Plan Review Details - Permit 16061439
Plan Review Stops For Permit 16061439
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-01-11 Cont ID  
Sent By jwitmer Date 2017-01-11 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2017-01-11 Time 08:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-11-05 Cont ID  
Sent By jwitmer Date 2016-11-05 Time 09:45 Rev Time 0.00
Received By jwitmer Date 2016-11-05 Time 09:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-08-05 Cont ID  
Sent By jwitmer Date 2016-08-05 Time 16:44 Rev Time 0.00
Received By jwitmer Date 2016-08-05 Time 13:25 Sent To  
Notes
2016-08-05 16:30:41BUILDING PLAN REVIEW
 W. P. B. REVISION: 16061312
 W. P. B. PERMIT: 15031312
 ADD: 333 FERN ST.
 CONT: KAST CONSTRUCTION
 CONTACT :
 TEL: (561)689-2910
 E-MAIL: [email protected]
  
 1) SHEET 046-A2-5-3 IN STAIRWELL # 4 A 2 HOUR VERTICAL
 EXIT ENCLOSURE. THE 5TH FLOOR REFLECTIVE CEILING PLAN
 INDICATES A DROPPED PORTION OF THE STAIRWELL CEILING
 WITH A 2 HOUR FIRE RATED ENCLOSURE. SHEET 144-A9-4-1
 STAIR DETAIL # 6 ALSO SHOWS THE 2 HOUR SHAFT WALL /
 DROPPED CEILING ASSEMBLY BUT WITH A 2 HOUR FIRE RATED
 ACCESS PANEL. SHEET 148-A10-1 DETAIL 14 SHOWS A BLOW UP
 SECTION OF THE RATED SHAFT WALL/ DROPPED CEILING
 ASSEMBLY.
  
 WHAT THE PLANS DO NOT PROVIDE IS WHAT IS LOCATED ABOVE
 THE 2 HOUR SHAFT WALL ASSEMBLY THAT REQUIRES ACCESS?
 PLEASE REVIEW THE 2010 FBC-B 1022.5 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT
 STAIRWAYS AND RAMPS ARE PROHIBITED EXCEPT FOR REQUIRED
 EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR
 INDEPENDENT VENTILATION OR PRESSURIZATION, SPRINKLER
 PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY
 SERVING THE INTERIOR EXIT STAIRWAY AND RAMP AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT
 STAIRWAYS.
  
 2) PLEASE ALSO REFER TO THE MECHANICAL REVIEW, IN
 REGARDS TO SHEET M2-6-1 SEE CODE SECTION 1104.2
 INDICATE THE TYPE AND AMOUNT OF REFRIGARATION IN THE
 SYSTEMCONTAINED IN THENEW MECHANICAL ROOM. FIRE RATED
 MACHINERY ROOMS MAYBE REQUIRED AND ADDITIONAL
 REQUIREMENTS PER 1104 & 1105 MAYBE APPLICABLE TO THE
 INSTALATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-03-06 Cont ID  
Sent By vperez Date 2017-03-06 Time 07:43 Rev Time 0.00
Received By vperez Date 2017-03-06 Time 07:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-01-06 Cont ID  
Sent By vperez Date 2017-01-06 Time 10:27 Rev Time 0.00
Received By vperez Date 2017-01-06 Time 10:10 Sent To  
Notes
2017-01-06 10:28:51PLEASE HAVE EOR SIGN AND SEAL ELECTRONICALLY ALL
 ELECTRICAL SHEETS FOR AN APPROVAL.
  
