FROM THE BACK WALL PER 2014 FBC-ACCESS. SEC.608.3.3.
 3) A LINT INTERCEPTOR IS REQUIRED PER 2014 FBC-PLUMBING
 SEC.1003.6.SUBMIT A DETAIL AND SIZING CALCULATIONS.SEC
 1003.2. A SCREEN PLACED IN A TROUGH/TRENCH DRAIN DOES
 NOT MEET THE INTENT.
 4) SHT.P2.09 - STAIR # 1 - THERE IS A KEY NOTE #12 NEXT
 TO THE 4 INCH SANITARY LINE DOWN BUT THERE IS NO
 KEYNOTE #12 LISTED. CLARIFY.
 5) SHT. P4.02 - KEYNOTE #1 IS SHOWN AS A 2 INCH VENT AT
 POINT "S" AND ALSO AS A 3 INCH VENT AT POINT
 "B".CLARIFY. IS IT 2 INCH OR 3 INCH?
 6) SHT. P4.02 - THE URINAL IN THE MEN'S RESTROOM IS
 INSTALLED ON A VERTICAL WET VENT WHICH IS NOT PERMITTED
 PER 2014 FBC-PLUMBING SEC. 912.1.1 (SEE DEFINITION OF
 BATHROOM GROUP). THE URINAL SHALL BE INDIVIDUALLY
 VENTED.
 7) SHT.P4.01 - RISER S/2 - POINT "P" - THE VENT FROM
 THE STACK IS SHOWN AS 3 INCH, REDUCES TO 2 INCH AND
 THEN INCREASES TO 3 INCH AT THE CONNECTION TO RISER S/2
 ON SHT.P4.03 - CLARIFY.
 8) SHT. P4.03 - RISER S/14 - 13TH FLOOR TOILET ROOM
 #1305 BY STAIRS #2 - THE SANITARY RISER DOES NOT COMPLY
 WITH 2014 FBC-PLUMBING SECS.912 OR 914 FOR A HORIZONTAL
 WET VENT OR A CIRCUIT VENT.PLACING AN INDIVIDUAL VENT
 ON THE FIRST WATER CLOSET CONNECTED TO THE HORIZONTAL
 DRAIN WILL CORRECT THIS ISSUE.
 9) SHT. P4.03 - 7TH FLOOR KING SUITE - ONLY 4 FIXTURE
 UNITS ARE PERMITTED ON A 2 INCH WET VENT PER 2014
 FBC-PLUMBING SEC.912.3 & TABLE 912.3. SEE FLOORS #7-
 #12.
 10) SHT. P4.06 - WATER RISER #1 - BEVERAGE DISPENSERS,
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER 2014
 FBC-PLUMBING SECS.608.16.1 & 608.16.10. I COULD NOT
 FIND THE NOTE ON THE PLAN. CLARIFY.
 11) SHT. P4.07 - DETAILS "A" &"B" - BOTH WATER RISERS
 INCLUDE "TYPICAL KING ROOM" VERBIAGE - CLARIFY.
 12) SHT. P4.07 - DETAIL "B" - IF THIS WATER RISER IS
 SUPPOSED TO BE THE "KING SUITE" A WATER CLOSET IS
 MISSING FROM THE RISER IN THE HALF BATH AND A LAVATORY
 IS MISSING FROM THE RISER IN THE FULL BATH.
 13) SUBMIT A CCOMPLETE WATER RISER FOR THE LAUNDRY
 ROOM.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 14) PLACE A NOTE ON THE SANITARY DRAWINGS THAT ALL
 FLOOR DRAINS SHALL BE EQUIPPED WITH TRAP PRIMERS. I
 CANNOT FIND THE NOTE AS STATED IN THE NARRATIVE. 2014
 FBC-PLUMBING SEC.1002.4.
 15) THE FUNNEL DRAINS RECEIVING THE DISCHARGE FROM THE
 ELEVATOR SUMPS SHALL BE EQUIPPED WITH TRAP PRIMERS.
 2014 FBC-PLUMBING SEC.1002.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-16 Cont ID  
Sent By tklarge Date 2016-08-16 Time 14:06 Rev Time 0.00
Received By tklarge Date 2016-07-23 Time 06:09 Sent To  
Notes
2016-08-14 08:49:551) CIVIL DRAWING C-10 SHOWS A 1500 GALLON GREASE
 INTERCEPTOR AND PLUMBING SHEET P5.06 CALLS OUT A 1250
 GALLON INTERCEPTOR. CLARIFY.
