Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2018-07-03 Cont ID  
Sent By jgomez Date 2018-07-03 Time 09:25 Rev Time 0.00
Received By jgomez Date 2018-07-03 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2018-06-05 Cont ID  
Sent By jgomez Date 2018-06-05 Time 15:05 Rev Time 0.00
Received By jgomez Date 2018-06-05 Time 14:50 Sent To  
Notes
2018-06-05 15:21:37RESIDENTIAL (R3) REVISION, 8TH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ORIGINAL COMMENT:
 1- GAF FLAT ROOF NOA 13-1022.15 SPECIFIED ON DRAWING
 S-2 AND SELECTED INSULATED ASSEMBLY ON PAGE 6 OF 16:
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 AT PERIMETER AND CORNER AREAS.
 FBC-RESIDENTIAL 2010.
 NOTE: SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED FOR RAS 117 CALCULATIONS REQUIREMENTS.
  
 RESPONSE:
 A) INFORMATION IN RAS 117 CALCULATIONS SUBMITTED DON'T
 MATCH ENGINEER OF RECORD DRAWINGS SUBMITTED UNDER
 REVISION #16061282. ENGINEER SELECTED ASSEMBLY WITH THE
 MAXIMUM DESIGN PRESSURES OF -52.5 . ENGINEER DOING THE
 RAS 117 CALCULATIONS IS USING ASSEMBLY WITH A MAXIMUM
 DESIGN PRESSURE OF -45PSF. IN ADDITION, THE FASTENER
 USED FOR THE ASSEMBLY WITH A MAXIMUM DESIGN PRESSURE OF
 -45PSF IS DIFFERENT THAN THE ONE SPECIFIED BY THE
 ENGINEER DOING THE RAS 117 CALCULATIONS. FASTENERS ON
 THE APPROVED ASSEMBLIES CAN NOT BE INTERCHANGED. REVISE
 AS REQUIRED TO MATCH. COORDINATE ALL THE INFORMATION TO
 AVOID MORE CONFLICTS AND UN-NECESSARY DELAYS. SEC.
 R301.1 FBC-RESIDENTIAL 2010.
  
 B) THIS PROJECT WAS REVIEWED UNDER THE 2010 FBC
 RESIDENTIAL NOT 2017. REVISE AS REQUIRED. CHAPTER 553
 F.S.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2018-03-08 Cont ID  
Sent By jgomez Date 2018-03-08 Time 11:56 Rev Time 0.00
Received By jgomez Date 2018-03-08 Time 11:36 Sent To  
Notes
2018-03-08 11:43:18RESIDENTIAL (R3) REVISION, 7TH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- GAF FLAT ROOF NOA 13-1022.15 SPECIFIED ON DRAWING
 S-2 AND SELECTED INSULATED ASSEMBLY ON PAGE 6 OF 16:
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 AT PERIMETER AND CORNER AREAS.
 FBC-RESIDENTIAL 2010.
 NOTE: SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED FOR RAS 117 CALCULATIONS REQUIREMENTS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2017-11-02 Cont ID  
Sent By jgomez Date 2017-11-02 Time 10:03 Rev Time 0.00
Received By jgomez Date 2017-11-01 Time 18:12 Sent To  
Notes
2017-11-01 18:13:29 
 RESIDENTIAL (R3) REVISION, SIXTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE:
 CONTRACTOR OWES $154.50 FOR PREVIOUS REVISION FEES. NO
 MORE REVIEWS WILL BE DONE UNTIL THESE FEES ARE PAID.
 FEES FOR CURRENT SUBMITTAL WILL BE ASSESSED ONCE LATEST
 SUBMITTAL IS CLARIFIED.
  
  
 1- NO CLEAR WHAT THE CONTRACTOR IS DOING. CONTRACTOR TO
 CLARIFY WHY LATEST DRAWINGS S-2 AND S-3 THAT WERE
 SIGNED BY ENGINEER OF RECORD ON 08/10/17 WERE VOIDED.
 WHY SUBMITTING OLD DRAWINGS THAT WERE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD ON 06/29/16. NO SURE WHAT ARE
 THE REVISIONS FOR THIS JOB. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- NONE OF THE COMMENTS FROM PREVIOUS CHECKLIST WERE
 ADDRESSED. NO CLEAR WHAT THE CONTRACTOR IS DOING. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- I WANT TO REQUEST A MEETING WITH THE CONTRACTOR AND
 MY SUPERVISOR TO GET THIS JOB BACK IN TRACK.
  