 V.PEREZ

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-20 Cont ID  
Sent By malbarra Date 2016-07-20 Time 10:38 Rev Time 0.00
Received By albarran Date 2016-07-19 Time 18:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-07-20 Cont ID  
Sent By wjolin Date 2016-07-20 Time 16:19 Rev Time 0.00
Received By scaldero Date 2016-07-20 Time 16:05 Sent To  
Notes
2016-07-20 16:19:14PERMIT #16061439
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) REVIEW BY ENGINEER OF RECORD AND/OR FIRE ALARM AND
 FIRE SPRINKLER CONTACTORS MAY BE NEEDED TO ENSURE THAT
 CHANGES DO NOT AFFECT PLANS FOR FIRE PROTECTION
 SYSTEMS, AS APPROVED.
  
 2) SUBMIT REVISIONS FOR FIRE PROTECTION SYSTEMS, IF
 NEEDED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-03-10 Cont ID  
Sent By ccole Date 2017-03-10 Time 10:20 Rev Time 0.00
Received By ccole Date 2017-03-02 Time 09:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-01-27 Cont ID  
Sent By ccole Date 2017-01-27 Time 11:03 Rev Time 0.00
Received By ccole Date 2016-12-27 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-11-07 Cont ID  
Sent By cpuell Date 2016-11-07 Time 09:32 Rev Time 0.00
Received By cpuell Date 2016-10-14 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-08-18 Cont ID  
Sent By cpuell Date 2016-08-18 Time 08:42 Rev Time 0.00
Received By cpuell Date 2016-07-18 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-03-10 Cont ID  
Sent By ccole Date 2017-03-10 Time 10:20 Rev Time 0.00
Received By ccole Date 2017-03-09 Time 10:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-01-27 Cont ID  
Sent By ccole Date 2017-01-27 Time 10:45 Rev Time 0.00
Received By ccole Date 2017-01-27 Time 07:08 Sent To  
Notes
2017-01-27 11:02:053RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16061439
 1/27/17
  
 1) THE REVISED PLANS AND ENERGYGAUGE COMPLIANCE FORM
 EACH REQUIRE DIGITAL SIGNATURES.
  
 2) REVISE SHEETS M4.02 & M4.07 IN ACCORDANCE WITH THE
 FAN CHANGES AND PRESSURIZATION METHOD FOR STAIRWELL #2.
  
 3) PROVIDE A SUBMITTAL FOR THE NEW PRESSURIZATION FANS
 SPF-1-1 & SPF 6-1.
  
 4) THE FOLLOWING LIST OF REVISED APARTMENT PLANS APPEAR
 TO SHOW DRYER EXHAUST DUCTS RUNNING THROUGH RETURN AIR
 PLENUMS WHICH IS PROHIBITED PER SECTION 504.4.: SHEETS
 M3-1-1, 3-2-1, 3-3-1, 3-10-1, 3-14-1, & 3-15-1.
  
 5) THE SUBMITTED REVISION NARRATIVE DID NOT COMPLETELY
 LIST ALL THE CHANGES SHOWN IN THE REVISED PLANS. PLEASE
 PROVIDE A COMPLETE NARRATIVE WITH THE RESUBMITTED
 PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-10-26 Cont ID  
Sent By ccole Date 2016-10-26 Time 14:04 Rev Time 0.00
Received By ccole Date 2016-10-26 Time 10:55 Sent To  
Notes
2016-10-26 14:28:502ND REVIEW FBC-2010 MECHANICAL
 PERMIT #16061439
 10/25/16
  
 1) SHEET M-2-6-1: THE EXHAUST FROM EF-2 SHALL DISCHARGE
 TO THE OUTDOORS PER SECTION 501.2 FBC-10 MECHANICAL
 (CORRECTION OF COMMENT #2 FROM THE 1ST REVIEW).
  
 2) M-2-6-1: PLEASE PROVIDE DOCUMENTATION FROM CARRIER
 INDICATING THE EXTERIOR CONDENSER UNITS MAY BE
 INSTALLED INDOORS AND ARE COMPLIANT WITH MANUFACTURER'S
 SPECIFICATIONS.
  
