Plan Review Details - Permit 16061264
Plan Review Stops For Permit 16061264
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-07-05 Cont ID  
Sent By jwitmer Date 2016-07-05 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2016-06-29 Time 07:06 Sent To  
Notes
2016-06-29 07:07:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061264
 ADD: 420 6TH ST.
 CONT: TRI GENERAL CONTRACTORS
 TEL: 561-324-6944
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON.JULY 05/ 2016
 ACTION: DENIED
  
 1) PLEASE PROVIDE A COMPLETE SET OF FLOOR PLANS SHOWING
 THE 1ST FLOOR AND WHAT EITHER APPEARS TO BE A MEZANINE
 OR A 2ND FLOOR. PLEASE PROVIDE THE SQUARE FOOT FLOOR
 AREA OF THE MEZANINE/ 2ND FLOOR AS WELL AS THE OPEN
 AREA OF THE 1ST FLOOR TO DETERMINE THE FLOOR AREA AND
 USAGE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN.
  
 107.3.5.1.1 COMMERCIAL BUILDINGS:BUILDING
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS, REQUIRED OR NOT
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS: STAIR & 2ND FLOOR LOADS
 WIND REQUIREMENTS IF WINDOWS AND DOORS ARE BEING ADDED
 OR ALTERED
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
  
 2) THE LAST KNOWN USE FOR THIS SPACE WAS AN WAREHOUSE
 AND ACCESSORY OFFICE OCCUPANCY PERMIT # 08040438.
 PLEASE SEE THE 2014 FBC-EXISITNG BUILDING CODE
 SECTION 1001.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THE APPLICATION, PLANS NOR THE TITLE BLOCK
 INDICATE THERE IS A CHANGE IN OCCUPANCY.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2) EXST. BLDG. CODE SECTION 1005 MEANS OF EGRESS.
 1005.1 GENERAL. MEANS OF EGRESS IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-07-13 Cont ID  
Sent By vperez Date 2016-07-13 Time 11:05 Rev Time 0.00
Received By vperez Date 2016-07-13 Time 11:03 Sent To  
Notes
2016-07-13 11:05:40INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE SEE BUILDING AND FIRE COMMENTS REGARDING
 OCCUPANCY CHANGE. A COMPLETE REVIEW WILL NOT BE
 PERFORMED AT THIS TIME. RESUBMIT
 2. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-06-23 Cont ID  
Sent By wjolin Date 2016-06-23 Time 13:29 Rev Time 0.00
Received By wjolin Date 2016-06-23 Time 13:12 Sent To  
Notes
2016-06-23 13:29:12420 6TH STREET
 PERMIT #16061264
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PREVIOUS RENOVATION/ADDITION TO THIS ADDRESS
 (PERMIT #08040438) SHOWS THE FIRST FLOOR AS BEING A
 STORAGE OCCUPANCY. THE CURRENT PLANS SUBMITTED FOR
 ACCESSIBLE RESTROOMS INDICATE THE OCCUPANCY HAS CHANGED
 TO AN ASSEMBLY OCCUPANCY. SUBMIT PLANS AND PERMIT FOR A
 CHANGE OF OCCUPANCY. PROVIDE A LIFE SAFETY PLAN SHOWING
 ALL OCCUPANCY TYPES, EXITS, FIRE RATED SEPARATIONS,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-07-13 Cont ID  
Sent By vperez Date 2016-07-13 Time 11:05 Rev Time 0.00
Received By vperez Date 2016-07-13 Time 11:05 Sent To  
Notes
2016-06-22 15:44:00B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-07-05 Cont ID  
Sent By jwitmer Date 2016-07-05 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2016-07-05 Time 14:49 Sent To  
Notes
2016-07-05 14:49:58BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-07-08 Cont ID  
Sent By ccole Date 2016-07-08 Time 14:52 Rev Time 0.00
Received By ccole Date 2016-07-08 Time 14:49 Sent To  
Notes
2016-07-08 15:09:441ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT 316061264
 7/8/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE MECHANICAL PLANS THAT INCLUDE AN AC LAYOUT
 PLAN, AND A EXHAUST VENTILATION PLAN AND DETAILS FOR
 THE NEW BATHROOMS- SEE TABLE 403.3.
  
 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION
 AND PROVIDE ENERGY CALCULATIONS FOR THE NEW OCCUPANCY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-06-27 Cont ID  
Sent By gearl Date 2016-06-27 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2016-06-24 Time 10:00 Sent To  
Notes
2016-06-24 17:11:391ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
  
 1. WATER FOUNTAIN REQUIRED FOR CHANGE OF OCCUPANCY
 SHALL COMPLY WITH FBC PL [B] 410.2 MINIMUM NUMBER.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 FBC PL TABLE 403.1/ A DRINKING FOUNTAIN COMPILING WITH
 FBC ACC 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 2. A SERVICE SINK IS REQUIRED FOR CHANGE OF OCCUPANCY
 SHALL COMPLY WITH FBC PL TABLE 403.1
  
 3. PLEASE PROVIDE WATER RISER DIAGRAM .PER WPB AMEND TO
 FBC 107.2.1
  
 4. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET SHALL COMPLY WITHE FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 4. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE LAVATORY'S
 SHALL COMPLY WITHE FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE WATER
 FOUNTAIN SHALL COMPLY WITHE FBC ACC 602.2 CLEAR FLOOR
 SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6. THE DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
  
 EXCEPTIONS:
  
 1. DOORS TO A TOILET ROOM OR BATHING ROOM FOR A SINGLE
 OCCUPANT ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT
 FOR COMMON USE OR PUBLIC USE SHALL BE PERMITTED TO
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE PROVIDED
 THE SWING OF THE DOOR CAN BE REVERSED TO COMPLY WITH
 603.2.3.
  
 2. WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
  
 7. TOILET SHALL COMPLY WITH FBC ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 8. GRAB BARS SHALL COMPLY WITH FBC ACC 609.4 POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
  
  
  
  
  
  
 DISREGARD COMMENTS BELOW
2016-06-24 09:59:59NEED TO CORRECT DRAWING OF VENTING FOR FIXTURES NEED TO
 HAVE BETWEEN W/C AND LAV. NEED TO HAVE SIZE OF VENTS ON
 DRAWING

Review Stop Z ZONING
Rev No 1 Status P Date 2016-07-25 Cont ID  
Sent By aaponte Date 2016-07-25 Time 17:09 Rev Time 0.00
Received By aaponte Date 2016-07-25 Time 17:09 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy