2016-06-27 16:23:47 | PUT A CALL IN 3:30 PM FOR MICHAEL FOR AN EXPLANATION OF |
| SCOPE. NO ACTIVE VOICE MAIL. AS SUBMITTED PLANS ARE NOT |
| ACCEPTABLE. |
| MADE A SECOND ATTEMPT AT 4:30 AND STILL NO ANSWER. |
| PLANS WERE SENT TO SMALL DENIED BIN "M" UNTIL MICHAEL |
| CALLS BACK. |
| |
| REVIEW FAILED AS NOTED BELOW: |
| 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| 1. SCOPE OF WORK NOT CLEARLY DEFINED ON PLANS. |
| 2. CITY OF WEST PALM BEACH AMENDMENTS SECTION 107.2.1 |
| REQUIRES THAT IN ADDITION TO THE SCOPE OF WORK, ALL |
| PLANS SHALL HAVE THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| 3. IF THESE NEW LIGHTS ARE BEING INSTALLED IN A |
| COMMERCIAL ESTABLISHMENT, LIGHTING CONTROL AS PER THE |
| FBC-E CODE IS REQUIRED. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |
| |
| |
| |