 3) A2.6.2: PLEASE TAG THE WALLS ENCLOSING THE NEW MECH
 RM AND INCLUDE THE WALLS IN THE LEGEND. REFER TO
 SECTION 304.6 EXCEPTION AND VERIFY COMPLIANCE FOR
 VEHICULAR IMPACT PROTECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-26 Cont ID  
Sent By ccole Date 2016-07-26 Time 08:43 Rev Time 0.00
Received By ccole Date 2016-07-26 Time 08:43 Sent To  
Notes
2016-07-26 08:48:331ST REVIEW MECHANICAL
 REVISION #16061439
 MASTER #15031312
 7/16/16
  
 1) SHEETS M2-3-1, 4-1, 5-1, 6-1: INDICATE THE TYPE OF
 DUCTWORK TO BE INSTALLED IN THE GARAGE AND THE
 CLEARANCE HEIGHTS FROM FINISHED FLOOR TO BOTTOM OF THE
 DUCTS. REFER TO SMACNA DUCT CONSTRUCTION STANDARDS-
 2005, AND SECTION 304.6 FBC-14 MECHANICAL.
  
 2) M2-6-1: THE EXHAUST FROM EF-2 SHALL DISCHARGE TO THE
 OUTDOORS- SEE SECTION 501.3 AND REVISE THE PLAN.
  
 3 ) M2-6-1: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR GEF-6-2, PROVIDE A SEQUENCE OF OPERATION FOR THE
 FAN, AND SHOW HOW MAKEUP AIR IS BEING PROVIDED FOR THE
 EXHAUST.
  
 4) M2-6-1: REFER TO SECTION 1104.2 AND INDICATE THE
 TYPE AND AMOUNT OF REFRIGERANT IN THE SYSTEMS CONTAINED
 IN THE NEW MECHANICAL ROOM. PLEASE NOTE A FIRE-RATED
 MACHINERY ROOM MAY BE REQUIRED, AND ADDITIONAL
 REQUIREMENTS PER SECTIONS 1104 AND 1105 MAY BE
 APPLICABLE TO THE INSTALLATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE CONDENSERS- THE UNITS SHALL BE
 INSTALLED IN ACCORDANCE WITH THEIR LISTING OR PER
 MANUFACTURER'S INSTRUCTIONS.
  
 5) M2-6-1 SHOWS THE 8 CONDENSER UNITS TO BE RELOCATED
 ARE CU TYPES 3, 4A, AND 5A, HOWEVER SHEET M2.91 SHOWS
 THE UNIT TYPES RELOCATED WERE CU'S 2 & 3.
  
 6) M2-1-1 & M4.00: THE TRASH ROOM AC HAS BEEN CHANGED
 TO A 1.5 TON SYSTEM, HOWEVER THE AC AND ENERGY
 CALCULATIONS INDICATE A 5TON SYSTEM.
  
 7) M3.1.1: THE 32X6 AND 16X12 RETURN AIR TRANSFERS FROM
 BEDROOM 301.04 ARE UNDERSIZED PER SECTION 601.5
 EXCEPTIONS 2 & 3. A) THE 36X12 TRANSFER AT THE MAIN AC
 PLENUM IS ALSO UNDERSIZED PER 601.5 EXCEPTION 2.
  
 8) M3.2.1: INDICATE HOW THE SUPPLY AIR FOR THE AC-3
 SYSTEMS IS BEING RETURNED TO THE UNITS IN THE CLOSETS-
 SEE SECTION 602.1 FOR PLENUM REQUIREMENTS AND
 LIMITATIONS.
  
 9) M3.3.1: SEE COMMENT #8 ABOVE AS IT PERTAINS TO
 AC-4A.
  
 10) ADVISORY: PLEASE REVIEW THE RETURN AIR SYSTEMS FOR
 THE APARTMENTS SHOWN ON MASTER PLAN SHEETS M3.10.1,
 M3.14.01, M.3.15.1 AND M3.16.1- PERMIT #15031312. IT
 APPEARS THAT SOME OF THE RETURN AIR AND TRANSFER GRILLS
 SHOWN ARE UNDERSIZED PER SECTION 601.5. PLEASE REVIEW
 AND REVISE
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-23 Cont ID  
Sent By gjohnson Date 2017-01-23 Time 12:46 Rev Time 0.00
Received By gjohnson Date 2017-01-23 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-11-02 Cont ID  
Sent By tklarge Date 2016-11-02 Time 12:34 Rev Time 0.00
Received By tklarge Date 2016-11-02 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-08-17 Cont ID  
Sent By tklarge Date 2016-08-06 Time 11:14 Rev Time 0.00
Received By tklarge Date 2016-08-06 Time 04:15 Sent To  
Notes
2016-08-06 05:57:17NARRATIVE:
 1) NUMBER 039 ON NARRATIVE -SHEET A2.3.2 - NARRATIVE
 STATES THAT NEW PLUMBING WAS ADDED IN CORRIDOR 207
 OUTSIDE DINING 302.03. CLARIFY WHAT PLUMBING WAS ADDED
 AND THERE DOES NOT APPEAR TO BE A "CORRIDOR 207" ON THE
 PLAN. CLARIFY.
 2) NUMBERS ON NARRATIVE 045 (A2.5.2), 051 ( A2.7.2),
 054 (A2.8.2), 077 (A6.1.1), 078 (A6.1.2), 080 (A6.2.1),
 083 (A6.3.1), 097 (A6.8.1), 100 ( A6.9.1), 103
 (A6.10.1), 106 (A611.1), 108 (A.6.12.1), 111 (A6.13.1)
 THE NARRATIVE STATES "UNITS MODIFIED PER FHA REVIEW."
 WHAT EXACTLY HAS BEEN MODIFIED IN THESE UNITS. BE
 SPECIFIC.WPB AMEND. TO FBC SEC. 107.2.1.
 3) NUMBER 119 ( A6.16.1) ON NARRRATIVE - NOTES
 "EQUIPMENT ADDED AT COMMON ROOM 701.04". THERE DOES NOT
 APPEAR TO BE ROOM WITH THIS NUMBER ON THE PLAN AND
 SPECIFY WHAT EQUIPMENT WAS ADDED. WPB AMEND. TO FBC
 SEC. 107.2.1.
 4) NUMBERS 122 (A6.17.1) & 124 (A6.18.1) - SPECIFY
 WHATT WAS REVISED ON THE PLANS. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2017-04-04 Cont ID  
Sent By skennedy Date 2017-04-04 Time 15:38 Rev Time 0.00
Received By skennedy Date 2017-04-04 Time 15:38 Sent To  
Notes
2017-03-16 10:54:373/15/17 - GAVE PEDDS TO JWITMER
2017-01-30 10:33:48**APPLICANT WILL BE SUBMITTING PEDDS FOR DIGITAL
 SIGNATURE**

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-01-27 Cont ID  
Sent By ccole Date 2017-01-27 Time 11:05 Rev Time 0.00
Received By ccole Date 2017-01-27 Time 11:05 Sent To  
Notes
2017-01-27 11:05:08THE REVISED MECHANICAL PLANS AND ENERGY CALCULATIONS
 ARE NOT ELECTRONICALLY SIGNED AND SEALED.
 CCOLE/1/27/17
2016-08-05 16:46:271ST REVIEW CYCLE. ARCHITECTURAL & STRUCTURAL SHEETS
 HAVE NOT BEEN ELECTRONICALLY SIGNED AND SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS (ELECTRONIC SEALS).

Review Stop Z ZONING
Rev No 1 Status P Date 2016-08-18 Cont ID  
Sent By aaponte Date 2016-08-18 Time 08:35 Rev Time 0.00
Received By aaponte Date 2016-08-18 Time 08:34 Sent To  
Notes
***NONE***