Plan Review Details - Permit 16061352
Plan Review Stops For Permit 16061352
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-09-21 Cont ID  
Sent By jwitmer Date 2016-09-21 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2016-09-21 Time 13:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-08-20 Cont ID  
Sent By jwitmer Date 2016-08-20 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2016-08-20 Time 09:30 Sent To  
Notes
2016-08-20 10:22:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061352
 ADD: 1905 S. DIXIE HWY. SUITE # 100A & 100B
 CONT: SISCA
 TEL: 561-228-7503
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 08/2016
 ACTION: DENIED
  
 1) COMPLIED.
  
  
 2) SHEET A-1.0:
  
 2A ) COMPLIED.
  
 2B)2ND REQUEST. CODE RESEARCH INDICATES THE TENANT
 SPACES TO BE MERCANTILE OCCUPANCIES. UNDER THE HEADING
 OF MEANS OF EGRESS THERE ARE (2) DISCREPANCIES, (1) THE
 OCCUPANCY TYPE IS LISTED AS BUSINESS, THE (2) ISSUE IS
 OCCUPANT LOAD IS FIGURED AT 60 SQ. FT. / OCCUPANT
 PLEASE REVIEW THE 2014 FBC-B TABLE 1004.1.2 WHERE
 EITHER AT BASEMENT OR GRADE FLOOR LEVEL THE OCCUPANT
 LOAD IS TAKEN AT 30 SQ. FT./ OCCUPANT.
  
 3) SHEET A-2.0:
 3A) COMPLIED. PLEASE REVIEW THE ALLOWABLE CENTERS FOR
 AN ACCESSIBLE WATER CLOSET IN THE 2014
 FBC-ACCESSIBILITY CODE THE WATER CLOSET IS TO BE
 LOCATED BETWEEN 16 INCHES TO 18 INCHES FROM THE SIDE
 WALL. SEE ACCESS. CODE 604.2. THE OTHER ISSUE THE PLANS
 DO NOT SHOW AN OVER ALL MEASUREMENT OF THE RESTROOMSTHE
 MINIMUM MEASUREMENT WOULD BE 7 FEET 1 INCH. THE PLANS
 CENTER THE WATER CLOSET AT 16 3/4 INCHES OFF THE WALL
 AND THE LAV IS CENTERED AT 15 3/4 INCHES OFF THE
 OPPOSITE SIDE WALL. THE "CLEARANCES" FROM THE SIDE WALL
 OVER THE WATER CLOSET TO THE CLOSET EDGE OF THE LAV IS
 60 INCHES, THE CENTERLINE DISTANCE OFF THE WALL FOR THE
 LAV AT 15 3/4 INCHES WILL INCREASE THE OVERALL DISTANCE
 OR THE ROOM BY 3/4 INCHES.
  
 3B) COMPLIED. THE DETAILS FOR THE GRAB BARS ALL SHOW
 THE DISTANCE 36 INCHES FROM THE FINISH FLOOR TO
 CENTERLINE, PLEASE NOTE THE 2014 FBC-ACCESSIBILITY CODE
 SECTION 609.4 REQUIRES THE MEASUREMENT TO BE TAKEN FROM
 THE TOP OF THE GRIPPING SURFACE.
  
 3C) 2ND REQUEST. THE RESPONSE INDICATES THERE IS AN
 ATTACHMENT INDICATING THE ANCHOR TYPE WINGITS GBW40 TO
 BE INCLUDED IN THIS SUBMITTAL. PLEASE NOTE NO SUCH
 SUBMITTAL IN THIS SUBMITTAL PACKAGE.
 1ST ROUND COMMENT. THERE ARE NO DETAILS SHOWN HOW CODE
 COMPLIANCE FOR BACKING FOR GRAB BARS. 2014 FBC-ACCESS.
 CODE 609.8 STRUCTURAL STRENGTH.
  
 3D) 2ND REQUEST. NOT FOUND. THE PLANS DO NOT SHOW
 ACCESSIBLE SGINAGE. SHOW COMPLIANCE WITH ACCESS. CODE
 703.1 GENERAL.
 SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL AND
 TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH
 BOTH VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE
 SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
  
 703.2 RAISED CHARACTERS.
 RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE
 DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED
 CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH 703.4.
  
