Plan Review Details - Permit 16061435
Plan Review Stops For Permit 16061435
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-07-11 Cont ID  
Sent By skennedy Date 2016-07-11 Time 08:27 Rev Time 0.00
Received By skennedy Date 2016-07-11 Time 08:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By albarran Date 2016-06-27 Time 16:23 Rev Time 0.00
Received By albarran Date 2016-06-27 Time 16:04 Sent To I
Notes
2016-06-27 16:23:47PUT A CALL IN 3:30 PM FOR MICHAEL FOR AN EXPLANATION OF
 SCOPE. NO ACTIVE VOICE MAIL. AS SUBMITTED PLANS ARE NOT
 ACCEPTABLE.
 MADE A SECOND ATTEMPT AT 4:30 AND STILL NO ANSWER.
 PLANS WERE SENT TO SMALL DENIED BIN "M" UNTIL MICHAEL
 CALLS BACK.
  
 REVIEW FAILED AS NOTED BELOW:
 1ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. SCOPE OF WORK NOT CLEARLY DEFINED ON PLANS.
 2. CITY OF WEST PALM BEACH AMENDMENTS SECTION 107.2.1
 REQUIRES THAT IN ADDITION TO THE SCOPE OF WORK, ALL
 PLANS SHALL HAVE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 3. IF THESE NEW LIGHTS ARE BEING INSTALLED IN A
 COMMERCIAL ESTABLISHMENT, LIGHTING CONTROL AS PER THE
 FBC-E CODE IS REQUIRED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-27 Cont ID  
Sent By albarran Date 2016-06-27 Time 16:24 Rev Time 0.00
Received By albarran Date 2016-06-27 Time 09:57 Sent To  
Notes
2016-06-27 16:26:416/27/16 MULTIPLE UNSUCCESSFUL ATTEMPTS WERE MADE TO
 CONTACT MICHAEL SO I HAD TO FAIL THE REVIEW AS NOTED ON
 THE ELECTRICAL REVIEW NOTES. SENT AN EMAIL TO THE EMAIL
 ADDRESS ON THE PERMIT APPLICATION. FILE SENT TO SMALL
 DENIED BIN "M". MA
2016-06-27 09:57:19ELEC <5K