Plan Review Details - Permit 16061268
Plan Review Stops For Permit 16061268
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-02-06 Cont ID  
Sent By cthroop Date 2017-02-06 Time 14:03 Rev Time 0.00
Received By cthroop Date 2017-02-06 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-01-19 Cont ID  
Sent By vperez Date 2017-01-19 Time 14:34 Rev Time 0.00
Received By vperez Date 2017-01-19 Time 14:34 Sent To B
Notes
2017-01-12 12:45:45SENT TO PLUMBING FIRST
  
 VP

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-08-01 Cont ID  
Sent By vperez Date 2016-08-01 Time 10:06 Rev Time 0.00
Received By vperez Date 2016-08-01 Time 10:04 Sent To  
Notes
2016-08-01 10:06:082ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS:
  
 1. PLEASE ADDRESS PENDING PLUMBING REVIEWER COMMENT FOR
 AN ELECTRICAL APPROVAL.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-06-30 Cont ID  
Sent By vperez Date 2016-06-30 Time 13:29 Rev Time 0.00
Received By vperez Date 2016-06-30 Time 13:26 Sent To  
Notes
2016-06-30 13:29:17INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADDRESS PENDING PLUMBING REVIEWER COMMENT FOR
 AN ELECTRICAL APPROVAL.
 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-02-06 Cont ID  
Sent By cthroop Date 2017-02-06 Time 14:03 Rev Time 0.00
Received By cthroop Date 2017-01-10 Time 14:43 Sent To  
Notes
2017-01-12 12:46:07SENT TO PLUMBING FIRST
2017-01-10 14:43:30RESUB ROUTED TO VPEREZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-08-01 Cont ID  
Sent By vperez Date 2016-08-01 Time 10:06 Rev Time 0.00
Received By vperez Date 2016-08-01 Time 10:06 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-06-30 Cont ID  
Sent By vperez Date 2016-06-30 Time 13:30 Rev Time 0.00
Received By vperez Date 2016-06-30 Time 13:30 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-01-17 Cont ID  
Sent By tklarge Date 2017-01-17 Time 05:15 Rev Time 0.00
Received By tklarge Date 2017-01-17 Time 04:43 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-07-29 Cont ID  
Sent By tklarge Date 2016-07-29 Time 13:23 Rev Time 0.00
Received By tklarge Date 2016-07-29 Time 12:24 Sent To  
Notes
2016-07-29 12:57:291) INDICATE ON THE SPECIFICATION SHEETS WHICH HOSE
 PRODUCT WILL BE USED WITH WHAT CHEMICALS. WPB AMEND. TO
 FBC SEC.107.2.1.
 2) THE SUBMITTED PLAN SHALL BE SIGNED AND SEALED BY THE
 LANDSCAPE ARCHITECT.FAC 61G10-11.010
 3) SHOW THE SIZES OF THE CHEMICAL TANKS ON THE
 PLANS.WPB AMEND. TO FBC SEC.107.2.1.
 4) SUBMIT DETAILS AS TO HOW THE CHEMICAL TANKS WILL BE
 ANCHORED TO WITHSTAND THE 170 MPH WIND LOAD
 REQUIREMENTS OF 2014 FBC SEC. 1609.
 5) INDICATE ON THE PLANS THE TYPE OF CONTAINMENT THAT
 IS BEING PROVIDED AND THE CAPACITY OF THE CONTAINMENT
 IN RELATION TO THE SIZE OF THE CHEMICAL TANKS ( 110%,
 125%, ETC.).WPB AMEND. TO FBC SEC.107.2.1.
 6) SUBMIT DETAILS AS TO HOW THE PIPING WILL BE ATTACHED
 TO THE CONCRETE PAD
 7) THE KURIYAMA ORV HOSE IS MADE FROM PVC. SUBMIT
 MANUFACTURER'S SPECIFICATIONS AS TO HOW THE HOSE WILL
 BE PROTECTED FROM UV RAYS IF EXPOSED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-30 Cont ID  
Sent By vperez Date 2016-06-30 Time 13:30 Rev Time 0.00
Received By tklarge Date 2016-06-30 Time 05:57 Sent To  
Notes
2016-06-30 06:11:271) NONE OF THE REQUIREMENTS OF MY PROVISO HAVE BEEN
 SUBMITTED. SUBMIT COMPLETE PLANS, PIPING DETAILS, PIPE
 SIZES, MSDS INFORMATION,SIGNED AND SEALED DRAWINGS,
 ETC., ETC.,
 2) SUBMIT DRAWINGS THAT ARE LEGIBLE. THE PRINTING ON
 THE 8 1/2 X 11 SHEETS IS TOO SMALL TO READ.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  