  
 NOTE:
 BELOW IS THE COPY OF PREVIOUS CHECKLIST. NOTHING WAS
 ADDRESSED:
  
 1- FLAT ROOF FL11946-R7 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL
 FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE
 STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON
 DETAILS ON SHEET S-3.
 SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS.
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15
 AND NOT INFORMATION WAS PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2017-08-16 Cont ID  
Sent By jgomez Date 2017-08-16 Time 13:58 Rev Time 0.00
Received By jgomez Date 2017-08-16 Time 12:16 Sent To  
Notes
2017-08-16 12:34:30RESIDENTIAL (R3) REVISION, FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ****NOTE:
 REVISION FEES WERE ADDED FOR THE THREE DRAWINGS
 SUBMITTED (S1, S2 AND S3 SIGNED AND SEALED BY THE
 ENGINEER ON 08/10/17). CONTRACTOR OWES $154.50 FOR
 REVISION FEES.
  
  
 1- FLAT ROOF FL11946-R7 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL
 FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE
 STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON
 DETAILS ON SHEET S-3.
 SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS.
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15
 AND NOT INFORMATION WAS PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-02-10 Cont ID  
Sent By jgomez Date 2017-02-10 Time 14:01 Rev Time 0.00
Received By jgomez Date 2017-02-10 Time 10:14 Sent To  
Notes
2017-02-10 10:16:59RESIDENTIAL (R3) REVISION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLAT ROOF FL11946-R7 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL
 FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE
 STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON
 DETAILS ON SHEET S-3.
 SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS.
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15
 AND NOT INFORMATION WAS PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-07-25 Cont ID  
Sent By jgomez Date 2016-07-25 Time 15:13 Rev Time 0.00
Received By jgomez Date 2016-07-25 Time 15:12 Sent To  
Notes
2016-07-25 15:15:28RESIDENTIAL (R3) REVISION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE:
 07/25/16 TALKED TO WARREN VON WERNE (ENGINEER OF
 RECORD) TO GO OVER COMMENTS. IT LOOKS LIKE MR. VON
 WERNE DIDN'T GET MY SECOND REVIEW COMMENTS. I AM
 E-MAILING THE COMMENTS BELOW TO MR. VON WERNE. THE
 COMMENTS BELOW ARE A COPY OF THE SECOND REVIEW, SINCE
 THE RE-SUBMITTAL PACKAGE DOESN'T ADDRESS THOSE
 COMMENTS:
  
 ORIGINAL COMMENT:
 1- ORIGINAL APPROVED PLANS DON'T INCLUDE FLAT ROOF
 SYSTEMS. ENGINEER OF RECORD NEEDS TO REVISE PLANS
 SPECIFYING THE PROPOSED FLAT ROOF.
 PROVIDE TWO SIGNED AND SEALED DRAWINGS SHOWING THE
 REVISION. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 RESPONSE:
 A) REVISED DRAWING S-2 SPECIFIES "MODIFIED BITUMEN
 ROOFING OVER 3/4" PLYWOOD SHEATHING (PER NOA
 #13-1022.15, 13-0416.05, AND #12-1219.02)". IT IS NOT
 CLEAR WHAT IS GOING TO BE THE FINISH ROOF MATERIAL.
 SPECIFIED NOA'S ARE FOR THREE DIFFERENT TYPES OF
 ASSEMBLIES BY DIFFERENT MANUFACTURER'S. NEED TO PROVIDE
 THE FOLLOWING:
 (1)IDENTIFY WHICH NOA IS GOING TO BE USED IN THIS ROOF
 DECK, THEN PROVIDE COMPLETE NOA (2 COPIES).
 (2) IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 USED.
 (3) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA. (NOTE: ASSEMBLIES WITH GENERAL LIMITATION
 #9 CAN NOT BE USED BECAUSE THEY DON'T ALLOW RAS 117
 CALCULATIONS).
  
  
 ORIGINAL COMMENT:
 2- FLAT ROOF NOA 11-0601.10 SUBMITTED IS NOT DESIGNED
 FOR FLAT ROOF. THIS NOA IS AN UNDERLAYMENT FOR PITCHED.
 ROOFS. REVISE AS REQUIRED.
 (A) PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF
 SYSTEM THAT IS DESIGNED FOR THE ROOF DECK FINISH AS
 SPECIFIED ON PLANS.
 FAC 61G20-3.002(33).
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
 (B) CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE USED FROM
 THE PRODUCT APPROVAL RE-SUBMITTED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
  
 (C) IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES, THEN SIGNED AND SEALED RAS
 117 CALCULATIONS ARE REQUIRED. SEE PRODUCT APPROVAL
 SUBMITTED. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
  
