2016-06-27 16:35:36 | ****CORRECTIONS**** |
| |
| ART LANGE - BUILDING INSPECTOR |
| 561-805-6667 [email protected] |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| RESIDENTIAL CODE 2015 5TH EDITION |
| |
| 1. PLEASE REVISE THE PERMITTED VALUE TO INCLUDE THE |
| SCOPE OF THE NEW WORK INCLUDED IN THE REVISIONS. |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 2. REVISE LEVEL OF ALTERATION TO COMPLY WITH THE |
| EXISTING BUILDING CODE SEC 505 LEVEL 3 ALTERATION. |
| |
| 3. REVISE EXISTING FLOOR PLAN TO INCLUDE THE NEW SCOPE |
| OF WORK, |
| |
| 4. PLEAASE SHOW A DETAIL FOR THE BEARING WALL BETWEEN |
| KITCHEN AND DINNING ROOM. INCLUDE FRAMING DETAIL AND |
| POINT LOAD METHOD. FRC602 |
| |
| 5. SHOW METHOD OF WALL ATTACHMENT. INCLUDE A STRAPPING, |
| BOLTING SPECIFICATIONS AND DETAILS. |
| |
| 6. THE NEW PLANS HAVE VARIOUS FRAMING DETAILS. SHOW THE |
| LOCATION FOR THESE ON THE PLANS. |
| |
| |