 3E) SEMI COMPLIED. ONE SUBMITTAL PACKAGE SHOWS THE
 PBS45 PUSHPLATE & A STANLEY ACCESS TECHNOLOGIES
 BROCHURE. THE ARCHITECTURAL PLANS DO NOT INDICATE WHERE
 THE PUSH BOTTON IS TO BE LOCATED TO ACTIVATE THE
 ACCESSIBLE DOOR SYSTEM, NOR DOES THE ELECTRICAL PLAN.
 IT APPEARS THERE IS GLASS WINDOWS AND MULLIONS
 SURROUNDING THE FRONT ENTRY DOORS. THE ELECTRICAL PLANS
 DO INDICATE A JUNCTION BOX FOR THE STANLEY ELECTRIC
 OPERATOR.
  
 THE PLANS DO NOT INDICATE IF THE 2 MEANS OF EGRESS ARE
 ACCESSIBLE MEANS OF EGRESS. 2014 FBC-ACCESSIBILITY CODE
 207.1 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH THE
 2003 IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 OR
 MORE MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR
 1018.1 FROM ANY ACCESSIBLE PORTION OF THE SPACE SHALL
 BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS OF
 EGRESS.
  
 3F)2ND REQUEST. THE RESPONSE INCLUDES THE 20 %
 DISPROPORTIONATE COST, NOT A SEPARATE LETTER GIVING THE
 BREAK OUT OF THE COST OF THE FUNDS SPENT. THIS LETTER
 CAN BE ON EITHER THE CONTRACTORS LETTER HEAD OR THE
 DESIGNER OF RECORD. PLEASE PROVIDE A LETTER SHOWING A
 ITEMIZED LIST OF ELEMNTS WHERE UP TO 20% OF THE
 CONTRACT VALUE HAS BROUGHT THESE ELEMENTS UP TO MEET
 THE CURRENT 2014 ACCESSIBLITY CODE. 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4)NEW COMMENT.PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 PLEASE NOTE THIS CAN BE A DEFERRED SUBMITTAL IF EITHER
 OF THE CONTACTOR OR DESIGNEER OF RECORD WISHES. A
 WRITTEN RESPONSE IS ALL THAT WOULD BE REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-08 Cont ID  
Sent By jwitmer Date 2016-07-08 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2016-07-08 Time 05:44 Sent To  
Notes
2016-07-08 06:58:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061352
 ADD: 1905 S. DIXIE HWY. SUITE # ???????
 CONT: SISCA
 TEL: 561-228-7503
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 08/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION DOES NOT INCLUDE THE SUITES
 TO BE INCLUDED IN THE SCOPE OF WORK TO BE COVERED UNDER
 THIS PERMIT. THE TITLE BLOCK ALSO JUST SAYS 1905 S.
 DIXIE HWY. IT WOULD APPEAR THE SCOPE OF WORK TO BE
 COVERED UNDER THIS PERMIT IS BOTH SUITES 100A & 100B?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENTCLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED.
  
 2) SHEET A-1.0:
 2A) CODE RESEACH OCCUPANCY CLASSIFICATION IS INDICATED
 AS MERCANTILE BUT ALSO LIST NON-SEPARATED USE. IS THERE
 ANOTHER OCCUPANCY TYPE NOT DECLARED WHERE NON-SEPARATED
 USE COMES INTO PLAY IN A MIXED USE BUILDING ? 2014
 FBC-B 508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR
 PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS
 OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED
 OCCUPANCIES.
  
 2B) CODE RESEARCH INDICATES THE TENANT SPACES TO BE
 MERCANTILE OCCUPANCIES. UNDER THE HEADING OF MEANS OF
 EGRESS THERE ARE (2) DISCREPANCIES, (1) THE OCCUPANCY
 TYPE IS LISTED AS BUSINESS AND THE OCCUPANT LOAD IS
 TAKEN AT 100 SQ. FT/ OCCUPANT, THE (2) ISSUE IS
 OCCUPANT LOAD IS FIGURED AT 60 SQ. FT. / OCCUPANT
 PLEASE REVIEW THE 2014 FBC-B TABLE 1004.1.2 WHERE
 EITHER AT BASEMENT OR GRADE FLOOR LEVEL THE OCCUPANT
 LOAD IS TAKEN AT 30 SQ. FT./ OCCUPANT.
  