 2) LANDSCAPE DRAWINGS - SHOW THE SOURCE OF WATER FOR
 THE IRRIGATION SYSTEM AND THE LOCATION OF THE
 IRRIGATION SYSTEM CONTROLLER AND THE RAIN SENSOR. WPB
 AMEND TO FBC SEC. 107.2.1.
 3) SUBMIT THE OCCUPANT LOAD FOR THE DIFFERENT
 OCCUPANCIES (ASSEMBLY- A-2, A-3, BUSINESS, STORAGE,
 ETC.). THIS INFORMATION IS NEEDED TO DETERMINE THE
 MINIMUM REQUIRED SANITARY FACILITIES FOR THE DIFFERENT
 OCCUPANCY GROUPS FOR THE COMMON AREAS PER THE 2014 FPC
 TABLE 403.1.
 4) THE ASSEMBLY AREAS MAY BE REQUIRED TO COMPLY WITH
 THE POTTY PARITY REQUIREMENTS OF THE 2014 FPC SEC.
 403.1.3.
 5) PLACE A NOTE ON THE ARCHITECTURAL PLANS THAT THE
 GENERATOR & FUEL PIPING WILL BE DONE UNDER A SEPARATE
 PERMIT.
 6) SHT. A0.01 NOTES THIS BUILDING IS A 6 STORY MIDRISE
 BUT THE APPLICATION NOTES THAT IT IS A 17 STORY
 BUILDING. IT APPEARS TO BE A 13 STORY BUILDING.
 CLARIFY.
 7) SHT. A2.09 REFERS TO DETAIL 4 ON SHT. A7.41 - THERE
 IS NO DETAIL 4 ON A7.41. CLARIFY.
 8) SHT. A7.41 - DETAIL #13 - SHOWER HEAD LOCATION - A
 FIXED SHOWER HEAD MOUNTED AT 48 INCHES ABOVE THE FINISH
 FLOOR IS NOT PERMITTED IN TRANSIENT LODGING ROOMS PER
 THE 2014 FBC-ACCESS. SEC.608.6 EXCEPTION.
 9) SHT. A7.41 - SEATS LOCATED IN THE HANDICAPPED
 ACCESSIBLE SHOWERS SHALL COMPLY WITH THE 2014
 FBC-ACCESS. SECS. 610.3 & 806.2.4. SUBMIT COMPLETE
 DETAILS FOR THE TYPE OF SEAT (RECTANGULAR OR L-SHAPED,)
 DIMENSIONS FROM WALLS, LOCATION, ETC.
 10) SHT. A7.41 - DETAIL #13 SHOWS THE MAXIMUM HEIGHT
 RANGE FOR THE ACCESSIBLE LAVATORY AS 3 FEET. THE
 MAXIMUM HEIGHT SHALL BE 34 INCHES. 2014 FAC SEC. 606.3.
 11) SHT. A8.01 - SHOW THE WALL FINISH MATERIAL FOR
 ROOMS #130,131,142,210,211,212,621, & 622. COMPLY WITH
 THE 2014 FBC SEC. 1210.
 12) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOWN. FAC
 SEC. 609.4.
 13) SHT. A7.41 - ALTERNATE ROLL-IN SHOWER MEN'S &
 WOMEN'S LOCKER ROOM - THE CONTROLS FOR THE ALTERNATE
 ROLL-IN SHOWER SHALL COMPLY WITH 2014 FAC SECS.
 608.5.3,608.6. THE THRESHOLD SHALL COMPLY WITH 608.7.
 14) SHT. A7.41 - THE DETAILS SHOW ALL THE HANDICAPPED
 WATER CLOSETS AT A HEIGHT OF ONE FOOT THREE INCHES
 ABOVE THE FINISH FLOOR YET DETAIL #3 SHOWS ONE FOOT
 SEVEN INCHES. CLARIFY.
 15) SHT. A7.41 - TOILET PAPER DISPENSERS SHALL BE
 LOCATED IN ACCORDANCE WITH THE FAC SEC.604.9.6.
 16) SHT. A7.41 - DETAIL #6 - THE LENGTH OF THE STANDARD
 TOILET STALLS SHALL COMPLY WITH FBC-PLUMBING SEC.403.