 (D) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) FLAT ROOF PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
 ORIGINAL COMMENT:
 3- THIS FLAT ROOF SYSTEM WAS NOT PART OF THE APPROVED
 PLANS. SPECIFY THE ADDITIONAL VALUE FOR THE NEW FLAT
 ROOF AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
 RESPONSE:
 THERE ARE MORE REVISION SHOWN ON SHEET S-2. REVISED
 PLAN SHOW NEW W12X22 STEEL BEAMS INSTEAD OF GLU LAM
 BEAMS. SPECIFY THE ADDITIONAL VALUE BASED ON THE
 PROPOSED REVISIONS. INCLUDE THE ENGINEER'S DESIGN FEES
 AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS
  
 NEW COMMENT:
 4- PATIO FRAMING PLAN ON SHEET S-2 SPECIFIES NEW W12X22
 STEEL BEAMS. DETAILS ON SHEET S-3 WERE NOT REVISED TO
 SHOW THE CONNECTIONS OF WOOD JOISTS TO THE STEEL BEAM.
 PROVIDE DETAILS FOR:
 A) CONNECTION OF WOOD JOIST TO STEEL BEAM. SEC. R301.1
 FBC 2010.
  
 B) CONNECTION OF 3/4" PLYWOOD TO THE STEED BEAM. SEC.
 R301.1 FBC 2010.
  
 C) CONNECTION OF 1X6 T&G WOOD CEILING TO STEEL BEAM.
 SEC. R301.1 FBC 2010.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON
 DETAILS ON SHEET S-3.
 SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-30 Cont ID  
Sent By jgomez Date 2016-06-30 Time 19:20 Rev Time 0.00
Received By jgomez Date 2016-06-30 Time 17:35 Sent To  
Notes
2016-06-30 17:47:55RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ORIGINAL COMMENT:
 1- ORIGINAL APPROVED PLANS DON'T INCLUDE FLAT ROOF
 SYSTEMS. ENGINEER OF RECORD NEEDS TO REVISE PLANS
 SPECIFYING THE PROPOSED FLAT ROOF.
 PROVIDE TWO SIGNED AND SEALED DRAWINGS SHOWING THE
 REVISION. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 RESPONSE:
 A) REVISED DRAWING S-2 SPECIFIES "MODIFIED BITUMEN
 ROOFING OVER 3/4" PLYWOOD SHEATHING (PER NOA
 #13-1022.15, 13-0416.05, AND #12-1219.02)". IT IS NOT
 CLEAR WHAT IS GOING TO BE THE FINISH ROOF MATERIAL.
 SPECIFIED NOA'S ARE FOR THREE DIFFERENT TYPES OF
 ASSEMBLIES BY DIFFERENT MANUFACTURER'S. NEED TO PROVIDE
 THE FOLLOWING:
 (1)IDENTIFY WHICH NOA IS GOING TO BE USED IN THIS ROOF
 DECK, THEN PROVIDE COMPLETE NOA (2 COPIES).
 (2) IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 USED.
 (3) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA. (NOTE: ASSEMBLIES WITH GENERAL LIMITATION
 #9 CAN NOT BE USED BECAUSE THEY DON'T ALLOW RAS 117
 CALCULATIONS).
  
  
 ORIGINAL COMMENT:
 2- FLAT ROOF NOA 11-0601.10 SUBMITTED IS NOT DESIGNED
 FOR FLAT ROOF. THIS NOA IS AN UNDERLAYMENT FOR PITCHED.
 ROOFS. REVISE AS REQUIRED.
 (A) PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF
 SYSTEM THAT IS DESIGNED FOR THE ROOF DECK FINISH AS
 SPECIFIED ON PLANS.
 FAC 61G20-3.002(33).
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
 (B) CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE USED FROM
 THE PRODUCT APPROVAL RE-SUBMITTED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
  
 (C) IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES, THEN SIGNED AND SEALED RAS
 117 CALCULATIONS ARE REQUIRED. SEE PRODUCT APPROVAL
 SUBMITTED. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
  
 (D) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) FLAT ROOF PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 SEE COMMENTS FOR ITEM #1 ABOVE AND COORDINATE
 ACCORDINGLY.
  
 ORIGINAL COMMENT:
 3- THIS FLAT ROOF SYSTEM WAS NOT PART OF THE APPROVED
 PLANS. SPECIFY THE ADDITIONAL VALUE FOR THE NEW FLAT
 ROOF AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
 RESPONSE:
 THERE ARE MORE REVISION SHOWN ON SHEET S-2. REVISED
 PLAN SHOW NEW W12X22 STEEL BEAMS INSTEAD OF GLU LAM
 BEAMS. SPECIFY THE ADDITIONAL VALUE BASED ON THE
 PROPOSED REVISIONS. INCLUDE THE ENGINEER'S DESIGN FEES
 AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS
  
 NEW COMMENT:
 4- PATIO FRAMING PLAN ON SHEET S-2 SPECIFIES NEW W12X22
 STEEL BEAMS. DETAILS ON SHEET S-3 WERE NOT REVISED TO
 SHOW THE CONNECTIONS OF WOOD JOISTS TO THE STEEL BEAM.
 PROVIDE DETAILS FOR:
 A) CONNECTION OF WOOD JOIST TO STEEL BEAM. SEC. R301.1
 FBC 2010.
  