 3) SHEET A-2.0:
 3A) PLEASE REVIEW THE ALLOWABLE CENTERS FOR AN
 ACCESSIBLE WATER CLOSET IN THE 2014 FBC-ACCESSIBILITY
 CODE THE WATER CLOSET IS TO BE LOCATED BETWEEN 16
 INCHES TO 18 INCHES FROM THE SIDE WALL. SEE ACCESS.
 CODE 604.2. THE OTHER ISSUE THE PLANS DO NOT SHOW AN
 OVER ALL MEASUREMENT OF THE RESTROOMSTHE MINIMUM
 MEASUREMENT WOULD BE 7 FEET 1 INCH. THE PLANS CENTER
 THE WATER CLOSET AT 16 3/4 INCHES OFF THE WALL AND THE
 LAV IS CENTERED AT 15 3/4 INCHES OFF THE OPPOSITE SIDE
 WALL. THE "CLEARANCES" FROM THE SIDE WALL OVER THE
 WATER CLOSET TO THE CLOSET EDGE OF THE LAV IS 60
 INCHES, THE CENTERLINE DISTANCE OFF THE WALL FOR THE
 LAV AT 15 3/4 INCHES WILL INCREASE THE OVERALL DISTANCE
 OR THE ROOM BY 3/4 INCHES.
  
 3B) THE DETAILS FOR THE GRAB BARS ALL SHOW THE DISTANCE
 36 INCHES FROM THE FINISH FLOOR TO CENTERLINE, PLEASE
 NOTE THE 2014 FBC-ACCESSIBILITY CODE SECTION 609.4
 REQUIRES THE MEASUREMENT TO BE TAKEN FROM THE TOP OF
 THE GRIPPING SURFACE.
  
 3C) THERE ARE NO DETAILS SHOWN HOW CODE COMPLIANCE FOR
 BACKING FOR GRAB BARS. 2014 FBC-ACCESS. CODE 609.8
 STRUCTURAL STRENGTH.
  
 3D) THE PLANS DO NOT SHOW ACCESSIBLE SGINAGE. SHOW
 COMPLIANCE WITH ACCESS. CODE 703.1 GENERAL.
 SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL AND
 TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH
 BOTH VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE
 SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE
 CHARACTERS, SHALL BE PROVIDED.
  
 703.2 RAISED CHARACTERS.
 RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE
 DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED
 CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH 703.4.
  
 3E) THE PLANS DO NOT INDICATE IF THE 2 MEANS OF EGRESS
 ARE ACCESSIBLE MEANS OF EGRESS. 2014 FBC-ACCESSIBILITY
 CODE 207.1 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH
 THE 2003 IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2
 OR MORE MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1
 OR 1018.1 FROM ANY ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS
 OF EGRESS.
  
 3F) PLEASE PROVIDE A LETTER SHOWING A ITEMIZED LIST OF
 ELEMNTS WHERE UP TO 20% OF THE CONTRACT VALUE HAS
 BROUGHT THESE ELEMENTS UP TO MEET THE CURRENT 2014
 ACCESSIBLITY CODE. 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-09-14 Cont ID  
Sent By vperez Date 2016-09-14 Time 09:22 Rev Time 0.00
Received By vperez Date 2016-09-14 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-08-24 Cont ID  
Sent By vperez Date 2016-08-24 Time 14:19 Rev Time 0.00
Received By vperez Date 2016-08-24 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-07-14 Cont ID  
Sent By vperez Date 2016-07-14 Time 07:31 Rev Time 0.00
Received By vperez Date 2016-07-14 Time 07:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-08-29 Cont ID  
Sent By fstal Date 2016-08-29 Time 16:28 Rev Time 0.00
Received By fstal Date   Time   Sent To B
Notes
2016-08-29 16:29:18NFPA 1-1.14.5: FIRE PROTECTION CONTRACTORS SHALL SUBMIT
 SHOP DRAWINGS FOR REVIEW AND APPROVAL.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-06-28 Cont ID  
Sent By fstal Date 2016-06-28 Time 16:47 Rev Time  
Received By fstal Date   Time   Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-21 Cont ID  
Sent By   Date 2016-09-21 Time   Rev Time 0.00
Received By lmarchan Date 2016-09-08 Time 15:54 Sent To  
Notes
2016-09-09 15:54:37B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-09-01 Cont ID  
Sent By gjohnson Date 2016-09-01 Time 09:49 Rev Time 0.00
Received By gjohnson Date 2016-08-15 Time 10:23 Sent To  
Notes
2016-08-16 10:23:40B12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-25 Cont ID  
Sent By gjohnson Date 2016-07-25 Time 14:07 Rev Time 0.00
Received By gjohnson Date 2016-06-23 Time 13:15 Sent To  
Notes
2016-06-24 13:15:26B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-07-25 Cont ID  
Sent By gjohnson Date 2016-07-25 Time 14:10 Rev Time 0.00
Received By gjohnson Date 2016-07-08 Time 05:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-08-23 Cont ID  
Sent By ccole Date 2016-08-23 Time 17:45 Rev Time 0.00
Received By ccole Date 2016-08-23 Time 17:24 Sent To  
Notes
2016-08-23 17:48:00MECHANICAL PROVISO:
  