 17) SHT. ID-0.1 ADA GUIDELINES - THE ACCESSIBILITY CODE
 THAT IS IN EFFECT IN FLORIDA IS THE 2014
 FBC-ACCESSIBILITY VOLUME, NOT THE ADA. THE FLORIDA CODE
 IS AN ADA EQUIVALENT CODE AND CERTIFIED BY THE DOJ.
 THESE DETAILS ARE NOT REQUIRED AND MAY CONFLICT WITH
 THE FBC.
 18) SHT.ID-2.40 - DETAIL 03 & SHT.ID-4.30 - SHOWS A
 SINK LOCATED IN THE CORRIDOR. IF AVAILABLE TO THE
 GUESTS THIS SINK SHALL COMPLY WITH FBC-ACCESS. SECS.
 305. 606. MAX. HEIGHT SHALL BE 34 INCHES.
 19) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE ZOELLER
 ALARM FOR THE ELEVATOR SUMP PUMP. WPB AMEND. TO FBC
 SEC. 107.2.1.
 20) SHT. P-2.01 - SHOWS THE FIRE STANDPIPE DRAIN
 DISCHARGING TO THE STORM DRAINAGE SYSTEM. CITY CODE OF
 ORDINANCES ARTICLE V, SEC. 90-203 (A) PROHIBITS THE
 DISCHARGE OF ANYTHING OTHER THAN STORM WATER INTO THE
 STORM DRAINAGE SYSTEM.
 21) LABEL THE GW WATER RISERS ON THE WATER DISTRIBUTION
 ISOMETRICS. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 22) SHT. P4.01 - GREASY WASTE RISER GR/1 SHOWS NO
 CONTINUATION POINT. CLARIFY. SUBMIT A COMPLETE
 RISER/COLLECTION SYSTEM FOR THE GREASE WASTE SYSTEM.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 23) SHT. P4.01 - SHOW THE CONTINUATION POINT FOR THE
 VENT FOR THE HAND SINK IN THE CAFE? (ROOM #134).
 24) INDIVIDUAL VENTS, BRANCH VENTS, CIRCUIT VENTS AND
 RELIEF VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH
 SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE
 ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2014 FPC
 SEC.906.2.
 25) SHT. P2.08 - KEYNOTE #16 - REFERS TO 3 INCH
 SANITARY TO LEVEL 6 AND STATES "SEE P2.06 FOR LAYOUT."
 P2.06 IS FOR THE FOURTH FLOOR. CLARIFY.
 26) SHT. P2.09 - KEYNOTE #6 REFERS TO SHT. P2.01 FOR
 CONTINUATION. THIS LINE IS NOT SHOWN ON P2.01. CLARIFY.
 27) SHT. P2.09 - 3 PD'S (62 SF, 18 SF, 18 SF) & 1 DD
 (1161 SF) AT GRID LINES 7-8 & B-C DO NOT APPEAR TO BE
 ON THE STORM RISER DRAWINGS. CLARIFY.
 28) SHT. P2.12 - KEYNOTE #8 REFERS TO A GAS SOLENOID
 VALVE & SHUTOFF VALVE. THE VALVES SHALL BE LOCATED IN
 THE SAME ROOM AS THE APPLIANCE. 2014 FGC SEC.409.5.1.
 29) SHT. P2.12 -KEYNOTE #11 REFERS TO SHTS.P4.04 &
 P4.06 FOR ENLARGED KITCHEN/BAR PLANS. THERE ARE NO SUCH
 ENLARGED PLANS ON THESE SHEETS. CLARIFY.
 30) SHT. P2.12 - BOTTOM PLAN - KEYNOTE # 3 REFERS TO
 SHTS. P4.04 & P4.06 FOR GREASY WASTE PIPING. THERE IS
 NO GREASY WASTE PIPING ON THESE SHEETS. REVISE NOTE TO
 REFER TO CORRECT PAGE.
 31) SHT. P2.12 - IDENTIFY ALL THE RISERS WITH A RISER
 IDENTIFYING TAG NUMBER. WPB AMEND. TO FBC SEC. 107.2.1.