 B) CONNECTION OF 3/4" PLYWOOD TO THE STEED BEAM. SEC.
 R301.1 FBC 2010.
  
 C) CONNECTION OF 1X6 T&G WOOD CEILING TO STEEL BEAM.
 SEC. R301.1 FBC 2010.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON
 DETAILS ON SHEET S-3.
 SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-06-24 Cont ID  
Sent By jgomez Date 2016-06-24 Time 07:43 Rev Time 0.00
Received By jgomez Date 2016-06-24 Time 07:39 Sent To  
Notes
2016-06-24 15:41:02RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ORIGINAL APPROVED PLANS DON'T INCLUDE FLAT ROOF
 SYSTEMS. ENGINEER OF RECORD NEEDS TO REVISE PLANS
 SPECIFYING THE PROPOSED FLAT ROOF.
 PROVIDE TWO SIGNED AND SEALED DRAWINGS SHOWING THE
 REVISION. SEC. R301 OF 2010 FBC-RESIDENTIAL. .
  
 2- FLAT ROOF NOA 11-0601.10 SUBMITTED IS NOT DESIGNED
 FOR FLAT ROOF. THIS NOA IS AN UNDERLAYMENT FOR PITCHED.
 ROOFS. REVISE AS REQUIRED.
 (A) PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF
 SYSTEM THAT IS DESIGNED FOR THE ROOF DECK FINISH AS
 SPECIFIED ON PLANS.
 FAC 61G20-3.002(33).
  
 (B) CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE USED FROM
 THE PRODUCT APPROVAL RE-SUBMITTED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 (C) IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES, THEN SIGNED AND SEALED RAS
 117 CALCULATIONS ARE REQUIRED. SEE PRODUCT APPROVAL
 SUBMITTED. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 (D) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) FLAT ROOF PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- THIS FLAT ROOF SYSTEM WAS NOT PART OF THE APPROVED
 PLANS. SPECIFY THE ADDITIONAL VALUE FOR THE NEW FLAT
 ROOF AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2018-07-03 Cont ID  
Sent By jgomez Date 2018-07-03 Time 09:26 Rev Time 0.00
Received By jgomez Date 2018-06-27 Time 15:23 Sent To I
Notes
2018-06-28 15:24:10RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2018-06-05 Cont ID  
Sent By jgomez Date 2018-06-05 Time 15:21 Rev Time 0.00
Received By jgomez Date 2018-06-05 Time 14:50 Sent To  
Notes
2018-06-05 14:51:15RAS 117 CALCS SUBMITTED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2018-03-08 Cont ID  
Sent By jgomez Date 2018-03-08 Time 12:08 Rev Time 0.00
Received By jgomez Date 2018-02-16 Time 15:16 Sent To I
Notes
2018-02-20 15:16:19RESUB OF REVISION ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2017-11-02 Cont ID  
Sent By jgomez Date 2017-11-02 Time 10:52 Rev Time 0.00
Received By jgomez Date 2017-10-23 Time 10:30 Sent To  
Notes
2017-10-24 10:30:49RESUB OF REVISION ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-08-16 Cont ID  
Sent By jgomez Date 2017-08-16 Time 14:00 Rev Time 0.00
Received By jgomez Date 2017-08-11 Time 17:35 Sent To  
Notes
2017-08-11 17:35:35REVISION RE-SUBMITTAL ON JULIO'S DESK. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-02-10 Cont ID  
Sent By jgomez Date 2017-02-10 Time 14:33 Rev Time 0.00
Received By jgomez Date 2017-02-03 Time 16:07 Sent To  
Notes
2017-02-03 16:07:19JGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-25 Cont ID  
Sent By jgomez Date 2016-07-25 Time 15:15 Rev Time 0.00
Received By jgomez Date 2016-07-15 Time 13:39 Sent To  
Notes
2016-07-15 13:40:00SKENNEDY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-30 Cont ID  
Sent By jgomez Date 2016-06-30 Time 17:35 Rev Time 0.00
Received By jgomez Date 2016-06-29 Time 09:23 Sent To  
Notes
2016-06-30 09:23:35RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-24 Cont ID  
Sent By jgomez Date 2016-06-24 Time 07:43 Rev Time 0.00
Received By jgomez Date 2016-06-22 Time 09:00 Sent To B
Notes
***NONE***