 1) M6.1 PLAN SHEET IS MISSING FROM ONE OF THE APPROVED
 SETS: PLEASE INSERT AT PERMIT PICKUP.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-05 Cont ID  
Sent By ccole Date 2016-07-05 Time 07:28 Rev Time 0.00
Received By ccole Date 2016-07-05 Time 07:28 Sent To  
Notes
2016-07-05 07:48:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061353
 7/5/16
  
 1) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF AC SYSTEMS 1 & 2- SECTION
 606.2.1. PLEASE NOTE THAT MANUFACTURER'S SPECIFICATIONS
 TYPICALLY INDICATE THAT 5-TON SYSTEMS HAVE CAPACITIES
 EXCEEDING 2000 CFMS.
  
 2) M1.1: PROVIDE THE CLEARANCE DISTANCES FOR THE O/A
 INTAKES AS REQUIRED BY SECTION 401.4, ITEMS 1-4.
  
 3) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE EXTERIOR CONDENSERS, AND COMPLETE
 DETAILS FOR ANCHORING THE UNITS TO THE CONCRETE PADS-
 LENGTH OF THE 1/4" BOLT, AND TYPE AND SIZE OF CLIP
 FASTENERS- SECTION 301.15.
  
 4) A-1.1 & M0.1: DOORS A101 & B101 MUST BE
 NON-COMBUSTIBLE- SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-09-20 Cont ID  
Sent By gjohnson Date 2016-09-20 Time 13:29 Rev Time 0.00
Received By gjohnson Date 2016-09-20 Time 13:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-09-01 Cont ID  
Sent By gjohnson Date 2016-09-01 Time 09:23 Rev Time 0.00
Received By gjohnson Date 2016-09-01 Time 09:22 Sent To  
Notes
2016-09-01 09:47:37 
 2ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHT A-1.0 CODE RESEARCH INDICATES THE TENANT SPACES
 TO BE MERCANTILE OCCUPANCIES. UNDER THE HEADING OF
 MEANS OF EGRESS THERE ARE (2) DISCREPANCIES, (1) THE
 OCCUPANCY TYPE IS LISTED AS BUSINESS, THE (2) ISSUE IS
 OCCUPANT LOAD IS FIGURED AT 60 SQ. FT. / OCCUPANT
 PLEASE REVIEW THE 2014 FBC-B TABLE 1004.1.2 WHERE
 EITHER AT BASEMENT OR GRADE FLOOR LEVEL THE OCCUPANT
 LOAD IS TAKEN AT 30 SQ. FT./ OCCUPANT. CLARIFICATION OF
 THIS AFFECTS THE NUMBER OF BATHROOMS REQUIRED. IF IT IS
 A MERCANTILE ONLY 1 IS REQUIRED BUT IF IT IS BUSINESS
 SEPARATE FACILITIES ARE REQUIRED FOR MEN AND WOMEN
 WHICH IS 2 BATHROOMS PER UNIT. 2014 FBC PL SEC 403.2
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-07-25 Cont ID  
Sent By gjohnson Date 2016-07-25 Time 13:30 Rev Time 0.00
Received By gjohnson Date 2016-07-25 Time 13:30 Sent To  
Notes
2016-07-25 14:05:121ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING CONTACTS:
  
 1. WATER CLOSET DIMENSION OF THE SIDE WALL IS SHOWN AS
 183/4IN IT SHALL BE MIN. 16. MAX 18IN. PER FBC ACC SEC
 604.2
 2. SHOW OVERALL DIMENSION OF BATHROOM SHALL COMPLY WITH
 FBC ACC. 604.3.1 AND 604.8.1.6
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
 PER FBC ACC 604.7
 4. GRAB BARS SHALL COMPLY WITH FBC ACC
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,