 32) SHT. P2.13 - BOTTOM PLAN - KEYNOTE # 9 - SHOW THESE
 RISERS ON P2.09 AS NOTED. I CANNOT FIND THESE RISERS ON
 P2.09.CLEARLY IDENTIFY THESE RISERS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 33) SHT. P2.09 SHOWS A SANITARY AND WATER LINE IN
 STAIRWELL #1. THIS IS NOT PERMITTED PER 2014
 FBC-BUILDING SEC. 1009.3.1.5.1.
 34) SHT. P4.01 - THE PLANS SHOW THE WASTE FROM THE
 ELEVATOR SUMPS DISCHARGING INTO THE GREASY WASTE
 SYSTEM. THIS IS NOT PERMITTED. THE ELEVATOR SUMPS ARE
 EQUIPPED WITH ALARMS. THIS DISCHARGE CAN GO TO THE
 SANITARY OR TO A SEPARATE OIL SEPARATOR IF DESIRED. FBC
 1003.3.1.
 35) SHT. P4.01 - RESTROOMS #209 & 210 AND ROOMS #235,
 236, 237 & 238 - THE RISER DOES NOT COMPLY WITH THE
 2014 FPC FOR WET VENTS OR CIRCUIT VENTS.
 36) A LINT INTERCEPTOR IS REQUIRED FOR THE LAUNDRY ROOM
 PER 2014 FPC SEC. 1003.6.
 37) SHTS. P4.01 & P4.02 - CLEARLY IDENTIFY THE
 CONTINUATION POINTS OF ALL VENTS.
 38) SHT. P4.02 - I CANNOT FIND KEYNOTE #1 ON THE PLAN.
 CLARIFY.
 39) SHT. P4.02 - CLARIFY THE DESIGN OF THE FIRST LEVEL
 SANITARY SYSTEM. IT DOES NOT COMPLY WITH THE 2014 FPC
 SEC. 912 FOR WET VENTS OR SEC. 914 FOR CIRCUIT VENTING.
 40) SHT. P4.02 - THE LAYOUT OF THE 5TH FLOOR SANITARY
 DOES NOT CORRELATE WITH THE FLOOR PLAN ON SHT. P2.08. -
 CLARIFY.
 41) SHT.P4.02 - THE 1ST LEVEL RISER SHOWS A PIECE OF
 KITCHEN EQUIPMENT DISCHARGING INTO THE SANITARY. THEY
 SHALL DISCHARGE INDIRECTLY INTO THE GREASE WASTE
 SYSTEM. FPC SEC. 1003.3.1.
 42) SHT. P4.02 - REFERS TO SHT. P5.01 FOR CONTINUATION
 OF SANITARY LINES AND VENTS. THERE ARE NO RISERS ON
 SHT. P5.01. CLARIFY.
 43) SHT. P4.03 - RISER S/2 - KEYNOTE #3 - THE
 REFERENCED VENT IS NOT IDENTIFIED ON SHT. P4.02.
 CLARIFY.
 44) SHT. P4.03 - RISER S/15 - THERE ARE NOT FIXTURES
 SHOWN ON THE STACK AND IT IS INCOMPLETE. PROVIDE THE
 ENTIRE RISER FOR REVIEW.
 45) SHT. P4.03 - RISER S/14 - RESTROOMS BY STAIR #2 -
 THE RISER DOES NOT COMPLY WITH THE FPC SEC. 912 OR SEC.
 914 FOR A HORIZONTAL WET VENT OR A CIRCUIT VENT.
 46) SHT. P4.04 - KEYNOTE #2 REFERS TO SHT. P4.03 FOR
 THE CONTINUATION OF WATER LINES. SHT.P4.03 IS SANITARY
 RISERS. KEYNOTE #2 DOES CORRELATE WITH WHAT IS SHOWN ON
 THE WATER RISER. SEE KEYNOTES #3 & #8 ALSO. CLARIFY.
 47) SHT. P4.05 - KEYNOTE #1 REFERS TO SHT. P4.03A.
 THERE IS NO SUCH SHEET. CLARIFY.
 48) SHT. P4.05 - SIZE ALL SECTIONS OF THE WATER RISER.
 SEE KEYNOTE #1 AND PIPING AT POINTS A & B.
 49) SHEET P4.05 - SHOW THE CONTINUATION POINTS OF THE
 "A" LINE. THE RISER APPEARS TO SHOW TWO LINES TURNED
 DOWN.
 50) SHT. P4.05 - KEYNOTE #5 DOES NOT APPEAR TO
 CORRELATE WITH THE RISER. CLARIFY.
 51) SHT. P4.05 - SHOW THE CONTINUATION POINT OF THE 140
 DEGREE WATER.
 52) SHT. P4.06 - WATER RISER #1 - BEVERAGE DISPENSERS,
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER FPC SECS.
 608.16.1 & 608.16.10.
 53) SUBMIT A WATER RISER FOR THE TYPICAL KING ROOM. THE
 WATER RISER ON P4.07 IS FOR THE KING SUITE. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 54) SHT. P4.07 - DETAIL "C" THE WATER RISER SHOWS 2
 LAVATORIES IN EACH ROOM & SHT. P2.10 AND RISER S/12
 APPEAR TO SHOW ONE LAVATORY IN EACH ROOM. CLARIFY.
 55) SHT. P4.07 - DETAIL 'H" - IDENTIFY THE L/SK & SK ON
 THE WATER RISER. IF THESE ARE IN THE LAUNDRY ROOM
 INCLUDE THE LAUNDRY ROOM NUMBER ON THE DETAIL AND
 SUBMIT A COMPLETE WATER RISER FOR THE LAUNDRY.
 56) ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS. 2014 FPC
 SEC. 1002.4.
 57) SHT. P4.10 - SUPPLY THE TONS OF REFRIGERANT PER
 RISER. THE SIZING OF THE CONDENSATE RISERS SHALL COMPLY
 WITH FPC TABLE 314.2.2.
 58) THE FLOOR DRAINS RECEIVING THE DISCHARGE FROM THE
 ELEVATOR SUMPS SHALL BE EQUIPPED WITH TRAP PRIMERS.
 2014 FPC SEC.1002.4.
  
 NOTE: THE BUILDING CODE REQUIREMENTS FOR THE POOL
 EQUIPMENT ROOM WILL BE REVIEWED WHEN THE POOL PLANS ARE
 SUBMITTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-03-21 Cont ID  
Sent By jwitmer Date 2017-03-21 Time 14:46 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2017-03-21 14:46:16TUES. MARCH 21/ 2017
 COMPLIED. ROOFING PRODUCT APPROVALS:
 MIAMI-DADE NOA 15-1026.10 SEAMAN CORP FIBER TITE SINGLE
 PLY ROOF SYSTEMS OVER CONCRETE DECK PAGE 25 OF 51 -240
 PSF LIMITATION # 9.
 FLORIDA APPROVAL 7989-R1 ATLAS ROOFING INSULATION AC
 FOAM III.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-07-18 Cont ID  
Sent By jwitmer Date 2016-07-18 Time 06:28 Rev Time 0.00
Received By jwitmer Date 2016-07-18 Time 06:28 Sent To  
Notes
2016-07-18 06:31:48ROOFING/ BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061443
 ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-718-5987 / MARGARET LEON
 E-MAIL: MLEONDADLP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JULY 14/2016 - MON. JULY 18/2016
 ACTION: DENIE
  
 1) NO ROOFING PRODUCT APPROVALS WERE SUBMITTED THIS
 REVIEW. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 2) ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY
 EITHER A FLORIDA ARCHITECT OR ENGINEER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2017-10-02 Cont ID  
Sent By shill Date 2017-10-02 Time 08:09 Rev Time 0.00
Received By shill Date 2017-09-29 Time 17:44 Sent To  
Notes
2017-10-02 08:09:42SI ONSITE INSPECTOR MARK PINA, JOSEPH SERVOS
 LAZARO ALFONSO, PE, SI
 BLISS & NYITRAY
 THRESHOLD INSPECTION PLAN ON SHEET S1.02
 VERDEX CONSTRUCTION LLC
  
 ROUTED ORIGINAL TO RECORDS, COPY TO K.CONRAD
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-07-16 Cont ID  
Sent By jwitmer Date 2016-07-16 Time   Rev Time 0.00
Received By jwitmer Date 2016-07-16 Time   Sent To  
Notes
2017-07-27 11:05:22SEE BUILDING REVIEW
  
 SI ONSITE INSPECTOR MARK PINA, JOSEPH SERVOS
 LAZARO ALFONSO, PE, SI
 BLISS & NYITRAY
  
  
  
2016-07-16 14:32:52SEE BUILDING REVIEW NOTES 5.

Review Stop Z ZONING
Rev No 5 Status P Date 2017-10-24 Cont ID  
Sent By aaponte Date 2017-10-24 Time 12:07 Rev Time 0.00
Received By aaponte Date 2017-10-24 Time 12:07 Sent To  
Notes
2017-10-24 12:10:59PROVISO: 1. PEDESTRIAN CROSSING RAMP AT TRINITY AND
 DIXIE SHALL BE REDESIGN FOR A BETTER PEDESTRIAN
 CIRCULATION.
 2. FIRE HYDRANT PROPOSED ON DIXIE SHALL BE MOVED AWAY
 FROM THE PEDESTRIAN PATH OF TRAVEL. IT CAN BE LOCATED 2
 FEET FROM THE BACK OF CURB, ALIGNED WITH TREES.
 3. PLEASE INSTALL LANDSCAPE BASE PLANTING ON EITHER
 SIDE OF THE SERVICE DOOR LOCATED BETWEEN THE FIRE
 CONTROL ROOM AND THE MANAGER'S ROOM.
 4. PLEASE STUDY THE POSSIBILITY OF INSTALLING BASE
 PLANTING ALONG DIXIE HWAY NEXT TO FACADE (MAX WIDTH 3
 FEET), AT GRADE OR IN PLANTERS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439

Review Stop Z ZONING
Rev No 4 Status P Date 2017-08-04 Cont ID  
Sent By aaponte Date 2017-08-04 Time 16:28 Rev Time 0.00
Received By aaponte Date 2017-08-04 Time 16:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2017-04-10 Cont ID  
Sent By aaponte Date 2017-04-10 Time 11:40 Rev Time 0.00
Received By aaponte Date 2017-04-10 Time 11:50 Sent To  
Notes
2017-04-10 11:50:291.COMPLIED- FAR LISTED IN SHEET A1.01 AND GBA LISTED IN
 THE SAME SHEET DO NOT MATCH.
 2. COMPLIED- PLEASE PROVIDE THE FAR DIAGRAMS FOR EACH
 FLOOR INDICATING THE AERAS COUNTED AS FAR AND THE
 SQUARE FOOTAGE.
 3. PLEASE PROVIDE DIAGRAMS TO CONFIRM COMPLIANCE WITH
 THE BLANK WALL AND MINIMUM FENESTRATION REQUIREMENTS
 FOR EACH FACADE. INCLUDE TOTAL AREA OF EACH FACADE,
 AREA OF EACH WINDOW AND PERCETAGE CALCULATION.
 4.PLEASE PROVIDE COLORED ELEVATIONS AND INLCUDE
 PICTURES OF DIFFERENT MATERIALS SPECIFIED FOR THE
 FACADE ALONG WITH THE DETAIL SPECIFICATION. PLEASE
 PROVIDE A BLOW OUT OF FIRST FLOOR FACADE WITH DETAILED
 MATERIALS.
 5. COMPLIED- PLEASE INCLUDE NOTES TO INDICATE CHANGES
 ON PLANE ELEVATION ON EACH FACADE AND THE DIMENSION OF
 SUCH CHANGE.
 6. NOT SATISFIED - PLEASE SHOW THAT THE SIDEWALK
 ELEVATION IS MAINTAINED ACROSS DRIVEWAY, SECTIONS
 PROVIDED SHOWS CROSS SLOPE BUT DO NOT CONFIRM
 THEELEVATION OF THE SIDEWALK IS MAINTAINED- PLEASE
 PROVIDE A SECTION TO CONFIRM THE SIDEWALK ELEVATION IS
 MAINTAINED ACROSS DRIVEWAYS.
 7. NO TRAFFIC MARKINGS SHALL BE PROVIDED ON THE
 SIDEWALK SURFACE.
 8. ALL ABOVE GROUND MECHANICAL EQUIPMENT (BACKFLOW
 PREVENTOR VALVES, TRANSFORMERS ETC) SHALL BE LOCATED
 OUTSIDE THE MINIMUM SETBACK LINE AND SHALL BE SCREENED
 WITH A WALL AND A LANDSCAPE HEDGE.
 9.PLEASE CONFIRM GLASSING IS LIGHT TINTED OR NO TINTED.
 10. PLEASE PROVIDE A GROUND FLOOR EXTERIOR LIGHTING
 PLAN. LIGHT FIXTURES SHALL MATCH ADJACENT FIXTURES ON
 CORRESPONDING SIDE.
 11. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT.
 12. PLESE INDICATE HOW MANY ON-STREET PARKING SPACES
 ARE GOING TO BE REMOVED. A FEE WILL BE ASSESSED FOR
 SUCH REMOVAL.
 13. PLEASE PROVIDE A NARRATIVE ON THE DETAIL
 SPECIFICATION OF THE ROOFTOP MECHANICAL EQUIPMENT TO
 CONFIRM APPLICANT COMMITMENT TO INSTALL THE LOWER NOISE
 LEVEL EQUIPMENT POSSIBLE.
 14. PLEASE INDICATE THE LOCATION OF THE ART ELEMENT TO
 COMPLY WITH THE ART IN PUBLIC PLACES ORDINANCE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 2 Status F Date 2016-12-22 Cont ID  
Sent By aaponte Date 2016-12-22 Time 15:59 Rev Time 0.00
Received By aaponte Date 2016-12-22 Time 15:59 Sent To  
Notes
2016-12-22 16:11:451. FAR LISTED IN SHEET A1.01 AND GBA LISTED IN THE SAME
 SHEET DO NOT MATCH.
 2. PLEASE PROVIDE THE FAR DIAGRAMS FOR EACH FLOOR
 INDICATING THE AERAS COUNTED AS FAR AND THE SQUARE
 FOOTAGE.
 3. PLEASE PROVIDE DIAGRAMS TO CONFIRM COMPLIANCE WITH
 THE BLANK WALL AND MINIMUM FENESTRATION REQUIREMENTS
 FOR EACH FACADE. INCLUDE TOTAL AREA OF EACH FACADE,
 AREA OF EACH WINDOW AND PERCETAGE CALCULATION.
 4.PLEASE PROVIDE COLORED ELEVATIONS AND INLCUDE
 PICTURES OF DIFFERENT MATERIALS SPECIFIED FOR THE
 FACADE ALONG WITH THE DETAIL SPECIFICATION. PLEASE
 PROVIDE A BLOW OUT OF FIRST FLOOR FACADE WITH DETAILED
 MATERIALS.
 5. PLEASE INCLUDE NOTES TO INDICATE CHANGES ON PLANE
 ELEVATION ON EACH FACADE AND THE DIMENSION OF SUCH
 CHANGE.
 6.PLEASE PROVIDE A SECTION TO CONFIRM THE SIDEWALK
 ELEVATION IS MAINTAINED ACROSS DRIVEWAYS.
 7. NO TRAFFIC MARKINGS SHALL BE PROVIDED ON THE
 SIDEWALK SURFACE.
 8. ALL ABOVE GROUND MECHANICAL EQUIPMENT (BACKFLOW
 PREVENTOR VALVES, TRANSFORMERS ETC) SHALL BE LOCATED
 OUTSIDE THE MINIMUM SETBACK LINE AND SHALL BE SCREENED
 WITH A WALL AND A LANDSCAPE HEDGE.
 9.PLEASE CONFIRM GLASSING IS LIGHT TINTED OR NO TINTED.
 10. PLEASE PROVIDE A GROUND FLOOR EXTERIOR LIGHTING
 PLAN. LIGHT FIXTURES SHALL MATCH ADJACENT FIXTURES ON
 CORRESPONDING SIDE.
 11. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT.
 12. PLESE INDICATE HOW MANY ON-STREET PARKING SPACES
 ARE GOING TO BE REMOVED. A FEE WILL BE ASSESSED FOR
 SUCH REMOVAL.
 13. PLEASE PROVIDE A NARRATIVE ON THE DETAIL
 SPECIFICATION OF THE ROOFTOP MECHANICAL EQUIPMENT TO
 CONFIRM APPLICANT COMMITMENT TO INSTALL THE LOWER NOISE
 LEVEL EQUIPMENT POSSIBLE.
 14. PLEASE INDICATE THE LOCATION OF THE ART ELEMENT TO
 COMPLY WITH THE ART IN PUBLIC PLACES ORDINANCE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2016-07-27 Cont ID  
Sent By aaponte Date 2016-07-27 Time 15:59 Rev Time 0.00
Received By aaponte Date 2016-07-27 Time 15:59 Sent To  
Notes
2016-07-27 15:59:32SITE PLAN APPROVAL PROCESS NOT COMPLETED YET.


Account Summary | Usage Policy | Privacy Policy